-
Upgrades? No. Changes? Probably
Meeting the LEED ventilation prerequisite is not likely to require substantial building upgrades, although it is likely to require some adjustments, such as altering minimum damper settings on existing equipment.
An in-house engineer or a third-party vendor can help you measure outdoor air flow in each air-handling unit and compare their performance against ASHRAE Standard 62.1-2007 requirements. ASHRAE and USGBC provide calculators for determining the required rates of outdoor air flow for your building based on floor area, actual occupancy, and other characteristics of the space and ventilation distribution system. Buildings that employ older ventilation equipment or unique ventilation solutions may have one or more air handling units that are unable to meet the ASHRAE 62.1-2007 requirements. In this scenario, you can still achieve this prerequisite by showing that these air handling units provide at least 10 cubic feet per minute per person of outside air under normal operating conditions.
Well-ventilated space will improve occupant comfort and productivity. Photo – YRG Sustainability
Achievable for naturally ventilated buildings
Naturally ventilated buildings must document compliance with a special section of the ASHRAE 62.1-2007 standard, and complete some specific measurements, but this should still be highly achievable for buildings with lots of windows or a well-designed engineered natural ventilation system.
Maintain good air quality along with energy performance
Reducing mechanical ventilation and outdoor air intake are easy ways to reduce energy consumption, but can compromise indoor air quality if not thoughtfully executed. This prerequisite and EAp2: Minimum Energy Efficiency Performance are often seen as being in conflict with each other, but IEQp1 is designed, in part, to ensure that energy efficiency in LEED-certified buildings does not come at the expense of good indoor air quality.
Regular inspection and preventive maintenance on mechanical equipment will help ensure optimal airflow in your building. Photo – YRG SustainabilityConsider these questions before pursuing this credit
- Is the building mechanically ventilated, naturally ventilated, or mixed-mode? ASHRAE Standard 62.1-2007 addresses natural and mechanical ventilation systems using different guidelines and criteria. Mixed-mode systems must demonstrate compliance while operating in mechanical mode only.
- Do you have a building automation system (BAS)A building automation system (BAS) uses computer-based monitoring to coordinate, organize, and optimize building control subsystems, including lighting, equipment scheduling, and alarm reporting. that measures outdoor air? If your building does not use a BAS to monitor the rate of outside air flow through the ventilation system, manual measurements of outside air flow must be taken at each air handling unit.
- Have the ventilation systems been tested or balanced in the last 2 years? If yes, do you have documentation on the measurements of outdoor air flow? Recent testing reports, which include ventilation rate procedure (VRP) calculations, may be used to compare measured outside air flow to the ASHRAE 62.1-2007 requirements.
- Do occupants and building maintenance staff feel that the building is well-ventilated? Does the air seem fresh? Stuffy? Odorous? Occupant feedback is a valuable early-detection tool to know if your ventilation system is operating properly and complying with ASHRAE 62.1-2007 standards.
- Do you have mechanical drawings that are helpful for managing ventilation systems and maintaining outdoor air flow calculations as required by ASHRAE? Do you have an HVAC preventative maintenance program? A set of accurate mechanical drawings will help you to determine where outside air flow measurements should be taken and provide manufacturer product information that can be useful in developing an ongoing preventive maintenance program to ensure proper system performance.
- Are your engineers trained and equipped to take outdoor air flow measurements? If not, is there an engineering firm that you can use to help with these tests?
LEED-EBOM IEQp1 FAQs
What if after our Preliminary Review we have to re-work the ventilation rate procedure calculations and find that we need to make corrections to the system in order to meet the prerequisite? Can we redo the outside air testing after making corrections? Would we need to update the performance period for all credits accordingly?
If for some reason you needed to make corrections to the ventilation system in order to meet the ventilation prerequisite during the review process, you could do so without having to reset the performance period for all of the performance based credits like EAp2. Outside air measurements can and must be redone to confirm that the systems meet the prerequisite after the corrections were made.
What if our systems do not meet the required outside air when systems are tested at worst-case conditions?
If the systems do not meet the required outside air during the initial testing the following actions should be taken:
- If the system (damper) set points for the worst case condition can be modified to supply sufficient outside air to meet the ASHRAE 62.1-2007 requirements, the team must do so.
- If the system is incapable of providing enough outside air to meet the ASHRAE 62.1-2007 requirements, the project can then pursue Case 2 and provide at least 10 cfm/person for those systems. Note that the team needs to supply evidence that the systems aren’t capable of meeting the ASHRAE 62.1-2007 requirements.
Our building has a single fan that supplies outside air to multiple AHU’s. Do we need to perform outside air testing at the supply fan or at all AHUs?
Outside air measurements need to be tested at the system level and so measurements would need to be taken at each AHU, not just the single supply fan.
We have a VAV system where single AHUs serve multiple zones. Do we need to take outside air measurements at each VAV box?
If a single AHU is supplying outside air to multiple zones through VAV boxes, outside air measurements need to be tested at the AHU level but not a the VAV boxes.
Legend
- Best Practices
- Gotcha
- Action Steps
- Cost Tip
Before the Performance Period
Expand All
For naturally ventilated buildings, follow the guidelines specified in ASHRAE 62.1-2007, Section 5.1 to assess compliance with the requirements. If your building has the proper ratio of operable windows or roof openings to floor area as described in the ASHRAE standard, you are likely to be able to show compliance. You may also show compliance by meeting the requirements of EQc1.3: IAQ Best Practices—Increased Ventilation.
For mechanical and mixed-mode ventilation systems, follow the guidelines specified in ASHRAE 62.1-2007, Section 6 (detailed below) and use the provided 62MZCalcs calculator to determine ASHRAE-compliant ventilation rates for each air-handling unit and zone in the building.
