Homes-v2008 EQc5: Local exhaust 1-2 points

LEEDuser’s viewpoint

Explore this LEED credit

Post your questions on this credit in the forum, and click on the credit language tab to review to the LEED requirements.

Credit language

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

Prerequisites

5.1 Basic local exhaust. Meet all the following requirements:
  1. Design and install local exhaust systems in all bathrooms (including half-baths) and the kitchen to meet the requirements of Section 5 of ASHRAE Standard 62.2-2007. Sample requirements that relate to minimum intermittent local exhaust flow rates are shown in Table 1, below.
  2. Design and install the fans and ducts to meet the requirements of Section 7 of ASHRAE Standard 62.2-2007.
  3. Exhaust air to the outdoors (i.e., exhaust to attics or interstitial spaces is not permitted).
  4. Use ENERGY STAR labeled bathroom exhaust fans (except for exhaust fans serving multiple bathrooms).
Table 1. Minimum Air Flow Requirements for Intermittent Local Exhaust

Location

Minimum air flow

Kitchen

100 cfm; vented range hood required if exhaust fan flow rate is less than 5 kitchen air changes per hour.

Bathroom

50 cfm

Credits

5.2 Enhanced local exhaust (1 point). Use one of the following strategies in every bathroom to control the use of the local exhaust fan:a. An occupancy sensor.b. An automatic humidistat controller.c. An automatic timer to operate the fan for a timed interval after occupant leaves the room.d. A continuously operating exhaust fan.5.3 Third-party performance testing (1 point). Perform a third-party test of each exhaust air flow rate for compliance with the requirements in Section 5 of ASHRAE Standard 62.2-2007. See all forum discussions about this credit »

What does it cost?

Cost estimates for this credit

On each BD+C v4 credit, LEEDuser offers the wisdom of a team of architects, engineers, cost estimators, and LEED experts with hundreds of LEED projects between then. They analyzed the sustainable design strategies associated with each LEED credit, but also to assign actual costs to those strategies.

Our tab contains overall cost guidance, notes on what “soft costs” to expect, and a strategy-by-strategy breakdown of what to consider and what it might cost, in percentage premiums, actual costs, or both.

This information is also available in a full PDF download in The Cost of LEED v4 report.

Learn more about The Cost of LEED v4 »

Documentation toolkit

The motherlode of cheat sheets

LEEDuser’s Documentation Toolkit is loaded with calculators to help assess credit compliance, tracking spreadsheets for materials, sample templates to help guide your narratives and LEED Online submissions, and examples of actual submissions from certified LEED projects for you to check your work against. To get your plaque, start with the right toolkit.

USGBC logo

© Copyright U.S. Green Building Council, Inc. All rights reserved.

Requirements

Prerequisites

5.1 Basic local exhaust. Meet all the following requirements:
  1. Design and install local exhaust systems in all bathrooms (including half-baths) and the kitchen to meet the requirements of Section 5 of ASHRAE Standard 62.2-2007. Sample requirements that relate to minimum intermittent local exhaust flow rates are shown in Table 1, below.
  2. Design and install the fans and ducts to meet the requirements of Section 7 of ASHRAE Standard 62.2-2007.
  3. Exhaust air to the outdoors (i.e., exhaust to attics or interstitial spaces is not permitted).
  4. Use ENERGY STAR labeled bathroom exhaust fans (except for exhaust fans serving multiple bathrooms).
Table 1. Minimum Air Flow Requirements for Intermittent Local Exhaust

Location

Minimum air flow

Kitchen

100 cfm; vented range hood required if exhaust fan flow rate is less than 5 kitchen air changes per hour.

Bathroom

50 cfm

Credits

5.2 Enhanced local exhaust (1 point). Use one of the following strategies in every bathroom to control the use of the local exhaust fan:a. An occupancy sensor.b. An automatic humidistat controller.c. An automatic timer to operate the fan for a timed interval after occupant leaves the room.d. A continuously operating exhaust fan.5.3 Third-party performance testing (1 point). Perform a third-party test of each exhaust air flow rate for compliance with the requirements in Section 5 of ASHRAE Standard 62.2-2007.
See all LEEDuser forum discussions about this credit » Subscribe to new discussions about Homes-v2008 EQc5