EBOM-2009 IEQc2.3: Occupant Comfort—Thermal Comfort Monitoring

  • EBOM IEQc2.3 Occupant Comfort Diagram
  • Occupant comfort, not HVAC performance

    You’ll need to implement two forms of thermal comfort monitoring for this credit:

    • Continuous monitoring of air temperature and humidity
    • Periodic measurements of air speed and radiant temperature

    This credit addresses the conditions that building occupants experience, not the measured conditions inside the ductwork or HVAC system.

    The cost of the credit will vary depending on how much equipment is already installed or available in-house and whether building staff can take the required periodic measurements within occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space..

    Automatic sensors needed…

    Air temperature and humidity measurements must be taken on 15-minute intervals, at a maximum. Existing sensors integrated into a building automation system (BAS)A building automation system (BAS) uses computer-based monitoring to coordinate, organize, and optimize building control subsystems, including lighting, equipment scheduling, and alarm reporting. can make continuous monitoring and data trending easy, while the absence of a BAS or automatic sensors will make this credit very difficult.

    …But so are handheld measurements

    IR temp sensorAn Infrared heat sensor gun may be used to take radiant temperature measurements.Project teams often overlook or misunderstand the requirements for measuring radiant temperature and air speed. These measurements must be taken at least once a year (under normal operating conditions) in the occupied spaces, and the use of handheld instruments is the only practical approach. Under no circumstances do velocity or temperature readings within the ventilation system satisfy the requirements for taking these measurements within occupied spaces.

    Radiant temperature measurements take into account the phenomenon that a heated space air may feel cold if surrounded by cold windows that absorb a great deal of heat radiated by people. Conversely, a room with cool air temperature may feel warm if occupants are absorbing radiation from the sun or a hot exterior wall, for example. Measuring radiant temperature gives you more information to take appropriate corrective actions to improve occupant comfort.

    Stay within acceptable ranges

    You must establish comfort criteriaComfort criteria are specific design conditions that take into account temperature, humidity, air speed, outdoor temperature, outdoor humidity, seasonal clothing, and expected activity. (ASHRAE 55–2004) based on ASHRAE Standard 55-2004 that is appropriate for your specific building.

    If you find that conditions are outside acceptable ranges, you must take corrective actions to correct any problems.

    Consider these questions when approaching this credit:

    • Are you performing continuous monitoring of air temperature and humidity in your building? If not, can appropriate sensors be added to cover an adequate portion of occupied spaces?
    • Do you have a system in place to respond to thermal comfort system alarms or occupant complaints with appropriate corrective actions in a timely manner?
    • Are building engineers or third party technicians available and capable of performing periodic testing of air speed and radiant temperature?

    FAQs for LEED-EBOM IEQc2.3

    The LEED Reference Guide states that we need to have at least one temperature sensor in each HVAC zone. What defines an HVAC zone for this credit?

    An HVAC zone is a group of spaces or a single space with individual temperature control from a shared HVAC system. So, in order to meet the credit requirements you need to have at least one temperature sensor for each zone with individual control. Note that when pursuing this credit, be sure to also delineate between HVAC zones that contain both perimeter and core spaces, zones that have perimeter areas with different orientations, or zones that have substantially different usage types may require additional temperature sensors.

    What type of measurement instrument do we need to use to monitor radiant temperature in occupied spaces?

    ASHRAE-55 does not require a specific device, but requires you to measure mean radiant temperature (MRT). Measurements from both black globe thermometers and infrared thermometers can be used to calculate MRT. See ASHRAE Fundamentals 2005 for additional details on calculations.

Legend

  • Best Practices
  • Gotcha
  • Action Steps
  • Cost Tip

Before the Performance Period

Expand All

  • Keep in mind that this credit focuses on the conditions that building occupants experience in the course of their normal daily activities, not the measured conditions inside the ductwork or the HVAC system.


  • Determine the best way to continuously monitor air temperature and relative humidity (RH) in your building.  


  • Presence of a building automation system (BAS) should make air temperature and RH measurements relatively easy. If you don’t use a BAS, you could install sensors in occupied spaces.


  • All sensors must be positioned 4–72 inches above the floor.


  • The maximum sample interval for continuous monitoring is 15 minutes.