The building's original system design specifications and airflow rates are not relevant to this prerequisite. Designing a system to achieve ASHRAE compliance does not mean that the system is delivering airflow at those rates under current operating conditions.
Develop a ventilation maintenance program including periodic checks and system repairs.
During the Performance Period
Expand All
For All Options
Conduct a visual inspection of outside air vents, dampers, and louvers and remove any obstructions that restrict outdoor air flow.
Conduct airflow monitoring using manual instrumentation or a building automation system to document outdoor airflow rates. Gather data or take measurements for each air handling unit or ventilation zone; sampling is not permitted. For all VAV boxes, you’ll need to set up the ventilation system to simulate the worst-case system conditions expected during normal operations, such as minimum outside air flow due to damper position.
If your building automation system does not continuously measure outdoor airflow, you should still be able to measure airflow accurately by performing a duct traverse with a pitot tube. If the system’s configuration does not allow for a duct traverse (such as with curved ductwork or limited access), anemometer measures can be taken at each air handling unit.
Compare measured flow with required levels of outdoor air for each ventilation zone. Calculate the required outdoor air levels by completing ventilation rate procedure (VRP) calculations using the provided ASHRAE 62MZCalcs spreadsheet for each air handling unit.
Perform VRP calculations for all air handling units and applicable floor areas. Make sure that the floor area covered by VRP calculations matches up with the total gross floor area that is reported in your LEED application.
In the ASHRAE 62MZcalc spreadsheet, be sure to override the default occupancy with actual building occupancy.
Test all building exhaust systems to confirm that they are functioning as intended. Be sure to confirm proper function, including fan speed, voltage, control sequences, and set points.
Costs for testing will depend on how many air handling units and ventilation zones need testing, whether staff are qualified to do testing in-house, and whether the building has a BAS that gathers data.
Adjust ventilation set points if testing shows that the building is over-ventilated to save energy and reduce operational costs.
Increased mechanical ventilation rates may increase energy costs for heating and cooling. Some strategies for mitigating these costs include energy recovery ventilation, economizers and controls, CO2 monitors, and demand-controlled ventilation.
Good indoor air quality can lower operational costs while increasing occupant health and productivity as well as the value and marketability of the building.
Case 1: Projects Able to Meet ASHRAE Standard 62.1-2007
Demonstrate that each air handling unit supplies the minimum outdoor air flow specified by ASHRAE 62.1-2007. If one or more air handling units do not meet the ASHRAE requirements, you can still earn the prerequisite by using the EQp1 Option B Calculator to show that those units supply at least 10 cfm per person.
Case 2: Projects Unable to Meet ASHRAE Standard 62.1-2007 Due to Physical Constraints
Demonstrate that it is not feasible to meet ASHRAE 62.1-2007 because of building design and construction. Also, demonstrate that at least 10 cfm per person of outdoor air is supplied under normal operating conditions. Projects able to demonstrate both of these items can earn the prerequisite, even though they don’t provide optimal indoor air quality.
Use the EQp1 Option B calculator for all air handling units that are unable to provide the minimum outdoor air flows required by ASHRAE 62.1-2007.
USGBC
Excerpted from LEED 2009 for Existing Buildings: Operations & Maintenance
COPYRIGHT © 2009 BY THE U.S. GREEN BUILDING COUNCIL, INC. ALL RIGHTS RESERVEDIEQ Prerequisite 1: Minimum indoor air quality performance
Required
Intent
To establish minimum indoor air quality (IAQIndoor air quality: The quality and attributes of indoor air affecting the health and comfort building occupants. IAQ encompasses available fresh air, contaminant levels, acoustics and noise levels, lighting quality, and other factors.) performance to enhance indoor air quality in buildings, thus contributing to the health and well-being of the occupants.
Requirements
Case 1. Projects able to the standard
OPTION 1. ASHRAE Standard 62.1-2007 or Non-U.S. Equivalent
Modify or maintain each outside air intake, supply air fan and/or ventilation distribution system to supply at least the outdoor air ventilation rate required by ASHRAE Standard 62.1–2007 ventilation rate procedure (with errata but without addenda ) under all normal operating conditions. Projects outside the U.S. may use a local equivalent to ASHRAE Standard 62.1-2007 for breathing zoneThe breathing zone is the region within an occupied space between 3 and 6 feet above the floor and more than 2 feet from walls or fixed air-conditioning equipment. (AHSRAE 62.12007) minimum ventilation rates.
OPTION 2. CEN Standard EN 15251: 2007
Projects outside the U.S. may modify or maintain each outside air intake, supply air fan and/or ventilation distribution system to supply at least the outdoor air ventilation rate required by Annex B of Comité Européen de Normalisation (CEN) Standard EN 15251: 2007, Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics.
Case 2. Projects unable to meet the standard
If meeting the ventilation rates required of the above standards is infeasible because of the physical constraints of the existing ventilation system, modify or maintain the system to supply at least 10 cubic feet per minute (cfm) (5 liters per second) of outdoor air per person under all normal operating conditions. Demonstrate through design documentation, measurements or other evidence that the current system cannot provide the flow rates required by the above standards under any operating condition even when functioning properly.
Each air-handling unit in the building must comply with either Case 1 or Case 2. If some airhandling units can provide the outside air flow required by the above standards and others cannot, those that can must do so. Buildings must provide at least 10 cfm (5 liters per second) per person of outside air at each air-handling unit under all normal operating conditions to earn this prerequisite.
- Show compliance with the applicable requirement above (Case 1 or Case 2) through measurements taken at the system level (i.e., the air-handling unit). For variable air volume systems, the dampers, fan speeds, etc. must be set during the test to the worstcase system conditions (minimum outside air flow) expected during normal ventilation operations. Each air-handler must be measured; sampling or grouping of air-handlers is prohibited.
