Intent
To achieve increasing levels of energy performance beyond the prerequisite standard to reduce environmental and economic harms associated with excessive energy use and greenhouse gas emissions that disproportionately impact frontline communities.
Requirements
Analyze efficiency measures during the design process and account for the results in design decision-making. Analysis can include energy simulation of efficiency opportunities, energy simulation analyses for similar projects, or published data from energy analyses performed for similar projects (such as AEDGs).
Analyze efficiency measures focused on load reduction and HVAC-related strategies; passive measures are acceptable. Project the potential energy savings and cost implications for all affected systems.
Select one of the options below.
Option 1. Tenant-Level Energy Performance Compliance (4–24 points)
Demonstrate a Performance Cost Index (PCI)1 below the Performance Cost Index Target (PCIt) calculated in accordance with Section 4.2.1.1 of ANSI/ASHRAE/IESNA Standard 90.1-2016, Appendix G, Table 4.2.1.3. For mixed use projects, the required PCI shall be calculated by using an area weighted average of the building types.
Calculate the PCI, PCIt, and percentage improvement using metrics of cost and greenhouse gas (GHG) emissions.
Total LEED points for EAc Optimize Energy Performance are determined by summing the points documented in Table 1 (energy cost metric) plus the points documented in Table 2 (GHG emissions metric), where points for each Table are determined based on the project percent improvement PCI below the PCIt documented for each metric.
Table 1. Points for percentage improvement in energy performance – Percent Cost PCI below PCIt (12 points)
ID+C
|
Points
|
0%1
|
4
|
3%
|
5
|
6%
|
6
|
9%
|
7
|
12%
|
8
|
15%
|
9
|
18%
|
10
|
21%
|
11
|
24%
|
12
|
Table 2. Points for percentage improvement in energy performance – Percent Greenhouse Gas Emissions PCI below PCIt (12 points ID+C)
ID+C
|
Points
|
0%1
|
4
|
3%
|
5
|
6%
|
6
|
9%
|
7
|
12%
|
8
|
18%
|
9
|
25%
|
10
|
35%
|
11
|
50%
|
12
|
Table 1 and Table 2 Notes:
1. *0% improvement is based on
base building compliance with ASHRAE 90.1-2016 requirements.
2. Renewable Energy:
- On-site renewable energy: For Table 1 and Table 2, on-site or on-campus renewable energy that meets ASHRAE Standard 90.1-2016 Section G 2.4.1 requirements for on-site renewable may be subtracted from the Proposed Building Performance in accordance with ASHRAE Standard 90.1-2016 Section G 2.4.1.
- For the Table 2 greenhouse gas emissions metric, Tier 2 New off-site renewables documented in EA Credit Renewable Energy may be subtracted from proposed greenhouse gas emissions for electricity prior to calculating proposed building performance. Projects in locations where hourly electric greenhouse gas emissions factors are available must document performance for the baseline, proposed, and renewable generation using hourly electric emissions factors.
OR
Option 2. Prescriptive Compliance (1–17 points)
Use any combination of the strategies in any or all of the categories below.
To be eligible for Option 2, projects must use the ASHRAE 90.1-2016 Prescriptive compliance path in EA Prerequisite Minimum Energy Performance. To be eligible for ASHRAE Advanced Energy Design Guide (AEDG) envelope and lighting strategies, the project space must meet the Scope requirements of the applicable AEDGs (or combination of AEDGs for mixed use). To be eligible for AEDG HVAC strategies, the entire building where the project is located must meet the Scope requirements of the applicable AEDGs.
Base Building Systems (1-5 points)
For
base building systems that serve the project, as well as any applicable improvements that are part of the project, document compliance with the following according to
base building type and climate zone.
Building Envelope (1-2 points)
- Advanced Energy Design Guides
- Comply with the recommendations in the appropriate ASHRAE 50% Advanced Energy Design Guide for all roofs, walls, floors, slabs, doors, vestibules, and continuous air barriers. (1 point)
AND / OR
- Comply with the recommendations in the appropriate ASHRAE 50% Advanced Energy Design Guide for all vertical fenestration.
OR
- Climate Zones 1 – 2:
- Thermal Mass Enclosure: More than 50% of opaque above-grade wall area meets ASHRAE 90.1-2016 definition for “mass wall”; and more than 50% of floor area meets ASHRAE 90.1-2016 definition for “mass floor” (1 point)
AND / OR
- Demonstrate a 25% envelope UA reduction beyond ASHRAE 90.1-2016 prescriptive envelope requirements (1 point)
OR
- Climate Zones 3 – 8:
- Demonstrate an envelope UA reduction beyond ASHRAE 90.1-2016 prescriptive envelope requirements:
- 25% UA reduction (1 point)
- 50% UA reduction (1 point)
HVAC and Service Water Heating Equipment Efficiency Systems (1 - 3 points)
- Advanced Energy Design Guides: For all base building and tenant HVAC systems that serve the project, comply with the HVAC efficiency and control recommendations in the appropriate ASHRAE 50% Advanced Energy Design Guide. (3 points)
OR
- Demonstrate an improvement beyond ASHRAE/ASHRAE/IESNA Standard 90.1–2016 prescriptive requirements for the following base building and tenant systems serving the project space:
- Reduction in fan power total allowance of 30% (1 point)
AND / OR
- Improvement in efficiency for at least 75% of the combined cooling, heating, and service water heating capacity:
- 15% (1 point)
- 30% (2 points)
-
Electric resistance heating except heat pump auxiliary heat must be included in total capacity.
Tenant Systems (1-12 points)
Interior Lighting Systems (1–7 points)
- Lighting Power Density (1–5 points) Reduce connected lighting power density below that allowed by ASHRAE/IESNA Standard 90.1–2016, either using the space-by-space method or applying the whole-building lighting power allowance to the entire tenant space. Points are awarded according to Table 3.
Table 3. Points for percentage reduction in lighting power density
Percentage below standard LPD
|
Points
|
10%
|
1
|
20%
|
2
|
30%
|
3
|
40%
|
4
|
50%
|
5
|
Daylighting Controls (1–2 points)
- Daylighting Controls (1-2 points) Install daylight-responsive controls for a given percentage of connected lighting load (lighting in non-regularly occupied space with occupant sensor controls may be excluded from connected lighting load).
- 35% (1 point)
- 70% (2 points)
Equipment and Appliances (1–5 points)
Install a percentage (by rated power) of eligible equipment and appliances meeting the following requirements:
- ENERGY STAR equipment including appliances, office equipment, electronics, and commercial food service equipment (lighting and building envelope products are excluded from this credit). (Electronic Product Environmental Assessment Tool (EPEAT) equipment may be used in lieu of Energy Star equipment where applicable).
- Prescriptive commercial kitchen and refrigeration equipment requirements listed in Appendix 3, Table 1.
The project scope of work must include at least 0.25 Watts per square foot of eligible equipment to apply this strategy, either limited to the eligible equipment within the project scope of work, or including all new and existing equipment. For existing equipment, ENERGY STAR or
EPEAT requirements may be referenced to the date of purchase of the equipment.
Percent of Eligible Equipment Installed by
Rated Power:
- 20% (1 point)
- 40% (2 points)
- 60% (3 points)
- 80% (4 points)
- 100% (5 points)