  • Location of existing BAS sensors may not be adequate to meet the credit requirements, so you may need to install additional sensors.  


  • Make sure that there is at least one air temperature sensor located in each HVAC zone.


  • Use additional sensors if space use and configuration makes it likely that a single measurement point will not be representative. Use separate sensors for perimeter and core areas within a single HVAC zone and equip rooms with additional sensors if they experience internal gains or solar gains that are higher than average for the building.


  • Make sure to have at least one humidity sensor in each distinct humidity zone in the building. Humidity zones are not necessarily aligned with temperature zones, so it may be acceptable to have fewer humidity sensors than temperature sensors.


  • Humidity zone boundaries are defined by differences in space use and are affected by differences in the ability of cooling control systems to manage humidity levels. Examples of zones that may have the same temperature settings as other zones but different humidity levels include kitchens, locker rooms, and swimming pools. Perform a thorough assessment of your building using mechanical drawings and floorplans and a full walkthrough to map out each of the zones and determine required locations for humidity sensors. The LEED-EBOM Reference Guide and ASHRAE 55-2004 provide useful guidelines for determining humidity zone boundaries in your building.


  • The need for additional sensors can be identified through the commissioning process. A building engineer or HVAC specialist can install these sensors.


  • System alarms, visible to a building manager or engineer as an email, pager, or text message, or in another form suitable for the building, must be set off when air temperature and humidity levels fall outside the acceptable thermal comfort ranges defined in ASHRAE 55-2004.


  • Establish a process for responding to system alarms and occupant comfort complaints with appropriate corrective action and in a timely manner. Regularly review thermal comfort conditions to identify opportunities for adjustments.


  • Establish a strategy for periodic measurements of radiant temperature and air speed at least once a year. These measurements are typically performed in occupied spaces using handheld devices, such as a globe thermometer or infrared heat sensor gun to measure radiant temperature and an anemometer to measure air speed.


  • Project teams often overlook or misunderstand the requirements for measuring radiant temperature and air speed. These measurements must be taken in the occupied spaces and the use of handheld instruments is the only practical approach. Under no circumstances do velocity or temperature readings within the ventilation system satisfy the requirements for air speed and radiant temperature measurements within occupied spaces.


  • The protocol and equipment used to perform these measurements must comply with Section 7 of ASHRAE 55-2004. This part of the ASHRAE standard addresses evaluation of the thermal environment and describes the required steps and equipment to properly take these measurements.


  • If a thorough commissioning process is also being pursued, these periodic measurement activities should likely be coordinated with that effort. A detailed IAQ audit might also be a chance to review thermal comfort monitoring and perform measurements.


  • Calibrate system sensors and actuators within the manufacturer’s recommended interval, maintain the associated records, and create a report for documentation purposes.


  • Costs will vary depending on the level of measurement and verification work that may be completed by in-house staff. There may be costs associated with installing additional sensors and measurement equipment for air temperature and humidity. It may be cheaper in some cases to purchase handheld measuring devices for building use and perform the periodic measurements in-house.

During the Performance Period

Expand All

  • Perform at least one set of measurements of radiant temperature and air speed in occupied building spaces.


  • You can take the measurements at any time during the year, as long as it represents normal conditions with normal building occupancy. For example, periodic measurements in an office should be taken during occupied weekday hours, not weekends or holidays when people aren’t around.


  • Trend the data for air temperature and humidity on an ongoing basis. This is not required for the credit, but will help confirm that conditions are falling within acceptable ranges. (See the Documentation Toolkit for an example.)


  • Ensure that system alarms are operating correctly and alarm occurrences are logged and tracked.


  • Communicate with relevant building personnel and ensure that they understand the procedures for delivering prompt adjustments or repairs in response to system alarms or occupant complaints.


  • Thermal comfort monitoring may uncover minor issues that require corrective action. Maintenance costs will vary from building to building depending on the mechanical systems that are in place. Tracking of system performance can be handled in-house at minimal cost.

  • USGBC

    Excerpted from LEED 2009 for Existing Buildings: Operations & Maintenance

    IEQ Credit 2.3: Occupant comfort - thermal comfort monitoring

    1 Point

    Intent

    To support the appropriate operations and maintenance of buildings and building systems so that they continue to meet target building performance goals over the long term and provide a comfortable thermal environment that supports the productivity and well-being of building occupants.