- Implement and maintain an HVAC system maintenance program to ensure the proper operations and maintenance of HVAC components as they relate to outdoor air
introduction and exhaust. - Test and maintain the operation of all building exhaust systems, including bathroom, shower, kitchen and parking exhaust systems.
Naturally ventilated buildings must comply with ASHRAE Standard 62.1-2007, paragraph 5.1(with errata but without addenda1).
Potential Technologies & Strategies
Conduct a visual inspection of outside air vents and dampers and remove any outside air vent or louver obstructions that restrict full outside air capacity from entering the distribution system. Conduct airflow monitoring to document outside air cubic feet per minute (cfm). Compare measured flow with designed flow for each unit. Test the operation of each exhaust fan and verify that exhaust airflow meets design requirements or intentions. EPA’s “Guidelines for HVAC System Maintenance” provides guidance on developing, implementing and maintaining an HVAC system maintenance program to ensure the proper operations and maintenance of HVAC components as they relate to IAQIndoor air quality: The quality and attributes of indoor air affecting the health and comfort building occupants. IAQ encompasses available fresh air, contaminant levels, acoustics and noise levels, lighting quality, and other factors..
Technical Guides
Chartered Institution of Building Services Engineers (CIBSE) Applications Manual 10: 2005, Natural Ventilation in Non-Domestic Buildings
This is a best-practice design guide to natural ventilation.
IEQ Space Matrix
This spreadsheet categories dozens of specific space types according to how they should be applied under various IEQ credits. This document is essential if you have questions about how various unique space types should be treated.
Non-Compliant AHU Form
Case 2: Projects Unable to Meet ASHRAE Standard 62.1-2007 Due to Physical Constraints
A form like this will be needed for all AHUs that are not capable of meeting the outdoor airflow required by ASHRAE 62.1-2007; these AHUs must provide a minimum of 10 cfm in order to meet the prerequisite.
Samples
Ventilation System Maintenance
All Options
Use logs or status reports to document preventive maintenance of ventilation systems.
Exhaust Systems Testing
You can use the form provided as a checklist for testing exhaust systems, and for recording results.
IEQp1 LEED Online Form
Use these LEED Online screen captures with annotated tips from LEEDuser to help you fill out this form.
LEED Online Forms: LEED-EBOM IEQ
The following links take you to the public, informational versions of the dynamic LEED Online forms for each EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems.-2009 IEQ credit. You'll need to fill out the live versions of these forms on LEED Online for each credit you hope to earn.
Version 4 forms (newest):
- IEQp1: Minimum IAQ Performance
- IEQp2: ETS Control
- IEQc1.3: Increased Ventilation
- IEQc1.4: Reduce Particulates
- IEQc2.4: Daylight & Views
- IEQc3.2: Custodial Effectiveness Assessment
Version 3 forms:
- IEQp1: Minimum IAQ Performance
- IEQp2: ETS Control
- IEQp3: Green Cleaning Policy
- IEQc1.1: IAQ Management Program
- IEQc1.2: Outdoor Air Delivery Monitoring
- IEQc1.3: Increased Ventilation
- IEQc1.4: Reduce Particulates
- IEQc2.1: Occupant Comfort—Occupant Survey
- IEQc2.2: Controllability of Systems—Lighting
- IEQc2.3: Controllability of Systems—Thermal Comfort
- IEQc2.4: Daylight & Views
- IEQc3.1: High-Performance Cleaning Program
- IEQc3.2: Custodial Effectiveness Assessment
- IEQc3.3: Purchase of Sustainable Cleaning Products
- IEQc3.4: Sustainable Cleaning Equipment
- IEQc3.5: Chemical & Pollutant Source Control
These links are posted by LEEDuser with USGBC's permission. USGBC has certain usage restrictions for these forms; for more information, visit LEED Online and click "Sample Forms Download."


213 Comments
Occupancy for the calculations
Good afternoon,
I have a question about the occupancy I have to take into account for the minimum air flow calculations. For the first review we entered the occupancy defined by the ASHRAE but the response was the following: "3.It appears that the values of occupancy used to define minimum outside air flow requirements via the supporting calculations are the design
occupancies listed in Table 6-1 of ASHRAE 62.1-2007. As indicated on the form, all values of occupancy used to define minimum outside air flow
requirements must be based on the maximum occupancy expected during normal facility operation and not design occupancy, minimum occupancy, or unusual or emergency conditions. According to the Reduced Occupancy Guidance for LEED for Existing Buildings Operations and Maintenance, 2009, the default values for occupancy listed in ASHRAE standard 62.1-2007 should be used only for completely vacant spaces."
We understood that we could not use the occupancy listed in the ASHRAE because it is the minimum occupancy and we need the maximum one. So for the next review we took into account the occupancy defined by the CTE (Spanish building code) that defines the maximum occupancy allowed in each space for some spaces and for the rest the occupancy defined by the owner. And now the response is the following: " ASHRAE Standard 62.1-2007 must be the criteria used instead of the CTE technical code."
What do we have to do? I am very confused. Please help me and thank you very much.
Patricia, the main issue is determining how many occupants your space actually has during normal operation. LEED only wants you to use default numbers (from 62.1) for spaces that are vacant (i.e. have no tenants or occupants at all).
For the spaces in your project you want to estimate the actual occupants of a space, and enter that whole number into your calculations. Only by using the real occupancy can you correctly determine the actual critical zone. The real occupants can be determined based on chair count or tenant-self-reporting, but cannot be based on code default assumptions. In my experience the LEED reviewers will trust the number of occupants that you provide.
Which calculator version I have to use
I have downloaded the "USGBC LEED 62MZCalc (May 2011) and I have to complete manually the cells that correspondon to the "Inputs of the system". In the "2002UM-62MZ" calculator I do not have to do this because this cells give me automatically an average value of the As, Ps and Vpsd. What I have to do?
