NC-2009 EAc5: Measurement and Verification

  • NC EAc5
  • Monitor energy—or more

    Measurement and verification (M&V) involves recording actual energy use over the course of occupancy, and comparing that data with the estimated energy use seen in the design. The M&V process ensures all systems are performing as specified and identifies any anomalies in equipment, operations procedures or user habits. In addition, an M&V plan can help reduce energy costs, assist with commissioning, and, over time, document and improve the efficiencies of energy conservation measures.

    M&V gives you a plan and a system to compare your project’s actual performance against design predictions. While M&V can be applied to a variety of metrics including water use and indoor environmental quality, this credit focuses only on energy performance. To earn it, you’ll need to develop an M&V plan, install devices to support the plan, and also have steps in place for corrective action. The credit requirements don’t tell you exactly what systems to monitor—that depends on your mechanical system design and what equipment you have installed. In general, you are expected to monitor energy from all systems or components that will provide data points for end uses identified in the energy model and that will help in the recalibration of the model. 

    What’s it cost?

    The cost of M&V varies a lot. Added costs come from designing and installing specific monitoring systems, including adding multiple meters and wiring. The cost is higher in larger and more complex buildings or those with multiple uses. The cost premium will be lower if your project already plans to include a Building Management System (BMS) or submeters to record usage data. If your building is small with a minimum set of uses, and needs only few meters to meet the credit, an M&V system might also be relatively affordable.

    For large buildings that have complex mechanical and electrical systems and that do not have a BMS, adding the equipment and systems needed to implement an M&V plan is likely to be cost-prohibitive. Some projects also find that Option B (see the Checklists tab) is particularly costly due to the requirements of added meters and wiring. 

    Is it worth it?

    Despite aiming high during design, LEED-certified buildings don’t always perform as well as expected. An M&V program will not only help building operators be aware of performance issues, it can locate the source of problems or poor assumptions, and provide a better overall understanding of the value of energy-saving strategies.

    To make the investment worth it, the owner must be committed to developing and implementing the M&V plan, analyzing and understanding the building’s performance, and acting on the results. The cost premium of M&V installation and operation is typically offset by long-term energy savings, but this is highly dependent on the building type as well as the owner’s willingness to make needed changes and upgrades. The credit is generally more applicable for larger commercial buildings than residential buildings since its cost benefits may not affect the developers directly. Residential buildings may also see less benefit because the building operator has little control over energy use by residents.

    Who does it?

    The “M&V provider” takes responsibility for developing the M&V plan. This role can be filled by the commissioning agent, energy modeler, mechanical engineer, project engineer, or a facilities manager.

    What’s the standard?

    The industry standard for M&V, both in the U.S. and internationally, is the International Performance Measurement and Verification Protocol (IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits.), owned by the nonprofit Efficiency Valuation Organization. LEED has singled out Volume III of the IPMVP guidance as the basis of its requirements. Several organizations have published M&V guidelines based on IPMVP. Among them are ASHRAE, the U.S. Department of Energy’s Federal Energy Management Program (FEMP), and some utilities and states that fund energy-efficiency projects. Some organizations with M&V standards offer guidance in writing M&V plans, including sample language. (See Resources for more information.)

    Commonly metered systems

    Although no specific metering is required for this credit, the following list outlines energy uses that are often included in the M&V plan (where applicable).

    • Lighting and lighting controls
    • Constant and Variable motors
    • VFDA variable frequency drive (VFD) is a device for for controlling the speed of a motor by controlling the frequency of the electrical power supplied to it. VFDs may be used to improve the efficiency of mechanical systems as well as comfort, because they use only as much power as needed, and can be adjusted continuously. Operations
    • VFD power use
    • Readings required for packaged equipment efficiency logging
    • HVAC loads
    • HVAC Systems, equipment, and controls
    • Hydronic heating efficiency
    • Domestic water heating efficiency
    • Building-related process energy systems and equipments
    • General water use
    • Process waterProcess water is used for industrial processes and building systems such as cooling towers, boilers, and chillers. It can also refer to water used in operational processes, such as dishwashing, clothes washing, and ice making. use
    • Process Refrigeration
    • Total Facility Gas usage metering
    • Total Facility Electricity usage

    Consider these questions:

    • Does the local utility offer any rebates or incentives for a BMS or sub-metering?
    • Are there any legal issues with third party sub-metering? Is third party sub-metering allowed by the local municipality or utility company?
    • What is the cost increase associated with a BMS and M&V plan?
    • Who will be the projects M&V provider (who will write the plan and perform the follow up tasks)? Who will train the operational staff to implement the M&V plan?
    • Are there any issues or limitations to including M&V maintenance and recording as part of the operational staff scope?
    • Would Option B or Option D be most appropriate for this project?
    • Will a BMS be incorporated in the building design?
    • What design constraints might be associated with including an M&V plan?
    • What would the scope of the system be? What end uses / systems are part of the project? How many sub-meters would the project need? If going for Option B, how many ECMs need to be isolated? If going for Option D, will an energy model be developed for EAc1 anyway?
    • What operational savings can the project team expect with an M&V plan?
    • What type of corrective action would be best for the project?
    • What is the level of precision desired for the M&V program?
    • What is the budget available?
    • What other energy awareness and reduction strategies are being considered or implemented?  (Educational Display, Fault Detection Diagnostics, Commisioning, etc.)  These strategies may have many synergies with M&V.

    FAQ's for EAc5

    How should we approach this credit for residential buildings where tenants are paying their own utilities?

    A measurement plan can include a sampling of units, and must include end uses. However, the metering does not have to be permanent. A short-term metering plan could be worked out with occupants in the units being sampled.

    Our project already includes a full direct digital control (DDC) system for HVAC. Does this satisfy the submetering requirements of this credit?

    No. DDC control points are not intended to measure energy consumption.

    Is the gas consumption of stoves, ovens, and etc. required under this point?

    It depends. This usage must be included in your models. If they are a significant energy user (say more than 5% of gas usage) then yes the energy use should be measured or derived. If the usage is small you might be able to make the case that you would not need to measure it.

    When is it applicable to go for option B instead of option D?

    Generally, if you have interactive energy conservation measures (ECMs) in new construction, you need to follow option D. Most new construction has interactive ECMs, and Option B is very rarely accepted by LEED reviewers for this reason.

    Is there a requirement to model baseline energy use as being 25% process loads?

    No. This is a consistent source of confusion and is not an ASHRAE or LEED requirement. You should always model the process loads as accurately as possible to reflect the actual building equipment and operation. If the baseline is less than the 25% default, simply note why that is the case.

    Does this credit specify how energy use should be measured?

    No. It can be a manual measurement, short-term trending device or permanent submeter. In certain situations an energy end use does not need to be "measured" at all but can be derived based on other data.

    What should the plan for corrective action contain?

    This part of the M&V Plan can't be very detailed since you do not yet know what needs to be done. What you will do depends upon the issues uncovered. In general the action plan simply identifies what you will do when deviations occur between the projected savings and the actual savings. Typically this involves identifying additional energy saving strategies in the facility and using the calibrated model, for example, to determine additional energy savings. The cost and savings of the additional energy saving measures should be summarized in the final M&V report. It's a good idea to indicate that the owner will be responsible for implementing these recommendations as budget and time allow.

Legend

  • Best Practices
  • Gotcha
  • Action Steps
  • Cost Tip

Pre-Design

Expand All

  • Consider incorporating a Building Management System (BMS) into the building. A BMS will streamline implementation of this credit, while offering other benefits.


  • Consider the impact of an M&V system on space requirements.  Keep in mind that a BMS will require additional space for monitors, wiring and sensors.


  • Consider the impact of an M&V program on mechanical system design requirements. Consider whether or not your mechanical system is capable of providing the necessary outputs for the BMS or monitoring system. The outputs are typically the energy usage recorded as kWh, Btus or therms for a given period of time. It may be an automated record kept by the BMS, or a metered reading on the equipment manually carried out at regular intervals. The specifics of the output metric and duration would be determined in the M&V plan and depend on the system installed. 

     


  • The “M&V provider” develops M&V plan. This role can be filled by the commissioning agent, energy modeler, mechanical engineer, project engineer, or a facilities manager. 

     


  • Contract with the M&V provider early in the process so that system components and recommendations can be implemented seamlessly into systems rather than becoming add-ons.

Schematic Design

Expand All

  • Discuss as a team whether M&V will contribute to the project’s goals for energy reduction and systems monitoring. Consider the project size, its complexity, and whether you plan to run a whole-building energy model. Also think about how the building is likely to be operated. If the system is not likely to be fully utilized, it may not be an appropriate investment.


  • Determine whether IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. Option B or Option D is most appropriate for the project design. (Option C, which was allowed in earlier versions of LEED, is not allowed, as it is considered less accurate, and doesn't allow for M&V of individual energy conservation measures.)