    Requirements

    Have in place a system for continuous tracking and optimization of systems that regulate indoor comfort and conditions (air temperature, humidity, air speed and radiant temperature) in occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space.. Have a permanent monitoring system to ensure ongoing building performance to the desired comfort criteriaComfort criteria are specific design conditions that take into account temperature, humidity, air speed, outdoor temperature, outdoor humidity, seasonal clothing, and expected activity. (ASHRAE 55–2004) as determined by either of the following standards:

    Option 1. ASHRAE standard 55-2004 or non-U.S. equivalent

    ASHRAE Standard 55-2004, Thermal Comfort Conditions for Human Occupancy (with errata but without addenda). Projects outside the U.S. may use a local equivalent to ASHRAE Standard 55-2004 Thermal Comfort Conditions for Human Occupancy.

    Option 2. ISO 7730: 2005 & CEN standard EN 15251: 2007

    Projects outside the U.S. may earn this credit by meeting the requirements of International Organization for Standardization (ISO) 7730, Ergonomics of the thermal environment, Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria; and CEN Standard EN 15251: 2007, Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics.

    The building must establish the following:

    • Continuous monitoring of, at a minimum, air temperature and humidity in occupied spaces. The sampling interval cannot exceed 15 minutes.
    • Periodic testing of air speed and radiant temperature in occupied spaces. Using handheld meters is permitted.
    • Alarms for conditions that require system adjustment or repair. Submit a list of the sensors, zone set-points and limit values that would trigger an alarm.
    • Procedures that deliver prompt adjustments or repairs in response to problems identified.

    All monitoring devices must be calibrated within the manufacturer’s recommended interval.

    Potential Technologies & Strategies

    Implement systematic monitoring of the actual performance of the building to the comfort criteriaComfort criteria are specific design conditions that take into account temperature, humidity, air speed, outdoor temperature, outdoor humidity, seasonal clothing, and expected activity. (ASHRAE 55–2004) defined by ASHRAE Standard 55-2004 (with errata but without addenda1).

    As appropriate, monitoring may include measurement and trending of temperatures, relative humidity, air speed and radiant temperatures at locations selected according to their variability and effect on occupants’ comfort.

    FOOTNOTES

    1 Project teams wishing to use ASHRAE approved addenda for the purposes of this prerequisite may do so at their discretion. Addenda must be applied consistently across all LEED credits.

Articles

Center for the Built Environment

This article from the Center for the Built Environment provides good information on the use of temperature sensors as part of the commissioning process.

Web Tools

Center for the Built Environment

The Center for the Built Environment (CBE) at U.C.–Berkeley provides good information on best practices involving HVAC equipment and indoor environmental quality.


ASHRAE

ASHRAE is the source to get information relating to ASHRAE Standard 55-2004, Thermal Environmental Conditions for Human Occupancy.

Technical Guides

IEQ Space Matrix

This spreadsheet categories dozens of specific space types according to how they should be applied under various IEQ credits. This document is essential if you have questions about how various unique space types should be treated.

Comfort Measurement Report

After taking radiant temperature and air speed measurements, document your results in a report like this one.

Trend Graphs

Graphing temperature and humidity data on an ongoing basis (as shown in this example with temperature data) is not required for the credit, but is a useful way to view the information that is gathered and note any anomalies.

LEED Online Forms: LEED-EBOM IEQ

The following links take you to the public, informational versions of the dynamic LEED Online forms for each EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems.-2009 IEQ credit. You'll need to fill out the live versions of these forms on LEED Online for each credit you hope to earn.

Version 4 forms (newest):

Version 3 forms:

These links are posted by LEEDuser with USGBC's permission. USGBC has certain usage restrictions for these forms; for more information, visit LEED Online and click "Sample Forms Download."

Sample LEED Online Form

This sample LEED Online form demonstrates through tips how to document IEQc2.3.

25 Comments

0
0
Peter Locke Sustainability Consulting Director McKinstry
Jun 12 2012
LEEDuser Member
59 Thumbs Up

Sample size for air speed measurements

Does anyone have a comment on the number of spaces (% of spaces?) that an air speed sample would need to include? I am working with a 3 story office space with ~100,000 sf of cubicles on each floor. Looking at the example in resources was not very clear. Thanks!