I have submitted this prerrequesite with the "2002UM-62MZ" calcualtor and the review team have not told me nothing about the calculator version in the review report, so could I submit with this version?
Besides, Do I have to leave the calculator in "IP" units mode or can I leave it in "SI"? I have submitted it in SI and the review team has not told me nothing about this as well, so I supose I can leave it in SI mode, or not?
Thank you very much.
Patricia, generally you only need to make revisions to the calculations in order to directly respond to the reviewer technical advice from the preliminary review.
Related to the 62MZ calc, it's typically best to use the USGBC LEED 62MZCalc but if the review team hasn't requested that you change calculators then you should be ok. Also, if you have entered all of the zones served by the system into the calculator then you don't need to manually enter the As or Ps values for the system inputs. But if you only want to enter potentially critical zones into the calculator then you do need to enter those values manually.
Keeping everything in SI units is ok but it may be helpful to point that out to the review team for the final review submission.
Occupancy rates
I am not sure why it says on the documentation screen shot that the total occupancy for the VRP calcs should be consistent with occupancy for other credits. For example we have 1,100 full time occupants, but the occupancy for the VRP will be higher because it includes occupancy of rooms such a conference rooms, etc. Where as you might have an occupancy of 79 in a conference room, but there won't actually be 79 people in there at all times.
Hi Nena
For multi-zone systems, the total population serving that system and the additive of all systems should equal the amount listed in other credits. But then the critical zones, such as a conference room, will have more detail into the peak population of that individual zone. The VRP calcs will take into account both of these variables.
And generally speaking, if you have a higher population than your other credits, you are actually under-accounting for outside air delivery. So if you're using this approach and still meeting the prerequisite requirements, I'd just be sure to note that you are aware of this discrepancy in some sort of narrative as supporting documentation.
Thanks!
Ventilation By Exhaust air make-up
We working on a industrial building where there is an unconditioned dining area for factory workers.
This dining area is provided with roof mounted exhaust fans. All exhaust make up is fresh air, that comes through windows and the louvers on the walls. Make up fresh air coming through windows and louvers are well above the ASHRAE minimum ventilation requirements, if make up air flow rate is assumed to be equal to the exhaust air.
However LEED review team says that this won't qualify for mechanical ventilation. Pls note their comment below.
" For spaces that only receive outside air indirectly as a result of makeup air pulled from openings in the building envelope, the project must meet the natural ventilation requirements. Note that the mechanical ventilation compliance path is only applicable to spaces that receive outside air directly from mechanical supply units."
Is this comment correct?
If yes, can we assume the amount of fresh air come through the windows is equal to exhaust air flow rate? or do we have to show the proximity to the windows?
kindly advise..!!
I believe the natural ventilation requirement is based on the window opening to floor area ratioFloor Area Ratio (FAR) is the measure of the density of non-residential land use. It is the total non-residential building floor area divided by the total buildable land area available for non-residential uses. For example, on a site with 10,000 square feet of buildable land area, an FAR of 1.0 would be 10,000 square feet of built building floor area. On the same site, an FAR of 1.5 would be 15,000 square feet of built floor area; an FAR of 2.0 would be 20,000 built square feet and an FAR of 0.5 would be 5,000 built square feet.. If the openings of the windows are at least 4% of the total floor area of that room, you should be good.
single or multi-zone?
Our building is fully occupied by the same company, so all the floors have similar open space layout, except for enclosed managers or small meeting rooms.
There´s an outside air intake in each AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. level. Each floor is served by one AHU, that provides a mixture of outside air with return air, on a constant volume. There are no VAV´s, no dampers and no different zones in our ventilation plenum.
Since the floors are mostly open space, have no critical zones (bigger meeting rooms, in the last floor, are served by different AHUs), and are all of the same type (office space), is it wrong to consider it a single-zone system, and measure the intakes only in the AHU level? Or should I consider it a multizone and go through all the VRP calculations?
Outside air measurements are required at the system level. In your case it would be at each AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork.. The LEED online template calculator (the appendix section of the template form) is for a constant volume unit that serve a single room. The 62MZ calculator is for all other types. You'll most likely be required to complete a 62MZ calculator and verify the OA at each AHU.
Hope this helps
Dave
Thank you, Dave, but maybe I was unclear. The question is more about multi zone and single zone systems definition.
When LEED refers to multi or single zone UNITS, they mean the same definition of ASHRAE ventilation ZONES?
I´m sure my system is a single zone, it´s not common to have multiple zone systems in Brazil. Although in each floor we have different rooms and offices, served by the same AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork., i think my approach in the template should be more for Appendix 1 "Mechanical Ventilation Single Zone Unit", is it right?
Thank you!
Hello Guilherme.
Multiple Zone Unit describes an AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. that serves more than one room.
Single Zone Unit describes an AHU that serves one room.
Systems with local recirculation and/or multiple recirculation paths (such as systems with fan-powered terminal units) should use the 62MZ calculator.
If you have a constant volume AHU that serves more than one room, and no terminal units within the system, you can use the Multiple Zone Unit calculator on the LEED online template. (from your description, i believe this to be the path you should choose)
If you have a constant volume AHU that serves only one room you will be required to use the Single Zone Unit calculator on the LEED online template.
If you have a system with local recirculation and/or multiple recirculation paths you will be required to use the 62MZ calculator.
For example, an AHU that serves (1) office and (1) conference room, this is defined as a Multiple Zone Unit (regardless if the system includes local recirc/terminal units). If an AHU serves only (1) office, and no other room, than this is considered a Single Zone Unit.
Hope this better clarifies.