    • Option B is based on engineering calculations using metered data and is generally appropriate for smaller buildingswithout interactive systems. You will need to verify compliance with Option B for projects with more complex control systems. 
    • Option D uses calibrated whole-building energy simulations for both the baseline and design case and is generally appropriate for larger, more complex buildings where energy modeling has or will occur. 

  • Data to support calculations (Option B) or calibration of simulations (Option D) is taken from a combination of meters and sensors included in the building automation systems, and through temporary installation of additional sensors and data loggers as needed.

     


  • Energy savings is determined by comparing actual metered or measured energy use to the projected energy use of a baseline building under similar operating conditions.

    • Energy Savings = Projected Baseline Energy Use – Post-Construction Energy Use (actual metered energy use).
    • Post-Construction Energy Use is determined by utility metering or submetering, or by using an energy simulation model of the projected building.

  • Talk to the facility operations staff about the financial benefits and operational requirements of the M&V plan. Any energy savings achieved through M&V will depend on their participation.

     


  • Introduce the M&V program into the design early in the process, because it can affect the design of the mechanical and electrical systems as well as the BMS. There is also inherent value in having the design teams think about how the building will be operated.


  • Metering individual hotel rooms may not be feasible due to inconsistent occupancy and limited ability to control energy usage. If your hotel project includes M&V, you must track occupancy data based on daily sales records. Metering all common spaces can benefit operations, though it won’t be sufficient to earn the LEED credit. 


  • Multifamily residential buildings are required to submeter all apartments individually and to collect data from occupants. Usage information may be made available to the occupants and energy cost savings may be transferred in lease or sale contracts. 


  • Utility companies may provide incentives or rebates for submetering and BMS programs. For example, New York City provides $2,000 per meter for advanced master meter installation in affordable housing and $1,500 per meter for market-rate housing. Check with your local utility to see if they provide any rebates.


  • The cost of M&V varies significantly from one project to another. Projects will need to get project-specific bids based on their individual design needs. The usefulness and the cost of M&V plans are influenced by the following: 

    • Level of detail and effort associated with verifying post-construction conditions
    • Number and types of metering points
    • Duration and accuracy of metering activities
    • Number and complexity of dependent and independent variables that must be measured or determined on an ongoing basis
    • Availability of existing data collection systems such as energy management systems
    • Level of precision designed and specified into the system, and your confidence in the data analysis

  • An M&V program that is implemented throughout the life of the building will provide the highest return on investment.  Design your M&V program for use throughout the life of the building to provide the highest return on investment.


  • Option B: Energy Conservation Measure Isolation


  • Isolating and metering different ECMs, such as HVAC systems or lighting, can provide useful information on energy consumption and provide insight on energy reduction measures.


  • The cost implications for ECM isolation depend on how many meters are installed and the complexity of the systems being monitored. See the appendix in ASHRAE, Guideline 14 for estimating the cost of meters. If systems are easily isolated and don’t require many meters, this credit can be relatively cheap, with Option B being more cost-effective than Option D.


  • Option D: Calibrated Simulation


  • Sub-metering different use areas in mixed-use buildings, such as office and laboratory space, can offer insight into what energy reduction measures will be most appropriate for different use spaces. 


  • Option D is the best choice for projects with highly efficient building envelopes and efficient mechanical and electrical systems. 


  • Permanent submetering or a BMS is not necessary. Project teams can instead choose a combination of utility analysis, spot-metering and permanent metering. However, these other methods will not provide the detailed information that a BMS would and may not help projects determine energy problems or understand actual energy use. An M&V plan without a BMS is rare in large new construction projects, but smaller, single-occupancy buildings may find that packaged energy monitors or monthly utility bills can provide helpful feedback without the investment in a costly BMS.  


  • Most M&V programs submeter individual systems such as lighting, heating, and cooling. Plug loads are not always submetered individually, it is easiest to individually submeter larger items and subtract the totaled submeter number from the total building usage to get the estimated plug load number. 


  • An M&V program generally includes sensors—which measure the volume and rate of flow, watts of energy draw, temperature, length of time, and other variables—and a central processor—which stores the collected information and helps building managers interpret it. Building automation systems typically include the central processor needed for M&V, but not all of the sensors, or the additional programming to tally energy use and track patterns. Adding these pieces to a building automation system should be easy, though.


  • The cost implications of this credit vary from one project to the next. Costs will depend on the complexity of the meter and sub-metering system, the cost of energy modeling and calibration, the cost of commissioning, and the size and complexity of the building. The cost premium for M&V will be lower for projects that already include a BMS. 

    • For retrofits, costs of M&V average no more than 5% of the total project cost, studies show. 
    • For new construction, the combined cost of the installed equipment and the first year of monitoring is generally less than 1% of the total project cost for buildings larger than 150,000 square feet, and less than 1.5% for smaller buildings, according to studies.

  • The cost to create a M&V plan for Option D is influenced by the following, according to IPMVP:

    • Size and complexity of ECMs, systems or building
    • The degree of accuracy expected from your readings of measured energy use, compared with estimated energy use. A somewhat less accurate calculation will take less time.
    • Simulation software utilized and its associated complexity
    • Extent and sophistication of submetering

Design Development

Expand All

  •  Determine the extent of the M&V program based on the owner’s goals, the project type and function, and IPMVP requirements. M&V goals can be included in the Owner’s Project Requirements and Basis of Design documents for EAp1 and EAc3


  • The M&V provider reviews the project design to determine which systems and equipment will be metered, and also determines how many meters will be required


  • The M&V provider works with the MEP to verify that all systems are designed to allow metering and submetering. Meters must be capable of interfacing with the selected BMS or metering system. 


  • The MEP designs and specifies the appropriate submetering devices, controls and M&V system. The M&V provider verifies that the M&V program and systems are capable of providing the information required for the credit.


  • Permanent installation of water meters will allow easier monitoring of water consumption and savings. Although this is not required for LEED, water metering for graywater and rainwater systems is generally included in M&V plans, and monitoring general water use is also worthwhile, to verify projected savings. 


  • Adding a M&V program to the project after mechanical and electrical systems have been designed may be cost-prohibitive due to redesign costs.


  • Option B: Energy Conservation Measure Isolation


  • The M&V provider determines all of the ECMs that need isolation and verifies that these systems do not interact with any other ECM. 


  • The M&V provider works with the owner and MEP to determine the best solution for metering or submetering ECMs.


  • Option D: Calibrated Simulation


  • The M&V provider works with the owner to determine the best system for monitoring actual energy use.


  • Run a preliminary energy model. If an energy model is being developed for EAc1: Optimize Energy Performance, the model can be used as the energy use baseline for the M&V plan. Otherwise a new model may be run to determine the baseline energy use. The actual energy use will be compared to this baseline. 


  • The BMS should be set up to collect data that will allow fair comparison between actual and predicted energy use. For example, since weather patterns are factored into the energy model, the BMS should capture these, along with other parameters such as operating schedule, occupancy density, space use, and system settings. 


  • To achieve this credit under Option D, the M&V plan must be able to identify specific building performance issues. A BMS or submetering will be able to build this capacity into the system.


  • The Whole Building Calibration Simulation requires information about the instruments that enable the project to monitor the categories listed in the IPMVP. 


  • The question of which systems need to be monitored is building-specific and is not prescribed by the credit requirements. 


  • Total energy consumption of the building must be tracked, along with any variables that may influence energy consumption. For example, in a hotel you would need to track occupancy. 


  • Projects must verify the savings of the efficiency measures. If individual metering capacity is not built into the project, the project must demonstrate some other firm commitment to obtaining this data. This requirement can be accomplished by providing a copy of the contract for data collection by a third party of individual meters. 

Construction Documents

Expand All

  • The M&V provider writes the M&V plan. If possible, involve the facility’s operational staff in writing the plan. The plan should lay out the measurement and response protocol. The M&V plan must define the following:

    • Baseline energy use
    • Post-construction energy use
    • Any adjustments that should be made to the baseline energy use

  • The industry standard for M&V plans, both in the U.S. and internationally, is the International Performance Measurement and Verification Protocol (IPMVP), owned by the nonprofit Efficiency Valuation Organization. LEED has singled out Volume III of the IPMVP guidance as the basis of its requirements, and several organizations have published M&V guidelines based on IPMVP. Among them are the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); the U.S. Department of Energy’s Federal Energy Management Program (FEMP); and some utilities and states that fund energy-efficiency projects. Some organizations with M&V standards offer guidance in writing M&V plans, including sample language.


  • Coordinate with the mechanical and electrical engineers to verify that the control devices will be able to provide the information needed for credit compliance.


  • The owner’s goals and IPMVP guidelines should drive the M&V plan, which should specify which systems are to be sub-metered and which are being spot metered, and how. The plan also explains how the energy end use is being predicted and measured, and how the M&V information will be used, such as adjusting building operations to reduce energy use. The plan shall also include a section on corrective action that will take place if the baseline energy use and the post-construction energy use vary greatly. 