1
1
0
Jason Franken Sustainability Professional Sep 10 2012 LEEDuser Expert 5076 Thumbs Up

The distribution pattern of air speed testing will be dictated by ASHRAE 55-2004, Section 7, Evaluation of the Thermal Environment. In the most basic terms, the periodic air speed measurements must be made in occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space., but the criteria for determining the location of those measurements are defined in the ASHRAE guidance and will be based on the layout and configuration of your building's spaces.

Post a Reply
0
0
Allen Doyle Sustainability Manager University California Davis
Mar 21 2012
LEEDuser Member
43 Thumbs Up

skipping RH sensors and getting IEQ 2.3?

Is it possible that a climate could be benign enough that RH sensors would be redundant or unnecessary, and a project would still gain IEQ 2.3 compliance with temperature monitoring alone?
In our situation of moderate humidity and temperatures we rarely control for RH (except with museums, libraries, or with chilled beam applications, for example). We monitor temperature very frequently and control it very well. If we had logs of interior RH that demonstrate we usually have comfortable conditions the "natural way," (without controlling it in AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork.'s) could we get the point without installing all the RH sensors and energy consuming equipment?

1
2
0
Samantha Harrell LEED Project Reviewer certificate holder Mar 27 2012 Guest 1383 Thumbs Up

I suggest you reference LEED InterpretationLEED Interpretations are official answers to technical inquiries about implementing LEED on a project. They help people understand how their projects can meet LEED requirements and provide clarity on existing options. LEED Interpretations are to be used by any project certifying under an applicable rating system. All project teams are required to adhere to all LEED Interpretations posted before their registration date. This also applies to other addenda. Adherence to rulings posted after a project registers is optional, but strongly encouraged. LEED Interpretations are published in a searchable database at usgbc.org. 5484 in your submittal. This LI has not yet been considered for EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems. 2009 projects, so the reviewer may determine that it is applicable to your project. The LI states that "if it can be proven that maximum humidity levels will not be exceeded based on the local climate, then the humidity monitoring requirement will be waived. To demonstrate compliance, provide climate data that shows peak outdoor humidity levels will not be problematic for indoor comfort as defined by in ASHRAE Standard 55, and/or provide a summary of the psychrometric analysis (without contribution of air cooling) accompanied by a narrative."

2
2
0
Allen Doyle Sustainability Manager, University California Davis Mar 27 2012 LEEDuser Member 43 Thumbs Up

Thanks, Samantha,
We await the response to LI 5484.
As you might expect, we only measure RH where we control it, so we may need to deploy loggers.
Alternatively we can calculate indoor RH from outdoor RH. Here is a site or calculator that will do the above:
http://www.lenntech.com/calculators/humidity/relative-humidity.htm

I'm looking for:
1) the equation to plug into a spreadsheet
2) what percent excursions from comfort standards would be allowed?
3) Finding worst case situations:
high indoor RH: High outdoor temp and RH
Low indoor RH: Low outdoor temp and RH
4) A NOAA or weather site that would list both T and RH at the same time.

Post a Reply
0
0
Sonrisa Lucero Owner / Energy Engineer / Sustainability Consultant Sustainnovations, LLC
Oct 10 2011
LEEDuser Member
852 Thumbs Up

Radiant Temperature Measurement

In the picture on the "Bird's Eye View" page, there is a picture of an infrared thermometer. This would take the temperature of an object. However, in order to comply with this credit, it is my understanding that we must be in compliance with the testing proceedures outlined in ASHRAE 55 and therefore use a black globe thermometer. Has anyone had success with this credit using just a simple radiant thermometer? I don't want to buy something I don't need, but the attached spreadsheet in the documentation toolkit would suggest a black globe thermometer is appropriate as well.

Further, ASHRAE 55 requires that we do the testing on a Design temperature day. Does anyone know if GBCI has been strict enforcing this requirement? Hitting a design day is somewhat difficult to schedule! The weather won't share its calendar!

Thanks!