Value input for “Measured outdoor airflow, CFM”
In this prerequisite we are following Case 1 and filling in details in the 2007UM-62MZ Calculator. Further, filling in the online template column 3 in Table IEQp1-2 requires “Measured outdoor airflow, CFM”. I am not able to identify which value has to be input for this column in the 2007UM-62MZ Calculator, which is the cell?
Thank you.
It's near the top of the "Vot Calculation" tab. The row colored green and is titled "Outdoor air intake provided for system".
I have not asked you for the "required outdoor air intake flow (Vot)", I have asked for the "Measured outdoor airflow (cfm)", Can you tell me the cell I have to input in the column with that name in the Table IEQp1-2?
Hello Patricia.
You'll need to download the "USGBC LEED 62MZCalc (May 2011)" found at:
http://new.usgbc.org/resources/usgbc-leed-62mzcalc
The "2007UM-62MZ" is not the complete calculator.
The complete LEED 62MZ calculator is also available for download on LEED Online as one of the credit resources of IEQp1. It's titled "USGBC+LEED+62MZCalc+(May+2011).xls"
Hope this helps.
Dave
I have downloaded the "USGBC LEED 62MZCalc (May 2011) and I have to complete manually the cells that correspondons to the "Inputs of the system" In the "2002UM-62MZ" calculator I do not have to do this because this cells give me an average value of the As, Ps and Vpsd. What I have to do?
I have submitted this prerrequesite with the "2002UM-62MZ" calcualtor and the review team have not told me nothing about the calculator version in the review report, so could I submit with this version?
Besides, Do I have to leave the calculator in "IP" units mode or can I leave it in "SI"?
Thank you very much.
Vacant Space Critical Zones
I am working on a building that has multiple floors that are completely stripped and wide open for new tenants to design the layout to. I am not sure if this is correct but I have calculated out the number of occupants according the to the total floor area and the ASHRAE 62.1 office space standards. As for entering critical zones in I do not know what to do. There are no walls and the whole floor is completely open. I would appreciate any assistance. Thank you.
The "Reduced Occupancy Guidance" http://new.usgbc.org/resources/ebom-reduced-occupancy-guidance does allow you to calculate the required OA based on defaults. An approach that has been approved on some of my projects is to split the vacant area into a few zones and then enter the information into the 62MZ calculators, using typical values for Ez and Ds for AHUs on other floors.
Adequate measurement equipment and procedures
We are working on an office building with fan-coils units conditioning office spaces on typical floors and several multi-split ceiling cassette units conditioning technical occupied areas (maintenance room, CFTV room and other O&M staff rooms) located on the first underground floor. My questions are:
Can I use a vane anemometer to take measurements in the external air dumper located inside the fan-coil room? Which methodology (sampling, equipment …) can I use to ensure a more precise measurement?
For the underground external air supply, we have a main rectangular duct and several flexible ducts connecting each cassette unit to the main rectangular duct. I need to measure each flexible duct (measurement at each AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork.) or can I measure the total air supplied by the main duct and divide it proportionally to the total air flow of each cassette unit? Which equipment is more adequate for this measurement? I really need make holes in the duct or there is another method less invasive?
The Reference Guide states that measurement at each AHU. However, it doesn’t say which methods or equipment should be used to get a reliable measurement value.
ASHRAE Standard 111-2008 "Measurement, Testing, Adjusting, and Balancing of Building HVAC Systems" is a valuable resource if you are considering doing these tests yourself. An anemometer is an appropriate tool for some kind of tests. The exact configuration of your air-handler/fan-coil room will determine if you can use an anemometer.
The situation you describe with the minisplits can be treated as a multi-zone system in the 62.1 calculations, and the main OA supply flow would be measured and documented to be sufficient for the critical zones.
Unknown CFM into spaces
We are using the 62MZ Calculator spreadsheet for an office building. The HVAC system does not utilize VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. boxes or any kind of terminal unit. Rather, it just feeds directly into each space. How do we fill in the CFM (Vdzd) cell for the critical zones? Do we need to calculate it from the space load, measure it, or can we just use a conservative engineering rule of thumb?
Thank you in advance for any help here.
You may be able to use a rule of thumb, but measuring (hopefully only for a few critical zones) or consulting any as-built or design mechanical plans would ensure that the building is actually supplying sufficient outside air.
IEQ p1 options
Hi, we are filling the form for the IEQp1 and we have a doubt on what to choose between mechanically ventilated or mechanically conditioned, since we consider our areas mech. ventilated AND mechanically conditioned and the data required is different for each option. Thank you for the help you can provide.
Choose both. The form allows you to check multiple boxes in that section.
Critical Zone Identification
We are doing a project in which building is of office type and is having 75 AHUs and each AHU is serving one specific tenant area, means there are 75 tenant. Each tenant area is almost 10,000 SF. Building was built as Core and Shell type, and the scope of developer is limited to AHU only ( AHU is located in AHU Room), all other duct work are under tenant scope ( diffuser, grills and inside duct work)
The problem is that building is old and client built up plan is not available and hence there is not any proof of identification of clear division of zones inside the tenant area like conference , private office, pantry etc.
In this scenario, I have these question
1) How can I identify critical zones if Client Built -up Floor Plan is not available?
2) Can I consider the each client area as a single office zone, which means there will be no critical zones analysis?
In response to your questions:
1) Potential critical zones can be identified by walking through each floor, and then the necessary parameters for each critical zone can be measured for later entry into the 62MZ calculator. Sometimes building staff will be able to provide this information if you give them guidance about how to identify a critical zone (i.e. densely occupied, low supply air flow).
2) No
Ashrae 62.1 vetilation rate - Constant OA with VAV system
We have a constant volume air fan feeding many floors. It feeds the mechanical space using it as a plenum. At the floor level there is a Supply fan serving the VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. and Fan boxes. The floor AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. only has a cooling coil, the heat is provided by reheats. Is it correct to use the maximum cfm for Vdzd and 100% for the Ds? When I use the minimum cfm for this calculation the required OA actually drops.