  • The plan establishes who is responsible for managing the process during operations and for taking corrective action. The plan also establishes how long the monitoring will continue. 


  • The M&V provider demonstrates through a narrative that the M&V plan will be able to verify actual energy use. For energy systems that are not addressed in the M&V plan you will need to provide a detailed reason for exclusion in the narrative. 


  • The M&V plan should define the actions that will be taken by the facility manager to investigate the cause of any discrepancies found and correct any malfunctioning equipment. If goals are not met, or if unexpected performance occurs, the M&V systems will provide useful feedback in tracking the source of problems.


  • Variable loads such as dimming controls can be profiled with short-term measurements that determine a load value pegged against another variable point that can be measured or accurately estimated over time. ECMs have to be metered to obtain actual savings. Variable loads like dimming controls can be measured only by metering them first at full power and then at low power. Measure and plot the power use at various dimming points at consistent time intervals. 


  • Option B: Energy Conservation Measure Isolation


  • Determine the baseline energy use for the ECMs.

     


  •  The projected baseline energy use can be determined using energy efficiency standards or guidelines.


  •  Option D: Calibrated Simulation

     


  • Run a final energy model that reflects all of the as-designed energy-efficiency measures.  


  • The projected baseline energy use is calculated by an energy model during the design phase. All ECMs are removed from the model and this energy data becomes the baseline to determine energy savings when compared to the actual energy use. According to Option D of IPMVP III, the model must be calibrated so it is ready to be used after one year of data collection.


  • It is easiest to calibrate the as-built energy simulation software if submetering devices correlate with the breakdown of the energy usage in the energy model. 


  •  Where applicable, the M&V plan should specify submetering sensor locations. Define the specific sensors with their location and sampling rates. In the plan, define the required energy model output and how measured data will be compared to the energy model. Also define how loads are arranged and grouped in electric panels; mixing power, lighting and HVAC equipment loads within individual panels is not recommended. 

     

     

Construction

Expand All

  • The M&V submetering devices or BMS are installed and commissioned to verify functional accuracy.

     


  • Installation of the M&V system should be fairly straightforward. Depending on the system and the experience of the subcontractors, however, specialized contractors may be needed.


  • Option D: Calibrated Simulation 


  • Verify that the whole-building simulation model matches the as-built design. 

Operations & Maintenance

Expand All

  • The M&V plan is implemented for at least the first year of building operations.


  • Ensure that appropriate personnel are trained to optimize the system to its greatest potential.


  • Track and archive trending data with utility metering and energy submetering systems required by the M&V plan.


  • Provide a yearly summary report that identifies energy performance issues and corrective actions.


  • If there are discrepancies between projected energy use and actual use, identify the cause and follow the M&V plan for corrective action. Discrepancies may result from inaccuracies in the simulation model, actual building use that differs from anticipated occupancy, improperly functioning equipment, and switches and controls not being properly calibrated. 


  • Meters and submeters should be recalibrated periodically according to manufacturers’ recommendations.


  • Encourage the operations team to focus on running the building at optimal efficiency. 


  • Record any post-construction upgrades or changes to operations and maintenance in order to best understand post-construction energy use. 


  • A 5%–10% discrepancy between the baseline energy use and the post-construction energy use may account for operational changes in a good energy model. However, a 25% discrepancy would not be out of the ordinary. 


  • The payback period for M&V programs depends on the initial cost of additional meters and whether the program identifies inefficiencies that wouldn’t have been found otherwise. Some fixes may be substantial and will pay for the metering system. After the BMS or metering system has been installed, the true return depends on the commitment of the owner and operational staff. Because M&V monitors actual building operation over time, M&V procedures can lead to valuable operational savings by uncovering building system design, installation, and control issues not caught by commissioning. 


  • M&V systems require continuous energy use and staff attention. One of the larger costs associated with this credit is the time needed by staff to read, interpret, and act on feedback provided by the M&V system. Although more expensive to install, a complex building or a building with multi-tenant spaces can benefit financially from an integrated computerized BMS that assists in day-to-day management. 


  • Option B: Energy Conservation Measure Isolation


  • The facilities manager or M&V provider compares the baseline energy use of the ECMs to the post-construction energy use.


  • The ECM usage can be tracked with a simple spreadsheet and does not require complicated calculations or modeling.


  • Option D: Calibrated Simulation


  • Set up the BMS to provide monthly reports as required by the M&V plan, if applicable. 


  • Perform a calibrated building energy simulation model that reflects actual occupancy and weather, after the first year’s energy usage data becomes available. The energy modeler performs the calibrated simulation with the assistance of the M&V provider. 


  • The calibrated energy simulation gives the owner and facility operator a true picture of savings from the ECMs instead of the predicted savings from the energy model developed during design. A simulation model developed during design makes a lot of assumptions on occupancy patterns, set points and weather. A calibrated energy model replaces those assumptions with real data while accommodating unforeseen program changes. If the actual results are greater than 10% from the predicted ones, compare the differences between the assumptions and the actual settings. Calibration is a great learning opportunity for the modeler to verify those assumptions with actual data. After the first year, you do not need to recalibrate the model, instead using energy usage from utility bills to compare against energy usage from previous years. The calibrated model is compared to the actual energy consumption rates and changes need to be made to the model until acceptable calibration is achieved. After all calibration adjustments have been made to the as-built energy model the same changes need to be made to the baseline energy model. 


  • Energy savings is verified by either comparing the calibrated as-built model to the calibrated baseline model, or by comparing the calibrated baseline energy use to the actual metered energy use.


  • Twelve months of data from the metered categories is used to calibrate the computer simulation model. The M&V plan shall demonstrate the ability to identify specific problem areas if discrepancies exist between the modeled and metered data. When calibrating the as-built energy model, weather patterns must be reflected. You may be able to obtain this through the BMS. Calibration changes will also include occupancy and operational adjustments to reflect actual usage.


  • Calibration of the energy model will add a small cost on top of the cost of the baseline as-built energy model.

  • USGBC

    Excerpted from LEED 2009 for New Construction and Major Renovations

    EA Credit 5: Measurement and verification

    3 Points

    Intent

    To provide for the ongoing accountability of building energy consumption over time.

    Requirements

    Option 1

    Develop and implement a measurement and verification (M&V) plan consistent with Option D: Calibrated Simulation (Savings Estimation Method 2), as specified in the International Performance Measurement & Verification Protocol (IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits.), Volume III: Concepts and Options for Determining Energy Savings in New Construction, April 2003.

    The M&V period must cover at least 1 year of postconstruction occupancy.

    Provide a process for corrective action if the results of the M&V plan indicate that energy savings are not being achieved.

    OR

    Option 2

    Develop and implement a measurement and verification (M&V) plan consistent with Option B: Energy Conservation Measure Isolation, as specified in the International Performance Measurement & Verification Protocol (IPMVP) Volume III: Concepts and Options for Determining Energy Savings in New Construction, April, 2003.

    The M&V period must cover at least 1 year of postconstruction occupancy.

    Provide a process for corrective action if the results of the M&V plan indicate that energy savings are not being achieved.

    OR

    Option 3 (1 point)

    Meet MPR 6 through compliance Opttion 1: Energy and Water Data Release Form. Projects must register an account in ENERGY STAR’s Portfolio Manager tool and share the project file with the USGBC master account.

    Potential Technologies & Strategies

    Develop an M&V plan to evaluate building and/or energy system performance. Characterize the building and/or energy systems through energy simulation or engineering analysis. Install the necessary metering equipment to measure energy use. Track performance by comparing predicted performance to actual performance, broken down by component or system as appropriate. Evaluate energy efficiency by comparing actual performance to baseline performance.

    While the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. describes specific actions for verifying savings associated with energy conservation measures (ECMs) and strategies, this LEED credit expands upon typical IPMVP M&V objectives. Measurement & verification activities should not necessarily be confined to energy systems where ECMs or energy conservation strategies have been implemented. The IPMVP provides guidance on M&V strategies and their appropriate applications for various situations. These strategies should be used in conjunction with monitoring and trend logging of significant energy systems to provide for the ongoing accountability of building energy performance.

    For the corrective action process, consider installing diagnostics within the control system to alert the staff when equipment is not being optimally operated. Conditions that might warrant alarms to alert staff could include:

    • Leaking valves in the cooling and heating coils within air handling units;
    • Missed economizerAn economizer is a device used to make building systems more energy efficient. Examples include HVAC enthalpy controls, which are based on humidity and temperature. opportunities (e.g., faulty economizer damper controls) ;
    • Software and manual overrides allowing equipment to operate 24 hours a day/7 days a week;
    • Equipment operation during unusual circumstances (e.g., boiler on when outside air temperature is above 65 °F).