1
2
0
Jason Franken Sustainability Professional Nov 02 2011 LEEDuser Expert 5076 Thumbs Up

Sonrisa, I believe that either device (an infrared thermometer or a black globe thermometer) would be acceptable to take periodic radiant temperature readings. I could be wrong, but I don't think ASHRAE 55 excludes the use of infrared thermometers. Honestly, when LEED User was being built, we may have just had a better photo of an infrared thermometer to put on this page.

As far as the testing schedule, you don't have to hit on a perfect design day, but GBCI will want to see that you are being thoughtfull about scheduling the testing in an appropriate time of the year.

2
2
0
Jeremy Poling Senior Consultant, Goby Nov 28 2011 Guest 220 Thumbs Up

ASHRAE 55 does not require a specific device, but requires you to measure mean radiant temperature (MRT).

Neither globe thermometers nor infrared thermometers measure MRT, but both produce results that can be converted to mean radiant temperature. The two technologies would just require different equations to convert the measurements.

Globe thermometers are more common since they only require one measurement to determine mean radiant temperature. Their measurement can be converted to MRT via Equation 11 on page 14.29 of ASHRAE Fundamentals 2005.

Infrared thermometers will require at least six measurements for each point (top, bottom, four sides) which can be converted to MRT via Equation 50 on page 8.10 of ASHRAE Fundamentals 2005.

Post a Reply
0
0
Jean Marais b.i.g. Bechtold DesignBuilder Expert
Feb 08 2011
LEEDuser Member
5192 Thumbs Up

humidity sensors "for" occupied spaces or "in" occupied spaces

The credit language says "in", but could it mean "for". Temperature sensors in each zone makes sense, but I just read an article in ASHRAE journal completely trashing humidity sensors as being grossly inaccurate (+- 20%).

Surely humidity sensors only make sense where the humidity is controlled, i.e. at the central AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork.? My collegues have never heard of humidity sensors in occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space. in offices.

Does this credit only make sense if one has terminal units that regulate humidity?

Don't forget that humidity in a locker room is expected and the thermal comfort expectation there (percentage dissatisfied) would adjust.

1
2
0
Marcus Sheffer LEED Fellow, 7group Mar 12 2011 LEEDuser Expert 19756 Thumbs Up

Humidity sensors are not necessarily inaccurate but they do require frequent calibration to be useful.

They are more useful where humidity is being controlled but humidity is a significant contributor to thermal comfort and that is why they are required. One could certainly make the case that they only make sense in a retrofit if they regulate humidity.

2
2
0
Jeremy Kuhre Sustainable Buildings & Operations Manager, Sustainable Solutions Corporation Mar 13 2012 LEEDuser Member 411 Thumbs Up

Has anyone successfully earned this credit by installing humidity sensors at the AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. returns (as opposed to in occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space.)? We are considering each floor a single humidity zone, so it makes more sense for us to install the sensor at the AHU (one per floor) to get the most accurate picture of humidity on the entire floor.

I'm not questioning the validity of the credit here, just the particulars in meeting the requirements.

Post a Reply
0
0
Melissa Young Manager, Corporate Environmental Programs
Jan 31 2011
Guest
124 Thumbs Up

No BAS.

As it says above, achieving this credit without a BAS is difficult. What exactly needs to be done if we don't have a BAS? Is it enough to install temperature and humidity sensors in occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space.? Or does the data need to be collected in some way?

1
1
0
Tristan Roberts LEED AP BD+C, Editorial Director – LEEDuser, BuildingGreen, Inc. Feb 08 2011 LEEDuser Moderator

Melissa, installing sensors as you describe should meet the requirements, but you do also need to track the data generated and make sure thhat you're meeting relevant comfort criteriaComfort criteria are specific design conditions that take into account temperature, humidity, air speed, outdoor temperature, outdoor humidity, seasonal clothing, and expected activity. (ASHRAE 55–2004).

Post a Reply
0
0
Wendy Gibson
Nov 05 2010
LEEDuser Member
1024 Thumbs Up

10% exemption and sampling

On the first floor of our building we have restaurants that have their own HVAC system and maintain their own tempatures. The only thing we do is bill them their electricity. Can we exclude them from this credit as long as they are less than 10% of the buildign? They are not participating in our LEED pursuit.