You will have to select the appropriate values for the worst case scenario for the floor level fan systems. In a typical VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. system, the worst case scenario is during heating mode, when system fan flows and zone air flows are both lower than 100% of design levels. However, you will have to experiment in the 62MZ calculator to determine which condition actually creates the highest requirement for outside air.
Mixed use: Production; Shipping/Receiving; R/D; Office Space
The building has four space types and 20 AHUs. The building lacks any integrated controls, so each AHU operates independent of the other. The building has primarily open floor plans, with a few conference rooms and private offices (for 1 person). 20 VRP calculators were completed - one for each AHU, with most AHUs having two zones. The conference rooms are included as a separate zone, as is the cafeteria. Most AHUs serve 6,000 SF or less (some serve only 2,000). The largest AHU serves 25,000 SF.
Our LEED Review comment was "a sufficient number of potentially critical zones have not been identi!ed in the supporting calculations in all cases. Zone level data is used to calculate the required outdoor air at the system level. The documentation must provide sufficient information to show that all potentially critical occupiable zones have been accounted for in the calculations to determine the critical zone. Only a few zones have been
entered in the calculations for each supply air fan. For single air handlers serving over 100,000 square feet, a minimum of 15 zones should
be listed in the VRP calculations for each of the large air handlers. Fewer zones are acceptable for smaller air handlers. Critical zones
generally include conference rooms, training rooms, or other high density spaces with variable occupancy, though office spaces or other
spaces may be the critical zone if the volume of air supplied to the space is limited."
I have a few questions:
1. Do we need to breakout each of the private offices as a separate zone (even though it's not treated as such by the AHUs)?
2. We have 20+ critical zones and have no AHU serving 100k square feet. How would you respond to this comment?
3. Last, we've been treating each of the AHUs as a separate 'system'. Do we need to send over a single calculator, that includes all zones from the smaller AHUs and aggregate all AHU information into one (make-believe) 'system calculator'.?
Thanks
Aaron
A ventilation zone is different from a thermal zone. So while a single VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. box may serve three offices, each of those offices should be considered separately for ventilation purposes, especially if they have different primary air flows.
If you are only providing one or two potential critical zones in your 62MZ calculator, it may not be clear that those zones are actually the system critical zones, especially if the zones listed in your calculator represent combined spaces.
So in response to your questions:
1. Yes, unless you can clearly show that conference rooms or other rooms are the actual critical zones .
2. Your response narrative must make it clear how potential critical zones were selected.
3. Each AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. should be treated as a single system.
62MZ calulator spreadsheet with critical zones
Hello everyone
maybe our first question posted here earlier was not so clear. we just want to know how many critical zones should be put into the spreadsheet with each AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. unit ?? From our understanding , using 62MZ cal spreadsheet and critical zones can be an alternative to calulate the minimum ventilation rate. From 62 MZ cal instructions it provides information on how to define the critical zones in heating or cooling modes. But it does not imply how many critical zones will be enough to put in in each case of AHU calulation ????
for example, one AHU unit serves to total 8 floor plans. For each floor plan there will be critical zones. So should we sum up critical zones from each floor plan and put into the 62MZ cal ? Or should we just use one floor plan as representative one and only count in critical zones from that plan and put into the 62 MZ cal spreadsheet????
we ask these questions here since we tested the 62MZ cal spreadsheet and it felts a bit tricky with inputs for system and inputs for potentially critical zones in the spreadsheet. Even someone suggested here earlier that the input for system can be overriden. Still we want to be sure that we are on the right track.
we really appreciate any advice and hints from anyone who had experience with use of this spreadsheet to earn this credit?
By definition, each air handling system has one critical zone. You should document enough zones to show that you have correctly selected the critical zone.
Thank you for your response regarding the critical zones.
However, we have now found an earlier discussion/answer below from Samantha Harrell from the 26th of March 2012.
In our project, our building is supplied with 100% outdoor air. Is it correct that we can not use calculations with critical zones according to 62MZ? Instead, we must use the VRP Compliance Calculator?
If we shall use the VRP Compliance Calculator, must all occupiable areas be included for these calculations (and not only the critical zones). Is this correct?
Yes. The concept of "critical zones" does not apply to a 100% OA system. Provide the calculation for all the spaces.
Timing for this Prereq
Need some advice on timing for this Prereq. Would there be any draw back to doing our ASHRAE calcs now for this credit and then having out TAB contractor come and measure OA and make adjustments to OA (as needed to meet ASHRAE per our calcs). We plan do begin our preformance period for our other IEQ and MR credits in several months. But I assume as long as I make my PP for this credit start now and end in several months (when the other ones end) it would be okay?
Nena, I don't see an obstacle to timing the credit in this way.
IEQp1 Design Supply Air Question
Hi,
For the Design total supply to zone (Vdzd) and Design total supply airflow (Vpsd), should those numbers reflect the design flow at the condition analyzed? For example, if I am analyzing ceiling supply heating condition and the zone has a max supply of 250cfm for heating mode and 1,000cfm for cooling mode, which number should I use?
Thanks,
You would use the 250 cfm for heating mode (and the Ez of 0.8 to match overhead air distribution in heating mode). The calculator embedded in the form asks you which condition you are analyzing, and your worst case is probably heating mode so it sounds like you're on the right track.
So just to clarify, if I have space where the minimum heating supply is the same as the maximum heating supply (even though the maximum cooling supply may be higher), then my Ds = 100%?
Michael,
You have two options:
Vdzd =250 cfm
Ds=100%
or
Vdzd=1000 cfm
Ds=25%
In the end you get the same value. We tend to do that latter. We put in the full capacity of the terminal unit and then what the turn down is for the design condition analyzed.