    Besides control diagnostics, consider employing retro-commissioning services or dedicating staff to investigate increases in energy usage (such a staff member is usually a resource conservation manager — see http://www.energy.state.or.us/rcm/rcmhm.htm for additional information).

Other

Efficiency Valuation Organization (EVO) Blog

M&V blog that is a place where the community can raise and discuss issues that arise in the practice of valuing efficiency projects. 

Technical Guides

IPMVP Volume I and III

IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. is the standard upon which the LEED M&V requirements are based. Use these documents should be used in designing the M&V system and plan. 


Applications Team, Energy-Efficiency Design Applications: Measurement & Verification Documents

This website provides a list of resources to help teams implement an M&V program.


M&V Guidelines: Measurement and Verification for Federal Energy Projects

These M&V guidelines are written for federal buildings but could be helpful for many projects. 


ASHRAE Guidelines 14-2004

ASHRAE provides technical guidelines for designing an M&V plan. This document can assist project teams in designing and implementing the M&V systems and plan.  

Organizations

The Energy Valuation Organization and the Association of Energy Engineers

The Energy Valuation Organization, in conjunction with the Association of Energy Engineers, offers an M&V professional certification program. The Association of Energy Engineers holds training seminars for those preparing to take the certification exam and anyone else interested in learning the fundamentals of M&V and working with IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits..  

Publications

Energy Management Handbook, By Wayne C. Turner, Steve Doty

Chapter 27 covers Measurement and Verification of Energy Savings and has some very useful information from the history of M&V, including various methods and equipment. 


Environmental Building News, June 2006.

This article discusses the usefulness of M&V, including examples of problems that M&V systems have been able to identify. 

Software Tools

WATERGY Software

NOTE: WATERGY is not currently available, but may be again in the future.

WATERGY is a spreadsheet model that uses water and energy relationship assumptions to analyze the potential of water savings and associated energy savings. 

Web Tools

USGBC Building Performance Partnership

USGBC’s Building Performance Partnership (BPP) engages commercial and residential LEED building owners and managers in an effort to optimize the performance of buildings through data collection, analysis and action. This partnership among USGBC and the thousands of LEED project owners will result in the population of a comprehensive green building performance database, enable standardization of reporting metrics and analytics, and establish new performance benchmarks. USGBC’s BPP participants are eligible for annual performance reports, report cards and real-time data interfaces to aid in their building performance goals. Together, USGBC and BPP participants will transform the way the world views building operations.

Template for M&V Plan

Option D: Calibrated Simulation

The Measurement and Verification (M&V) plan template shown here is based on Option D: Calibrated Simulation.

M&V Plan Sample

Option D: Calibrated Simulation

This Measurement and Verification (M&V) plan sample follows Option D: Calibrated Simulation.

Construction Submittal

HardhatDocumentation for this credit is part of the Construction Phase submittal.

LEED Online Forms: NC-2009 EA

The following links take you to the public, informational versions of the dynamic LEED Online forms for each NC-2009 EA credit. You'll need to fill out the live versions of these forms on LEED Online for each credit you hope to earn.

Version 4 forms (newest):

Version 3 forms:

These links are posted by LEEDuser with USGBC's permission. USGBC has certain usage restrictsions for these forms; for more information, visit LEED Online and click "Sample Forms Download."

130 Comments

0
0
Alicia Silva CEO Revitaliza consultores
May 03 2013
LEEDuser Member
333 Thumbs Up

Sub-metering in Option D

Marcus Sheffer posted some months ago in this credit:

"You will need to calibrate the model by energy end use on a monthly (and annual) basis.
[...]
Yes you would need to separate out the electric end uses in order to calibrate the model. Whole building metered data is not sufficient."

HOWEVER

I am reading the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits., page 18, Table 2:

"How Savings Are Calculated:
[...]
Energy use simulation, calibrated with hourly or monthly UTILITY BILL data. (Energy end use metering MAY be used to help refine input data.)"

Therefore, sub-metering does NOT appear to be mandatory for credit compliance, since sub-metering MAY be used to help refine input data.

I am glad to have different insights to this issue.

GH

1
6
0
Alicia Silva CEO, Revitaliza consultores May 03 2013 LEEDuser Member 333 Thumbs Up

In addition, quoting the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. Vol III, Concepts and Practices for Determining Energy Savings in New Construction, Part I, page 18:

"Option D Involves of computer simulation of whole building energy use. The Post-Construction Energy Use is determined by utility metering and/OR submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). or by using an energy simulation model of the as-built building calibrated to metered energy use data."

GH

2
6
0
Jatuwat Varodompun Dr, Green Building Soultion May 03 2013 LEEDuser Member 40 Thumbs Up

I think I was the one who also asked Marcus regarding this issue. I think the reviewer will look for the method of how we can reach the end-use energy data. Some of them might require only runtime record if the equipment consume constant power. I used to create IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. plan this way and try to find the solution for obtain the data for each end-use (fan, chiller, pump, light, etc.). Yes, the submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). is not mandatory if you can find to solution to extract the end-use from the whole.

3
6
0
Marcus Sheffer LEED Fellow, 7group May 03 2013 LEEDuser Expert 19756 Thumbs Up

Good to see someone reading the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits.! I am not sure too many folks submitting M&V Plans have done so.

Let me see if I can explain the the rationale for needing energy end use data. First of all I do not believe I ever said that projects had to install submeters. There are several ways to get energy end use data and submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). is just one of them. Sometimes it is not even actual energy use data as it could be data you would use to calculate energy use. You are correct that submeters or any direct measurements of energy use by end use are not required.

You will still need to calibrate your energy model by energy end use and have a data gathering plan in place to enable it. If you just calibrated to the monthly utility data by fuel type you could very easily be over predicting one end use and under predicting another and on balance the result may "appear" to match but it doesn't. You will find that it is virtually impossible to get each month to match within a reasonable range. When it does not match then you will need to have some kind of energy end use data to figure out the discrepancy. So the M&V Plan must include a methodology to gather the data needed by energy end use. It cannot be an afterthought that you will figure out after the results do not match. I can guarantee that the monthly data will not match in all cases so you are going to need some additional data. I think anyone who has calibrated an energy model would attest to this fact.

Recently we gathered some whole building data for a project we modeled that was an all electric building. Our model was within 6 kWhA kilowatt-hour is a unit of work or energy, measured as 1 kilowatt (1,000 watts) of power expended for 1 hour. One kWh is equivalent to 3,412 Btu. in the annual total energy consumption. Pretty good huh? Well it turns out we over predicted heating and under predicted cooling and on balance we got lucky. Even if each month was within range we would not have a calibrated model.

Unfortunately the language in the IPMVP is often a bit vague. It sets out broad goals and lets you figure out how to get there. Based on first hand experience I can tell you that you can't calibrate to the utility bills without calibrating to energy end use. Another way to think about it is to focus on the outcome. The energy model basically needs to be fully reflective of the way the actual building operates in order to be accurately calibrated. Without any energy end use data I would suggest that it would be impossible to do so.

Now the question becomes do we need to measure or meter each energy end use? Probably not. Very small ones that do not have a big impact on the overall energy use can be estimated. Maybe HVAC can be lumped together instead of trying to break out fans, pumps, heating and cooling. Some end uses could be derived from subtraction. This starts to get very project specific and how you do it depends on many factors.

If you can make the case in your M&V Plan that you can accurately calibrate the energy model without any energy end use data I would like to read how you will do it. If you think it through you will find that it is not possible unless you have clairvoyant energy modelers!

4
6
0
Alicia Silva CEO, Revitaliza consultores May 06 2013 LEEDuser Member 333 Thumbs Up

Marcus, thanks for your comment. I think it was very clarifying.
Then, the key point is how to calibrate the model by energy end use. We have some ideas:

1.Sub-metering
2.Utility bills (in big projects utility bills could be differentiated by end use)
3.Data loggers that record energy use in different circuits according to the modeler's needs. Data could be recorded over a 7-day period (for example) and estimate the rest of the month.

Is this correct?
Someone could bring up more options?

5
6
0
Marcus Sheffer LEED Fellow, 7group May 06 2013 LEEDuser Expert 19756 Thumbs Up

Yes you are correct. Here are some others.

You can take spot measurements and use that data to calculate the energy use. For example, if I know that the lighting is a constant load (i.e. always on) and the schedule is consistent (on at the same time, off at the same time) I could use a clamp on meter, measure the wattage of each fixture type, count the fixtures and do the math.

I mentioned subtraction before. For example, if you meter lighting, hot water and HVAC you could derive plug loads by subtracting the submetered data from the utility meter data.

Some information can be obtained through interviews with operational staff. Things like occupancy and schedules are often obtained this way.

Commissioning activities often yield useful information what can be used in calibration.

Hand calculations could be used to verify very small constant loads if necessary.