Our building is 15 stories and is primarily office space and break rooms with microwave, sink and fridge in them. From the credit it appears that we only need 1 humidity sensor for each humidity zone... do we need humidity sensors in each office space and kitchen area or can it be a random sampling and if can be a random sampling how do we know what is enough? -

Finally, is it safe to assume restrooms without showers would be considered the same humidity zone as office space, but those with showers would need their own sensors.

1
1
0
Dan Ackerstein Principal, Ackerstein Sustainability, LLC Jan 11 2011 LEEDuser Expert 6394 Thumbs Up

Hello Wendy

- I certainly think you can exclude the restaurants if they are less than 10% of building square footage. They seem to fit the requirements for the exemption in every meaningful way.

- You are correct that EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems. requires only 1 sensor per humidity zone. However, rather than a random sampling, I would point to the language that encourages placing sensors in such a was so as to ensure they are 'representative of conditions'. This is not the most direct guidance, but I think it reflects the interest in placing sensors where they will give you the most relevant and useful information about humidity levels, as opposed to simply slapping one on a wall somewhere in the zone. Also, in terms of guiding the number of sensors, note that the Reference Guide acknowledges that the number of humidity sensors may be fewer than temperature sensors - this implicitly suggests that a guide to your starting point for the number of humidity sensors should be the number of temperature sensors. If those are somewhat consistent, I would think you're in good shape.

- I think that's a safe bet. Clearly a restroom with showers is in a class by itself. I assume that any restroom is likely to have higher general humidity levels than office space, but I would suspect the difference is marginal.

Hope that helps a little,

Dan

Post a Reply
0
0
David Grosdeck Property Manager Cassidy Turley
Sep 14 2010
Guest
304 Thumbs Up

HVAC Zone deffinition

Please provide additional clarification on "HVAC zone" for this credit. We have a 4 story building. Our current BAS has temperature sensors located on the 1st and 4th floors to provide adequate input to the BAS for Air handler control of supply air temperatures to each of the terminal units in the occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space.. We feel that this would meet the intent of the credit, provided we add Humidity sensors in designated "humidity zones". Please comment.

1
7
0
John Beeson Chief Mystic in Resident, betterENVIRONMENT, LLC Sep 16 2010 LEEDuser Member 1066 Thumbs Up

As stated, there must be at least one air temperature sensor located in each HVAC zone. As the intent is to provide a comfortable thermal environment, each occupied space should have some degree of monitoring. As stated in the LRG, pg. 405, "...if space uses and configurations make it likely that a single measurement point is not representative..." additional sensor would be required.

A 4 story building with only two temperature sensors, in my mind, would not meet the requirements. It would be unlikely that thermal comfort would be met in all occupied areas by all occupants.

2
7
0
David Grosdeck Property Manager, Cassidy Turley Sep 17 2010 Guest 304 Thumbs Up

I am still trying to figure this one out and really need clarification. The bigger picture is that I have a four story 486,000 square foot building split up into 6 "Cores". Each core has it's own air handler that is controlled by the BAS. Each core has temperature sensors on the 1st and 4th floor that send signals to the BAS to control supply air temperatures. Conditioned air is controlled, monitored, and provided to terminal boxes throughout the core. Each terminal box is controlled by a pneumatic thermostat for occupant comfort. Since we have pneumatic thermostats they do not report to the BAS but still provide the occupants a way to control space temperatures.

The recommendation above in the Before the Performance Period section says - "Make sure that there is at least one air temperature sensor located in each HVAC zone." Please define HVAC ZONE in this case.

In the larger picture, we contol and track supply air temperatures throughout each core of the building with our BAS. If you can extend the definition of a "Zone" in this case to correspond to our "Core" we feel comfortable that we meet the intent to provide, monitor, and track conditioned air in occupant spaces.

If "Zone" is defined as an area controlled by an individual thermostat then this credit becomes much more unreasonable and unobtainable. We have over 600 thermostats in the building! I feel it would be very wasteful to remove/replace/retrofit all the terminal boxes and thermostats to expensive DDC controls required to have each thermostat report to the BAS.

We have an excellent Energy Star score and our building engineers are constantly monitoring the BAS to make sure our occupants are comfortable. This is my first experience with a LEED EB project and really need help understanding and meeting the intent of this credit.