If it's a Cooling-only system (no heating in the building), should Ds be 100% or the minimum operating setting for that particular VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas.?
Any input or advice is much appreciated.
Simon,
Unless your cooling only system is constant volume, then your worst case is when the zone needs minimum cooling. Typically you'll have a Ds around 50%-30%.
Fresh air requirements for a supermarket
I was wondering if anyone has experience dealing with supermarket fresh air calculations. In particular, is a supermarket's storage area considered an occupiable space? The definition of occupiable space says that storage rooms can be excluded, but has the difference between a storage space and a warehouse space been established at some point in the case of a supermarket?
Thanks
A warehouse is occupiable space. A closet is not.
"Occupiable Space: an enclosed space intended for human activities, excluding those spaces intended primarily for other purposes, such as storage rooms and equipment rooms, that are only occupied occasionally, and for short periods of time." from ASHRAE 62.1-2007
If someone is working in there it's occupiable.
Case 2
If the 62MZ calculator reveals that the critical zone is a zone with cooling only (with a min of 0), is that an appropriate reason to pursue Case 2?
Two Thoughts
1. You need to attempt to correct the your system unless it is infeasible because of the physical constraints of the existing ventilation system. So unless you can't reset your minimum to say 30% then you need to attempt to make corrections.
2. If your minimum is 0 then you won't be able to meet Case 2 either. In Case 2, you are required to provide 10 CFM/person under ALL normal operating conditions. Obviously your zone with a minimum of 0 can't provide 10 cfm/person.
OA damper that closes at certain conditions
We are working on getting an 8-story office building LEED EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems. certified. The system utilizes large built up air handlers to provide supply air to fan powered VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. boxes. The system is designed for full economizerAn economizer is a device used to make building systems more energy efficient. Examples include HVAC enthalpy controls, which are based on humidity and temperature. when the ambient air conditions are sufficient. During occupied hours approximately 20% outside air is being provided through the outside air louver most of the time, but when ambient temperatureTemperature of the surrounding air or other medium. (EPA) is below 35 degF and above 85 degF the outside air damper closes because the building cannot maintain temperature set point. We have louver, fan, duct, ect. capacity to meet 62.1 flow rates, but the system cannot maintain set point at the mentioned ambient conditions.
It seems that meeting ASHRAE standard 62.1-2007 is infeasible because of physical constraints limiting the system to provide outside air when outside air is below 35 degF and above 85 degF. Therefore, I assume that we would pursue case 2 and provide 10 cfm of outside air per person. Case 2 states that we need to demonstrate that the current system cannot provide 62.1 outside air flow rates “under any operating condition even when functioning properly”.
My question is since we can provide the required outside air most of the time, does that mean we don’t meet the requirements of case 2 and are out of luck? Thank you for any help that you can provide!
Darin,
The building will meet the prerequisite as long as the system provides at least 10 cfm per person under the worst case conditions and the systems are set to meet ASHRAE 62.1-2007 when they are physically able to do so.
I think that the rating system language you site above is meant to preclude situations where a building is only providing 10 cfm per person in all conditions, even if the systems can meet the ASHRAE standard during some or most conditions.
Thanks for the response Ben. Just to clarify, the 10 cfm per person requirement is for FTEFull-time equivalent (FTE) represents a regular building occupant who spends 8 hours a day (40 hours a week) in the project building. Part-time or overtime occupants have FTE values based on their hours per day divided by 8 (or hours per week divided by 40). Transient Occupants can be reported as either daily totals or as part of the FTE. Residential occupancy should be estimated based on the number and size of units. Core and Shell projects should refer to the default occupancy table in the Reference Guide appendix. All occupant assumptions must be consistent across all credits in all categories. occupants and ASHRAE 62.1-2007 occupants, correct?
Sure, the 10 cfm per person requirement is for the maximum expected occupancy during typical operations. It's not supposed to be the ASHRAE default except in some circumstances when the project needs to follow the reduced occupancy guidelines (less than 90% average occupancy over the performance period). Those guidelines are posted on USGBC's website.
estimating system Ds
Hello All,
I have a building where we are performing calcs on a select number of assumed potential critical zones as opposed to every zone. Regarding estimating and over-riding system Ds (percent of total design airflow at conditioned analyzed), is the following an appropriate strategy considering that I don't have access to the mechanical as-builts?
I will study the furniture plan and come up with a VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. zoning plan using engineering judgement. Based off of that VAV zoning plan, I will determine square feet of "exterior" and square feet of "interior". I will then apply common industry practice and assume a 20% minimum CFM setting for interior zones, a 50% minimum CFM setting for "regular" exterior zones, and a 75% minimum CFM setting for exterior zones with multiple exposures and a lot of glass and/or operable windows/doors (infiltration). The appropriate percentages will then be applied to the appropriate square footages and averaged to get a system Ds.
Does this approach seem like it will suffice for the 62MZ requirement as "sufficient information or backup calculations to confirm that the conditions represent the worst case"?
As always, your help is beyond appreciated.
Exhaust System test for pressurized buildings with no exhaust
Hi all,
We have an existing building built in the early 1900s with three 100% make up air units supplying fresh air with no exhaust. The building is pressurized and fresh air exits through the building envelope. We have taken supply air measurements. What are the EQp1 guidelines for exhaust system tests on pressurized buildings without exhaust fans? There are four small evacuation fans for each bathroom which evacuate less than 5% of the total supply air.
Thank you for your help with this question.
It sounds to me like you would test for proper functioning of the evacuation fans and then include a narrative with the prerequisite submittal summarizing the building's strategy related to pressurization and exhaust.
Trending Acceptable for Mins and Maxs?
Once the outside air has been read and the assumed potential critical zones have been identified, if a building owner/staff is unable to compile the mechancial as-builts in order to determine max (Vdzd) and min (used to determine Ds), is it acceptable to trend those spaces through the building DDC system for a certain period of time in order to determine those values? Any further advice? Thanks in advance.