And do not forget to calibrate the weather file to reflect the actual weather during the M&V period.

6
6
0
Alicia Silva CEO, Revitaliza consultores May 06 2013 LEEDuser Member 333 Thumbs Up

Absolutely helpful. Thanks again and I hope this helped other project teams to earn this credit.

GH

Post a Reply
0
0
Gustav Alfaro Mechanical Engineer
May 02 2013
LEEDuser Member
14 Thumbs Up

Defining the baseline

Hi to all:

Please help me to clarify how the baseline model is defined for the M&V plan, it is clear that for the "actual case" the proposed model created for the EAc1 must be calibrated based on energy bills and measured performance during one year; but how is defined the baseline mode for comparision purposes? Should it be the proposed model delivered for EAc1? Should it be the baseline model delivered for EAc1? Should it be the proposed model delivered for EAc1 substracting the ECMEnergy conservation measures are installations or modifications of equipment or systems intended to reduce energy use and costs. implemented during the design and construction?

Thank you a lot for your comments

1
4
0
Marcus Sheffer LEED Fellow, 7group May 02 2013 LEEDuser Expert 19756 Thumbs Up

You basically take the calibrated model of the building and use that to create another Appendix G baseline model. This is your calibrated baseline for comparison.

So the adjusted schedules, utility rates, occupancy, etc. that must be identical are taken from the calibrated model and applied to the Appendix G baseline model.

2
4
0
Gustav Alfaro Mechanical Engineer May 02 2013 LEEDuser Member 14 Thumbs Up

Thank you for your soon feedback. What you indicate is what I understood but the Reference Guide says "Calibration is achieved by adjusting the energy simulation model to reflect actual operating conditions and parameters. Next, the conservations measures are removed from the model to define the baseline..." so, this sentence is kind of confusing because it seems that, for instance, if one of the conservation measures was to insulate the walls, then in the EAc5 baseline models the walls should appear without insulation (removing the conservation measures). Id appreciate if you can clarify further.

3
4
0
Marcus Sheffer LEED Fellow, 7group May 02 2013 LEEDuser Expert 19756 Thumbs Up

They mean that you should take the level of wall insulation from what you have in your building back down to the code minimum insulation value. An Appendix G baseline does just that.

4
4
0
Gustav Alfaro Mechanical Engineer May 02 2013 LEEDuser Member 14 Thumbs Up

Thank you Marcus

Post a Reply
0
0
Lauren Fakhoury Research Assistant Sustainable Design Consulting, LLC
Apr 26 2013
LEEDuser Member
548 Thumbs Up

M&V Plan for Residential Project

Hi all,
I'm working on a residential project where the tenants do NOT pay their utility bills. The units are being individually sub-metered but the electric company does not provide a breakup per unit, instead a total bill goes to management. We are working to find out if a breakdown is possible, but in the meantime does anyone have experience creating an M&V plan for this type of project? Thanks.

1
3
0
Marcus Sheffer LEED Fellow, 7group Apr 26 2013 LEEDuser Expert 19756 Thumbs Up

We have explored the possibility of doing so on a couple residential projects. The complexity involved in gathering the necessary data is far higher with these types of projects and as a result each time we explored it it was abandoned as too difficult and expensive.

If you do pursue it I would suggest that perhaps you consider a sampling protocol for the units to keep the cost down.

2
3
0
Lauren Fakhoury Research Assistant, Sustainable Design Consulting, LLC Apr 29 2013 LEEDuser Member 548 Thumbs Up

Thanks, Marcus. I should clarify - the owner is willing to bear the cost. How do we get the information from the service provider if the tenant isn't responsible?

Thank you.

3
3
0
Marcus Sheffer LEED Fellow, 7group Apr 29 2013 LEEDuser Expert 19756 Thumbs Up

Getting the electric bills for some or all of the tenant spaces could be helpful but this is just a small part of the information you will need. Having the units sub-metered for electricity would be a good check against energy end use data you will need to gather from at least a sampling of units. If the units are sub-metered and the utility does not read them then you may need to read them yourself. Who owns the sub-meters?

As I said these projects are very difficult to properly implement M&V. In order to do this correctly you need to gather energy usage data for each energy end use, not just by fuel type. So lighting, heating, cooling, fans, plug loads, etc. This data can be gathered through building sub-meters installed by the owner or through a combination of short term trend meters and spot measurements. Sub-metering costs upfront but saves on labor during implementation. Gathering the data by hand (trend meters/spot measurements) is cheaper upfront but prohibitively expensive in all but relatively small buildings.

Just so your owner is aware, the metering and implementation cost to do this right for even a medium-size residential project could easily be $50,000 to $100,000. This is why most projects take the easy Option 3 point and run away from the M&V Plan. How many units and what is the square footage of your project?

Post a Reply
0
0
Josh Chapman
Apr 08 2013
Guest

EAc5 Measurement & Verification in Multi-family Projects

Hi All,

I am working on a New Construction, 299 dwelling unit Apartment building, pursuing Option D. All apartments have their own electric meter, paid directly by the tenants. The apartments represent over 68% of the overall energy usage of the building (based on the proposed EAc1 simulation).

How is one supposed to calibrate the proposed simulation when 1) the owner doesn't receive any of the tenants energy bills 2) energy consuption/demand are greatly dependent on the tenants living habits (T'stat set points, occupancy, lifestyle, etc)? Obviously, some type of data sampling (for measurement) could take place, but it would also require the tenant submitting their electric bills (and hopefully a statement of t'stat setpointsSetpoints are normal operating ranges for building systems and indoor environmental quality. When the building systems are outside of their normal operating range, action is taken by the building operator or automation system.).

What is a recommended sampling rate? What is a realistic calibration tolerance when so much of the energy usage is dependent on occupant lifestyles?

I assume the sampling is used to project an average for the tenant spaces. If that is the case, what would trigger 'corrective actions' for tenants, since any deviations from projected saving could easily be assumed to be caused from Tenant lifestyle?

Any suggestions would be helpful.
Thanks,
Josh

1
1
0
Marcus Sheffer LEED Fellow, 7group Apr 10 2013 LEEDuser Expert 19756 Thumbs Up

I think that sampling could work for a project like that. Off the top of my head something like at least 10% of the units would need to be included. In addition to the overal electric usage you would need to figure out how to determine energy use by end use (lighting, HVAC, plug loads, etc.) within each of the sampled units. How you do that would need to be part of the Plan.

Typical tolerances are +-10% on a monthly basis for each energy end use.
Corrective actions are triggered if the savings are not within the tolerance following the calibration.

You would also need to extrapolate the results of the sample to the whole building and the entire building calibration would need to be within the established tolerance.

Unfortunately apartment building are much more difficult to do correctly than many other building types so this credit is not often pursued for this project type.

Post a Reply
0
0
Kelly Duepner LEED BD+C Christner Inc.
Mar 27 2013
LEEDuser Member
51 Thumbs Up

Responsible party for preparing M&V plan

What are the pros and cons of having either the MEP engineers or the CxAThe commissioning authority (CxA) is the individual designated to organize, lead, and review the completion of commissioning process activities. The CxA facilitates communication among the owner, designer, and contractor to ensure that complex systems are installed and function in accordance with the owner's project requirements. be responsible for documenting the M&V plan?

1
1
0
Marcus Sheffer LEED Fellow, 7group Apr 10 2013 LEEDuser Expert 19756 Thumbs Up

It depends on the individuals involved. It is very hard to make such generalizations but in general the CxAThe commissioning authority (CxA) is the individual designated to organize, lead, and review the completion of commissioning process activities. The CxA facilitates communication among the owner, designer, and contractor to ensure that complex systems are installed and function in accordance with the owner's project requirements. is probably in a better position to do this work since they are already going be doing some of the work required. Be careful however that whoever does it must have a thorough and complete understanding of what needs to be done. M&V is not just some enhancement to the Cx1. Commissioning (Cx) is the process of verifying and documenting that a building and all of its systems and assemblies are planned, designed, installed, tested, operated, and maintained to meet the owner's project requirements. 2. The process of checking the performance of a building against the owner's goals during design, construction, and occupancy. At a minimum, mechanical and electrical equipment are tested, although much more extensive testing may also be included. process and requires a somewhat different focus.

Who is doing the project's energy model? Typically whomever does the initial modeling would need to be involved in the M&V effort.

Post a Reply
0
0
Dan Milewski
Mar 04 2013
Guest
14 Thumbs Up

EAc5 Measurement and Verification Option 3

Is Option 3 (1 point) - Meet MPR 6 through compliance Opttion 1: Energy and Water Data Release Form.