3
7
0
Paul C Sep 17 2010 Guest 1842 Thumbs Up

We have a 5 story multi-tenant office building and discussed with our engineer about defining HVAC zones. We believe the definition of a kitchen requires an exhaust fan so we have ruled all tenant kitchen/break rooms as still office space since they only include sinks, coffee machines...

We therefore will survey conditions throughout each floor and provide evidence as to why we are only using 5 (1 per floor) humidity sensors - assuming that our readings provide the evidence that humidity acorss the floor are same/consistent and there is no need to add additional sensors beyond one per floor.

4
7
0
John Beeson Chief Mystic in Resident, betterENVIRONMENT, LLC Sep 22 2010 LEEDuser Member 1066 Thumbs Up

David,

If each "core" is served by its own AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork., and the conditioned air from each core is controlled, monitored, and provided to terminal boxes throughout the core, then it would appear to be on the right path.

If understand this correctly, you have six cores running (vertically) through the bldg with air supplied by AHUs. The cores are tapped into by supply ducts at each floor level that serve termination boxes at various locations around the floors?

But please clarify for me: If it is the case that each core has temperature sensors on the 1st and 4th floor that send signals to the BAS to control supply air temperature, what happens on the 2nd and 3rd floors?

5
7
0
David Grosdeck Property Manager, Cassidy Turley Sep 22 2010 Guest 304 Thumbs Up

Thank you John. You do understand correctly on the supply ducts. They serve termination boxes at the various locations.

On the floor sensors, the BAS averages the temperatures for the 2nd and 3rd floor to adjust air temperatures. Is this acceptable?

6
7
0
John Beeson Chief Mystic in Resident, betterENVIRONMENT, LLC Sep 22 2010 LEEDuser Member 1066 Thumbs Up

David,

In my mind, the goal is to provide a comfortable thermal environment in all of the occupied spacesOccupied Spaces are defined as enclosed spaces that can accommodate human activities. Occupied spaces are further classified as regularly occupied or non-regularly occupied spaces based on the duration of the occupancy, individual or multi-occupant based on the quantity of occupants, and densely or non-densely occupied spaces based upon the concentration of occupants in the space. and to do this, the credit requires continuous monitoring of, at a minimum, air temperature and humidity in occupied spaces - that is, at least one air temperature sensor must be located in each HVAC zone. That being said, even though the "cores" might be within range, how does the BAS/managers know if the appropriate temps and humidity levels are being met in the actual occupied areas?

But, now, you got me thinking more. And I could be overthinking it. Do the termination boxes at the end of the supply ducts change the air temperature (warmer/cooler) and, consequently, the humidity?

7
7
0
David Grosdeck Property Manager, Cassidy Turley Sep 22 2010 Guest 304 Thumbs Up

I could add temperature sensors to each floor to provide continuous monitoring of temperatures. Humidity sensors would be added to defined humidity zones (kitchens, locker rooms, etc.)

The terminal boxes supply heated or cooled air at a temperature determined by the BAS to the occupied space until the individual thermostats are satisified.

This would be much easier to accomplish with a DDC system. However, the challenge of an Existing building is to provide comfort with the equipment we have. A DDC system with individual thermostat control/monitoring is just not economical to install in this large a facility. If a DDC system is the only way to achieve this credit it is just not possible and puts Existing Buildings at a disadvantage.

I think we are very close to achieving the intent of the credit. I appreciate your help in getting us farther along to obtain our goal. Let me know if you have additional comments or questions.

Thanks!

Post a Reply
0
0
Ashu Gupta Project Engineer
Jun 11 2010
Guest
529 Thumbs Up

Humidity Sensors

Is it necessary to install humidifier in every HVAC zone ?

1
1
0
Tristan Roberts LEED AP BD+C, Editorial Director – LEEDuser, BuildingGreen, Inc. Jun 11 2010 LEEDuser Moderator

For this credit, absolutely not. You simply need to measure humidity levels. Please see the detailed information on the requirements above in the credit language and Checklists tabs. (Paid membership required to see that content—and highly recommended.)

Post a Reply

Start a new LEED comment thread

May 19 2013
Type the characters you see in this picture. (verify using audio)
Type the characters you see in the picture above; if you can't read them, submit the form and a new image will be generated. Not case sensitive.

Copyright 2013 – BuildingGreen, Inc.