Roger,
Many times the Max and Min values for a terminal unit are listed as adjustable points in the DDC system. Check there first. Unfortunately, unless you are trending during peak indoor and outdoor conditions and you may not see your maximum flow at your critical zone during a short trending period. Minimums will probably occur more often and would be caught in a trending period of a day or so.
Zone population
Hi all,
I was doing the calculation for my office, and this confused me about the zone population because my office has 2 zones, office zone and conference rooms. Both are served by separate AHUs with separate OA supply.
What should i put in the zone population? Because people cannot occupy the office & conference room at the same time, so is there any ratio i can apply on the total design population?
Thank you,
Billy
Maybe my question is not clear enough... Let's say i have 10 meeting rooms with capacity of 10 seats/room, so maximum number of occupants is 200. Should i put this number as the design population? Because i believe you will never see the rooms being occupied 100%.
Billy,
In your case (2 zones, 2 separate systems) both zones need to separately account for the design maximum occupancy. You need to create calculations for each ventilation system separately.
If the same system was serving both the offices and the conference room you could take into account some design population diversity based on your judgement or the FTEFull-time equivalent (FTE) represents a regular building occupant who spends 8 hours a day (40 hours a week) in the project building. Part-time or overtime occupants have FTE values based on their hours per day divided by 8 (or hours per week divided by 40). Transient Occupants can be reported as either daily totals or as part of the FTE. Residential occupancy should be estimated based on the number and size of units. Core and Shell projects should refer to the default occupancy table in the Reference Guide appendix. All occupant assumptions must be consistent across all credits in all categories..
Thank you, Dylan... Hope i can get enough for the IEQp1 requirements.
Fresh Air Measurements on Rooftop Units
I am applying this credit to ten rooftop units that lack a straight duct section long enough to traverse with a pitot tube. The TAB contractor is concerned that measurements taken at the intake louvers will be inaccurate because of the influence of wind. I envision temporarily fastening some kind of manifold/duct section over the RTU's fresh air intake louver to facilitate measurements. Before I propose this to the TAB contractor has anyone tried anything similar (or simpler) with RTU's? Thanks in advance.
AHU measurements
In our building we have two main AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. that supply 26 AHU (one for each floor of the building) and then we have VAVs for each zone in each floor.
Do I need to perform measurements just in the two main AHU since this are the ones that have fresh air intake or we need to perform measurements in both the main and secondary AHU?
Thank you in advance
Luis,
You will need to provide calculations/measurements for all the units. The calculations for the 26 units on each floor will dictate the OA requirements of the 2 main AHUs.
Critcal Zone 100% Out Door Air System
We are currently confusion regarding a review we received. Our building is a multizone building that is supplied with 100% outdoor air. From the review team it is required to perform critical zone calculations even though spaces are supplied with 100% outdoor air. From my understanding critical zone calculations are required for recirculation systems to determine the Primary Outdoor air Fraction (Zp) and System Ventilation Efficiency (Ev).
How can i determine the critical zone for systems with 100% outdoor air supply? Shall I use instead the occupant density and zone distribution configuration (Ez) as the critical figures?
Thanks
You are correct, the critical zone is not an applicable calculation factor when the system supplies 100% outdoor air. A quick way to test this is to download the latest IEQp1 Sample Form (v04, active version) from LOv3 and indicate that the project is 100% outdoor air. The form will only allow inputs for applicable calculation factors.
We saw this discussion regarding IEQp1 you had in March 2012.
In our project, our building is also supplied with 100% outdoor air. Is it correct that we can not use calculations with critical zones according to 62MZ? Instead, we must use the VRP Compliance Calculator?
If we shall use the VRP Compliance Calculator, must all occupiable areas be included for these calculations (and not only the critical zones). Is this correct?
Thank you in advance.
Yes, as stated, the concept of "critical zones" does not apply to a 100% OA system. Provide the calculation for all the spaces.
Lg AHU serving multiple floors, perform calcs at zone level?
I was brought on to a project to complete the ASHRAE 62.1 calculator after the project was denied LEED EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems. IEQp1. The project consists of two high rise office buildings. Tower "A" is conditioned via one air handler per floor with mixed use and occupancy. Tower "B" is conditioned via 4 large air handlers, each serving multiple floors with mixed use and occupancy. I understand after reading through leeduser.com that ventilation readings need only be taken at the air handler at minimum OSA. The owner/F&M staff are having a hard time tracking down the mechanical as-builts which would assist in determining mins and zoning. So, my questions is as follows: am I required to perform the ventilation calcs at the zone level (i.e. determine critical zones such as interior conference rooms)? I just want to be sure that politely demanding as-builts from the client to determine potentially critical zones and the associated mins is appropriate.
Thanks in advance for your help.
So the lack of response to this question leads me to think that maybe my original question wasn't clear enough. Basically, I'm wondering if anywhere in the LEED EBOMEBOM is an acronym for Existing Buildings: Operations & Maintenance, one of the LEED 2009 rating sytems. or ASHRAE 62.1 documentation, there exists any exceptions to performing calcs at the zone level and allowances to only perform measurements at the Air Handlers. i.e., if the Air Handler is seeing a minimum of 20% outside air during normal operating conditions, all zones are also seeing a minimum of 20% outside air.
Thanks again in advance for any help.
Both the ASHRAE 62.1 calculations and the outside air testing need to be done at the system level (AHUs). But, the ASHRAE 62.1 calculations do need to incorporate the critical zones for each system. So, somehow you will need to determine the critical zones for each system and collect the relevant data points for those zone. We've seen that typically a handfull of critical zones for each system should be sufficient for the calculations and the LEED review.
Start a new LEED comment thread