Is option 3 available as a stand alone option or only as a exemplary performanceIn LEED, certain credits have established thresholds beyond basic credit achievement. Meeting these thresholds can earn additional points through Innovation in Design (ID) or Innovation in Operations (IO) points. As a general rule of thumb, ID credits for exemplary performance are awarded for doubling the credit requirements and/or achieving the next incremental percentage threshold. However, this rule varies on a case by case basis, so check the credit requirements. if Options 1 or 2 are achieved (i.e. do not need to achieve options 1 or 2 to get the one point).

Thanks

1
4
0
Marcus Sheffer LEED Fellow, 7group Mar 04 2013 LEEDuser Expert 19756 Thumbs Up

You earn one point for EAc5 if you agree to provide your data under MPR 6.

2
4
0
Dan Milewski Mar 04 2013 Guest 14 Thumbs Up

So it is basically a free point by just complying with the MPRs

3
4
0
Dan Milewski Mar 04 2013 Guest 14 Thumbs Up

Also, how far back can this point be claimed? I am working on a project that is under the NC-2009 rating system and is currently under review, but project was registered a couple years ago and at the time we indicated that we would be attempting 3 points for EAc5. However it looks like we will be at 59 points (1 point short of our desired Gold). We have been in the process of trying to get together the M+V Plan but with a significant cost. It would be great if we can stop our efforts and get the additional point under EAc5 Option 3.

Any help you can provide is appreciated.

4
4
0
Marcus Sheffer LEED Fellow, 7group Mar 04 2013 LEEDuser Expert 19756 Thumbs Up

Basically.

You could change your mind and pursue this option in the middle of your review.

Post a Reply
0
0
Margaret McColl Sustainability Specialist
Feb 26 2013
Guest
9 Thumbs Up

How to Determine and Overall M&V Accuracy

IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. Vol III requires the M&V Plan to include the "expected overall M&V accuracy" (pg 9) and in Section 4.5.9 Option D: Uncertainty it refers to ASHRAE Guideline 14 for guidance. ASHRAE Guideline 14 gives an accuracy example of 10% uncertainty with 90% confidence - I have seen this accuracy statement in a M&V Plan before, but I doubt it was determined using the rigorous calculations in the Guideline. The Guideline is also not really meant to be used on new buildings...

Does anyone have experience determining an overall M&V accuracy, with or without ASHRAE Guideline 14?
Is a 10% uncertainty with 90% confidence statement typically used with Option D?

Any in-sight or guidance would be greatly appreciated.

1
1
0
Marcus Sheffer LEED Fellow, 7group Feb 26 2013 LEEDuser Expert 19756 Thumbs Up

Make sure you have both a monthly and annual target for each energy end use. It is not sufficient to have only an annual total accuracy target. Typically the targets are expressed as +-XX%. The target can vary but is usually in the 5% to 20% range depending on the situation and the project. +-10% is a very commonly used value in alignment with Guideline 14.

There was a post by Gord Shymko in one of these EAc5 credit forums with more detail on this issue. Might want to search the other versions of LEED under this credit.

Post a Reply
0
0
Genko Ganev
Feb 25 2013
Guest

LEED NC 2009 - EAc5 - M&V

Would GBCI accept meter data entry into Energy Star Portfolio Manager for 12 months period as an approved method for M&V for new construction?

1
1
0
Tristan Roberts LEED AP BD+C, Editorial Director – LEEDuser, BuildingGreen, Inc. Feb 25 2013 LEEDuser Moderator

Genko, please see Option 3 in the EAc5 credit language, above.

Post a Reply
0
0
Yu Wang Mechanical Engineer SCHOLZE Consulting GmbH
Feb 04 2013
Guest
89 Thumbs Up

Electricity Consumption - Option D

I'm working on an option D M&V plan according to LEED. The building is heated and cooled with gas heat pumpA type of heating and/or cooling equipment that draws heat into a building from outside and, during the cooling season, ejects heat from the building to the outside. Heat pumps are vapor-compression refrigeration systems whose indoor/outdoor coils are used reversibly as condensers or evaporators, depending on the need for heating or cooling. In the 2003 CBECS, specific information was collected on whether the heat pump system was a packaged unit, residential-type split system, or individual room heat pump, and whether the heat pump was air source, ground source, or water source., therefore the electricity consumption just includes fan/pump power, process load and lighting.
If I have just whole building electric meter, can I use the following declaration to divide the electricity consumption in three parts?
1. pumps and fans (constant volume fan) electricity consumption: calculated with energy demand and run time
2. process load electricity consumption: calculated with occupancy time and energy demand.
3. lighting electricity consumption: subtract from the whole building electricity consumption.
Is it necessary to divde the electricity consumption separately?
Thanks!

1
3
0
Marcus Sheffer LEED Fellow, 7group Feb 04 2013 LEEDuser Expert 19756 Thumbs Up

You will need to calibrate the model by energy end use on a monthly (and annual) basis.
1. if you trend this data you could figure out energy use
2. how will you determine energy demand? It will need to be measured.
3. subtraction from metered data is a viable method
Yes you would need to separate out the electric end uses in order to calibrate the model. Whole building metered data is not sufficient.

2
3
0
Yu Wang Mechanical Engineer, SCHOLZE Consulting GmbH Feb 04 2013 Guest 89 Thumbs Up

For the process load, I can know the energy demand for computers, printer, elevator, dishwasher etc. The computer energy consuption can be calculated with occupancy time, and the other energy consumption with operating time. But this method is not exact. Will this solution be accepted?

3
3
0
Marcus Sheffer LEED Fellow, 7group Feb 04 2013 LEEDuser Expert 19756 Thumbs Up

But how do you know the actual energy demand for those items? Rated and actual are often very different. You will need to measure actual consumption. This can be through direct sub-metering, spot measurements, short-term trends, derived from other measured data, etc. This cannot be based on the same method used to make the prediction. You need to measure something in the actual operation of the building to confirm the consumption you predicted. If it is not the same then you make adjustments (calibrate) to the model until the values match within your tolerance range.

Under Option D you are attempting to make adjustments to your model so that it matches the utility bills (monthly and annually by end use). So what information do you need in order to do that? Totals are not enough because even if you match exactly you could just be lucky. We did an energy model a couple of years ago that was within 6 kWhA kilowatt-hour is a unit of work or energy, measured as 1 kilowatt (1,000 watts) of power expended for 1 hour. One kWh is equivalent to 3,412 Btu. based on the first year of actual operation. When we looked at the monthly data we under-predicted heating and over predicted cooling and on an annual basis we just got lucky. But as you can see just because some numbers match does not mean we had a calibrated model. The whole point of Option D is to create that calibrated model which is then used to verify savings relative to a calibrated baseline.

If you understand what you are trying to do the question of what to meter and how to do it usually falls into place.

Post a Reply
0
0
Tatiana Machado
Jan 22 2013
Guest
10 Thumbs Up

illumination metering with a photovoltaic system?

A project illumination system is controlled by a photovoltaic system. This system has a rechargeable battery as its primary energysource and as an auxiliary source it utilizes grid power.
Is necessary to individually measure the energy consumption of this system?

1
1
0
Marcus Sheffer LEED Fellow, 7group Jan 22 2013 LEEDuser Expert 19756 Thumbs Up

Very hard to say from the limited information provided. IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. does not require you to measure every energy use. Can the use be derived by other means, say subtraction? Is the use virtually inconsequential (less than 1% of total consumption)?

Sounds like exterior lighting powered by a battery which is charged by photovoltaics and the system is controlled by a photocell? If so as a renewable energy source it should be measured. This does not means it needs to be metered. Can the usage be derived by other means?

Post a Reply
0
0
Jatuwat Varodompun Dr Green Building Soultion
Dec 12 2012
LEEDuser Member
40 Thumbs Up

Submetering of each ECM

Can the submeters for optionD are only provided to cover all ECMs. For instance, if we aim to measure the pump energy, the submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). for the pumps will be provided. On the contrary, if we don't have any ECM of process energy, then the submetering for that portion is not required. would this will satisfy the EAc5 requirements?

Thanks

1
4
0
Marcus Sheffer LEED Fellow, 7group Dec 13 2012 LEEDuser Expert 19756 Thumbs Up

Under Option D you need to calibrate the entire energy model. You are not evaluating ECMs in isolation, that is Option B. However this option rarely applies to new construction since it is not appropriate for projects with interactive ECMs. So you need to either measure or be able to derive every major energy end use.

2
4
0
Jatuwat Varodompun Dr, Green Building Soultion Dec 13 2012 LEEDuser Member 40 Thumbs Up

What if we mornitor the enitre cooling system, so it will include cooling tower and chiller and pump under one sub-meter. is this considered submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). of "major" system of the HVAC? we are not plan to measure pump, chiller, and cooling tower saperately.

Does the electric domestic hotwater consider as a major energy components to be submeterSubmetering is used to determine the proportion of energy or water use within a building attributable to specific end uses such as tenant spaces, or subsystems such as the heating component of an HVAC system.?

thanks

3
4
0
Marcus Sheffer LEED Fellow, 7group Dec 13 2012 LEEDuser Expert 19756 Thumbs Up

I am not going to be able to tell you what you should submeterSubmetering is used to determine the proportion of energy or water use within a building attributable to specific end uses such as tenant spaces, or subsystems such as the heating component of an HVAC system. as I am not familiar with the project. You will need to answer this question for yourself relative to each end use - does this measurement give me the data I need to calibrate my energy model? Whether you submeter or not is generally a question of the efficiency of implementing the plan. SubmeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system). generally reduces the time you have to spend in the building gathering data by hand so it is often more efficient to gather data this way but that must be weighed against the cost of the submetering.

In general what you propose would potentially get you the cooling and some or all of the pump energy. Some modeling software separates the cooling tower end use from the chiller so you may need to somehow gets an idea of the relative energy use of each. Figure a way to break out the pumps from the total and those end uses might be covered. For example, if the pumps are variable speed then the controlled can often be programmed to gather the pump data needed to determine energy use.

Domestic hot water in a hotel is generally a major energy user. Anything over say 5% of the total energy use would be major in my opinion.

4
4
0
Jatuwat Varodompun Dr, Green Building Soultion Dec 13 2012 LEEDuser Member 40 Thumbs Up

Thanks so much.

Post a Reply
0
0
Jatuwat Varodompun Dr Green Building Soultion
Dec 12 2012
LEEDuser Member
40 Thumbs Up

Submetering

For Option D, do we need submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system).? and can it be analyzed using only whole building energy? if we required submetering, what level we have to monitored eg HVAC, lighting, process? do we have to cover it all or just some?

thanks

1
3
0
Marcus Sheffer LEED Fellow, 7group Dec 12 2012 LEEDuser Expert 19756 Thumbs Up

You need data gathered by each energy end use, so yes you must cover all of it. How you get the data depends on what is the most cost-effective means to gather it. So sub-metering is not specifically required. You can gather this data with spot measurements, short term trending meters, or even derive it by subtraction (i.e. you measure all electrical use except plug loads so you can derive plug loads by subtracting from the whole building electric meter).

Your focus in Option D is to gather the data you need to calibrate the energy model. So your plan should detail how you are going to gather the data. The data may not even be direct energy use. For example, a measurement of run time on a constant volume fan will allow you to derive energy use.

The level of monitoring varies depending on the project. Some projects may be small enough to lump all HVAC together and still enable a reasonable M&V approach. Some larger projects would probably require data gathering from system components.

M&V is pretty simple - gather the data you need to calibrate your energy model; calibrate your energy model to the utility bills (monthly and annually); create a revised baseline model from your calibrated model; the difference is your verified savings. Basically measure - verify.

2
3
0
Jatuwat Varodompun Dr, Green Building Soultion Dec 12 2012 LEEDuser Member 40 Thumbs Up

Thanks so much Marcus.

What if my project is a hotel with many guest rooms. I have submeterSubmetering is used to determine the proportion of energy or water use within a building attributable to specific end uses such as tenant spaces, or subsystems such as the heating component of an HVAC system. for each room but it measure all the energy use in a room not the enduse. Any suggestion for this case.

Jatuwat

3
3
0
Marcus Sheffer LEED Fellow, 7group Dec 13 2012 LEEDuser Expert 19756 Thumbs Up

You could use the sub-metered room data to verify spot or short-term trend measurements in a sampling of rooms. Assume you are sub-metering electric only right? For all the plug in devices you could use Kill-a-watt meters. For the hard wired you could use clamp on meters for spot measurements or trending meters like the ones from Hobo to gather the data you need. Add it up and use the whole room meter to verify your measurements. So you could gather data in say 10% of the rooms, apply occupancy data for the rooms and extrapolate for the whole building.

Post a Reply
0
0
Dena Eckman Sustainability Technician Karpinski Engineering
Dec 03 2012
LEEDuser Member

EAc5 Option 3

We have a large project that is on a DES - We meet the criteria that forces us to include upstream DES equipment. It is a City DES system and the system info is pretty much unobtainable, also the project is much to large to do a Model recalibration. the customer wants to know about the 1 point option? (option 3- Portfolio Manager). The treatment of DES in LEED does not state anything about Option 3. Can a project on a DES pursue Option 3 and if so is the DES information required to be reported? Has anyone run into this?

1
1
0
Marcus Sheffer LEED Fellow, 7group Dec 03 2012 LEEDuser Expert 19756 Thumbs Up

If the building you are submitting meters the incoming DES energy use then you should be able to use the reporting option.

Post a Reply
0
0
Jodie Clarke Commercial Services Manager O'Brien & Company
Nov 08 2012
LEEDuser Member
35 Thumbs Up

EAc5 Exemplary Performance

The guidance for exemplary performanceIn LEED, certain credits have established thresholds beyond basic credit achievement. Meeting these thresholds can earn additional points through Innovation in Design (ID) or Innovation in Operations (IO) points. As a general rule of thumb, ID credits for exemplary performance are awarded for doubling the credit requirements and/or achieving the next incremental percentage threshold. However, this rule varies on a case by case basis, so check the credit requirements. specifies the NC, CS and Schools rating systems. I would like to get credit for following Option 2 and 3 for Healthcare. Does anyone know if GBCI would award an exemplary performance point in HC?

1
1
0
Marcus Sheffer LEED Fellow, 7group Nov 08 2012 LEEDuser Expert 19756 Thumbs Up

I think it would be eligible there too.

Option B however is severely limited in new construction/major renovation projects since it is not applicable to projects with a series of interactive energy efficiency strategies. Often it is not possible to isolate and evaluate each one as required under Option B in LEED projects and it is very rarely applied.

Post a Reply
0
0
Eric Longfellow Project Manager Trinity Management Group llc
Jun 12 2012
LEEDuser Member
180 Thumbs Up

M&V baseline for retrofit?

Hi, we are working on a extensive renovation of a 80,000 SF university classroom/office building using LEED NC 2009. Most of the mechanical cooling will be removed and it will be restored to naturally ventilated with fan assist and nighttime dehumidification.

I'm seeking clarification on what kind of modeling will meet the requirement for the baseline. This credit references IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. Volume III for New Construction in gathering a hypothetical baseline - one that, in other posts here, it was confirmed should also meet the "proposed case" in EAc1.

However in our case the building has been extensively wired and many monitoring points put in. 12 months of ongoing data collection will cease next month and then the baseline and projected savings will be modeled on this. The draft M&V plan submitted by the consultant (not written specifically for LEED conformance) uses Option B and Option C. The model to be used does not appear to be tied to ASHRAE 90.1-2007/Appendix G or the EAc1 model. Is there still a way we can meet the requirements of this credit to receive 3 points? The IPMVP manual itself in chapter 2 does not specify how the baseline is to be calculated, but LEED does. Thanks!

1
2
0
Marcus Sheffer LEED Fellow, 7group Jun 12 2012 LEEDuser Expert 19756 Thumbs Up

Option C is explicitly prohibited for LEED and Option B is usually only allowed in very limited circumstances. The Baseline should be the same as was submitted for EAp2/EAc1.

It sounds like you have not yet submitted your M&V Plan to LEED but the LEED submission is not final? If you are still in the review process you can revise the M&V Plan, follow Option D and still get the points.

If you will have the data needed to calibrate the model with the actual utility bills then just create a calibrated baseline and determine the savings.

2
2
0
Eric Longfellow Project Manager, Trinity Management Group llc Sep 24 2012 LEEDuser Member 180 Thumbs Up

Thank you very much Marcus. We are having a separate consultant do the LEED compliant M&V plan.

Post a Reply
0
0
Ameet AA
May 15 2012
LEEDuser Member
324 Thumbs Up

LEED MV Credits compliance with Option D

To achieve this credit, during the CONSTRUCTION Stage we just have to submit the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits.-OPTION D compliant Measurement and Verification Plan together with Diagram showing the locations of any meters needed for measurement and

NOT the calibrated baseline energy simulation results?

If it is true then it seems more like a commitment through a Plan rather than submitting actual Energy savings derive after post occupancy?

Please advice,
Thank you

1
2
0
Dylan Connelly Mechanical Engineer, Integral Group May 15 2012 LEEDuser Expert 2972 Thumbs Up

Ameet,
You are correct. LEED NC is a Design and Construction tool. It does not require you to submit follow up information Post Occupancy. This is true other similar credits which require follow up by the project team but no additional documentation: IEQc7.2, EAc3, etc.
The Living Building Challenge is a rating system that is based on actual performance rather than only design.

2
2
0
Tristan Roberts LEED AP BD+C, Editorial Director – LEEDuser, BuildingGreen, Inc. May 15 2012 LEEDuser Moderator

Dylan is correct, but I would note that the Living Building Challenge is comparable as another design and construction system that follows up after occupancy.

LEED-EBOM is another LEED rating system that addresses actual building performance.

Post a Reply
0
0
Robert Himmler EGS-plan International GmbH
Mar 29 2012
LEEDuser Member
401 Thumbs Up

"required" metered systems

On this webpage in EAc5, I read that there are "Commonly metered systems", including lighting , motors, HVAC loads etc. In my case a part of items in this list seem not helpful on the model caliberation in the future but noted "required". For instance, the VFDA variable frequency drive (VFD) is a device for for controlling the speed of a motor by controlling the frequency of the electrical power supplied to it. VFDs may be used to improve the efficiency of mechanical systems as well as comfort, because they use only as much power as needed, and can be adjusted continuously. operations - Required, and HVAC Systems, equipment, and controls – Required, etc. I don't think I can use these data for my model caliberation process. In a thread it is said that the LEED-CI 2009 has used the old version LEEDNC2.2 to explain the credit and now lists out all the requirments for submeteringSubmetering is used to determine the proportion of energy use within a building attributable to specific end uses or subsystems (e.g., the heating subsystem of an HVAC system).. Is this list valid now? Do I have to follow this list -although I am not quite sure what it is exactly about VFD Operations and how it is metered. Currently in my M&V plan I am just able to measure by energy end uses like lighting, plug, process, etc, which can be compared directly with my simulation results .

1
1
0
Marcus Sheffer LEED Fellow, 7group Mar 29 2012 LEEDuser Expert 19756 Thumbs Up

Based on the IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. there are no requirements for any permanent metering. I cannot address the list above as I did not write it, however, your M&V Plan must include a thorough description of the data acquisition strategies for getting the data you will need to calibrate your model. If your metering is set up to directly measure or derive all of the energy end uses from your model this part of your M&V Plan should be covered.

Post a Reply
0
0
Karoline Geneser Engineer M. Sc., LEED AP Niras
Mar 02 2012
LEEDuser Member
36 Thumbs Up

Baseline in LEED reference guide and IPMVP

Considering EAc5, both LEED Reference Guide and IPMVPThe International Performance Measurement and Verification Protocol (IPMVP) provides best-practice protocol for measurement and verification of new construction. This standard is referenced in LEED's measurement and verification credits. use the term “Baseline”. Are both documents referring to the Baseline Simulation Model developed for EAc1, where a model of the building is made using standardized input for installations and constructions etc.?

1
1
0
Marcus Sheffer LEED Fellow, 7group Mar 02 2012 LEEDuser Expert 19756 Thumbs Up

Yes and no. The same model used for EAc1 should be used for EAc5. The difference is that the EAc5 baseline has been created from the Proposed model which has been calibrated to reflect the actual final construction, operating schedules, weather, etc.

Post a Reply
0
0
Maura Adams Environmental Stewardship Manager
Jan 10 2012
Guest
1620 Thumbs Up

Developing the plan post-construction

Is there any reason that we couldn't develop an M&V plan post-construction, assuming we have the necessary controls in place?

1
1
0
Marcus Sheffer LEED Fellow, 7group Jan 10 2012 LEEDuser Expert 19756 Thumbs Up

You can develop a M&V Plan anytime prior to your construction submission for LEED. The controls relate only as your control system is set up to provide at least some of the data you will need to perform the M&V. At this point you are basically stuck with the currently installed data collection which was installed (unless you want to spend more money) so depending on the set up you may have to gather data the old-fashioned way through spot measurements and short-term trending meters.

Post a Reply
0
0
Jeff Ross-Bain, PE, LEED AP BD+C Principal Ross-Bain Green Building
Oct 25 2011
LEEDuser Member
80 Thumbs Up

Option 3 - Whole Building Reporting / Energy Star PM

Energy Star Portfolio Manager does not cover all building types. Were a building to not fall into an Energy Star category, is it allowed to simply report the whole building energy and water use through another means (i.e. spreadsheet)?
Thanks!

1
1
0
Marcus Sheffer LEED Fellow, 7group Oct 25 2011 LEEDuser Expert 19756 Thumbs Up

Even though Portfolio Manager does not cover your building type you can still enter the data for USGBC through it. Alternatively you can send the data to USGBC. Contact LEEDPerformance@usgbc.org for specific instructions.

Post a Reply
0
0
André Knutsson Environmental engineer - Mc S. Civile Engineering YIT Buildings Systems AS
Oct 24 2011
Guest
194 Thumbs Up

M&V plan - Option D vs. Energy Standard

Our LEED project is situated in Norway. We had to run energy simulations after ASHRAE 90.1-2007 for LEED purposes. However the "real" energy simulations for the building is run after NS3031:2007 the Norwegian standard for energy use in builings. This is also the standard which gives the framework for the building in operations. The question is then what standard to use in the M&V plan ? If the EA c5 should have som meaning for us I suppose we have to use NS3031:2007 ?

1
2
0
Marcus Sheffer LEED Fellow, 7group Oct 24 2011 LEEDuser Expert 19756 Thumbs Up

You might be able to use the local standard but it would imply some risk in LEED.

The purpose of this credit is to verify the energy savings you predicted under EAc1 Optimize Energy Performance. Using something other than the model you have submitted for EAc1 will require much explaining and justification. You may or may not be able to do so, but trying to use the local standard is risky for LEED.

Just like you had to do a model under 90.1-2007, the M&V Plan should be based on it too. Sounds like you have to use NS3031:2007 in operations anyway.

2
2
0
André Knutsson Environmental engineer - Mc S. Civile Engineering, YIT Buildings Systems AS Oct 25 2011 Guest 194 Thumbs Up

Thanks Marcus.
I guess we have to discuss this with the building owner. There will be some more work to be done, and a little bit higher cost for operations on the maintenance staff.

Post a Reply
0
0
Robert Hink Principal, LEED Faculty The Spinnaker Group
Sep 08 2011
LEEDuser Member
445 Thumbs Up

Highrise condo - What to monitor and meter

With a 54 unit highrise condo, what would be acceptable to meter to meet the requirements of the credit. Individual unit electric meters? I can't imagine putting CTs on 130 individual heat pumpA type of heating and/or cooling equipment that draws heat into a building from outside and, during the cooling season, ejects heat from the building to the outside. Heat pumps are vapor-compression refrigeration systems whose indoor/outdoor coils are used reversibly as condensers or evaporators, depending on the need for heating or cooling. In the 2003 CBECS, specific information was collected on whether the heat pump system was a packaged unit, residential-type split system, or individual room heat pump, and whether the heat pump was air source, ground source, or water source. units? There is no lighting control panels per se to monitor. What would you suggest we monitor as part of the M&V plan

1
1
0
Marcus Sheffer LEED Fellow, 7group Sep 19 2011 LEEDuser Expert 19756 Thumbs Up

Hey Rob,

The metering needs to get to individual energy end uses (i.e. lighting, plug loads, HVAC, etc.) and does not have to be permenent. You might consider doing some spot measurements and short-term trending on a sampling of units as a possibility if you can get enough owners to cooperate. Having a whole unit meter on those would be a good idea too (assuming that the units are not separately metered already).

You don't have to measure everything but need to derive everything based on your measurements.

Post a Reply
0
0
Maura Adams Environmental Stewardship Manager
Aug 16 2011
Guest
1620 Thumbs Up

It doesn't seem like this

It doesn't seem like this credit should be so complicated. We have a full DDC system in the new building, which is part of a campus. We already have a Honeywell team on site to monitor other buildings and rectify problems, and they'll be doing the same for the new building. Can't we just write up a summary of the DDC points and how exactly they'll be monitored and problems acted upon?

1
1
0
Marcus Sheffer LEED Fellow, 7group Sep 19 2011 LEEDuser Expert 19756 Thumbs Up

The purpose of this is to validate energy savings.

DDC points and the information needed to perform the verification are very different things in many cases.

Post a Reply
0
0
April Ambrose Sustainability Consultant: Senior Project Manager Viridian
Aug 11 2011
LEEDuser Member
2413 Thumbs Up

Energy Star Portfolio Manager Naming

PIf4 says: Note: Project titles in portfolio manager must be the same as the LEED registered project name. Projects must also include their LEED project identification number in the notes portion of each Portfolio Manager registered property. The notes section is located on the "General Facility Information" page.

However, we are working on a publicly funded university that is considered a 'state' building. The state is currently benchmarking all of their facilities in Portfolio Manager. However, the consultant doing the benchmarking is required to label these in a very specific manner per their contract with the state. As you can see from the above text, USGBC requires a separate naming function. The facility will be benchmarked, but will we not get the credit because we couldn't name the facility according to the USGBC requirements? Any ideas on this?

Start a new LEED comment thread

May 19 2013
Type the characters you see in this picture. (verify using audio)
Type the characters you see in the picture above; if you can't read them, submit the form and a new image will be generated. Not case sensitive.

Copyright 2013 – BuildingGreen, Inc.