NC-2009 IEQp1: Minimum IAQ Performance

  • NC Schools IEQp1 credit reqs diagram
  • Baseline for outdoor air ventilation

    This prerequisite establishes a baseline for providing a minimum amount of outdoor air to buildings in order to maintain good indoor air quality and keep occupants comfortable and healthy. This prerequisite references ASHRAE 62.1-2007 (with errata but without addenda) and is often more stringent than local building codes, although it is not likely to entail any added costs.

    Two cases, both may be needed

    The compliance paths for mechanically ventilated and naturally ventilated spaces, Case 1 and Case 2, are somewhat different and you may need to follow both paths for the same building on a space-by-space basis. Spaces served only by natural ventilation must follow the distinct requirements set out in Case 2, even if other spaces in the same building are mechanically ventilated and are following Case 1. Mixed-mode spaces which alternate between natural or mechanical ventilation must follow the compliance path for mechanical ventilation, Case 1.

    For additions and major renovations, confirm that all ventilation systems serving the project meet the ventilation rates required by ASHRAE 62.1 2007, even if the ventilation system design itself is outside the scope of the project. If base buildingThe base building includes elements such as the structure, envelope, and building-level mechanical systems, such as central HVAC, etc. systems do not meet the standard’s requirements, you will need to either increase ventilation rates to comply or provide detailed analysis documenting the constraints and explaining why the base building systems cannot be upgraded.

    There’s some confusion in this language on whether mixed-mode refers to a ventilation design with both natural and mechanical ventilation all the time, which needs to be divided up to show compliance, or to a system where either is optional, in which case the worst-case design conditions are for when only the mechanical systems are used and window are shut.

    Any ventilation systems serving the project are covered

    Commercial interior projects will need to confirm that any ventilation systems serving the project meet the ventilation rates required by ASHRAE 62.1-2007, even if the ventilation system design itself is outside the scope of the project. If base building systems cannot be modified to meet the standard’s requirements, you will need to provide detailed analysis documenting the constraints and explaining why the base building systems cannot be upgraded. Systems must be able to provide at least 10 cfm per person to meet this prerequisite.

    ASHRAE 62.1: 2007 vs. 2004

    The 2007 edition of ASHRAE 62.1 combines  62.1-2004 and the eight approved and published addenda to the 2004 edition. The new edition does the following:

    • Clarifies dehumidification analysis requirements and offers exceptions to the 65% relative humidity limit requirement and to the net-positive intake-airflow requirement.
    • Corrects occupant category inconsistencies and provides additional information for several occupancy categories.
    • Updates references and clarifies the text particularly as related to subjective evaluation of air quality.
    • Updates information to be consistent with the U.S. EPA National Ambient Air Quality StandardsThe level of pollutants prescribed by regulations that are not to be exceeded during a given time in a defined area. (EPA).
    • Includes a new  appendix that summarizes the documentation requirements in the body of the standard, thus providing a single point of reference for users.
    • Requires proper design for buildings that contain both ETSEnvironmental tobacco smoke (ETS), or secondhand smoke, consists of airborne particles emitted from the burning end of cigarettes, pipes, and cigars, and is exhaled by smokers. These particles contain about 4,000 compounds, up to 50 of which are known to cause cancer. and ETS-free areas, by requiring classification of areas based on expected presence of ETS, pressurization of ETS-free areas, separation of ETS and ETS-free areas, and cautionary signage for ETS-areas.
  • FAQs for IEQp1

    A building has fan-assisted ventilation and no mechanical cooling system. Does this qualify as natural ventilation?

    If the building relies on the fans for daily ventilation, it is considered a mechanically ventilated building.

    Is outdoor air quality testing required in a space using natural ventilation?

    Testing in naturally ventilated spaces is not required per 62.1-2007 Sections 4-7 if the outdoor air quality adequately meets 62.1-2007, Table 4-1.

    For a space designed to be naturally ventilated, can operable windows or vents be used to satisfy the 62.1-2007 requirements?

    Both operable windows and vents can be used, but only the operable area within those elements can be counted towards the minimum percentage (4%) of net occupiable area.

    What options are available to projects outside the US to meet this prerequisite?

    Local codes may be used to meet the prerequisite if the project team can show equivalency with Sections 7 through 7 of ASHRAE Standard 62.1-2007. Projects outside the US can now also choose to comply with the minimum requirements of Annex B of CEN Standard EN 15251:2007 Ventilation for Nonresidential buildings.

    Can LEED 2009 projects elect to follow ASHRAE 62.1-2010 for this prerequisite?

    Teams may choose to substitute ASHRAE 62.1-2010, Sections 6.4.1-6.4.2, for ASHRAE 62.1-2007, Section 5.1.1, to document compliance with IEQp1 for naturally ventilated buildings. ASHRAE 62.1-2010 adds geometric requirements that extend the allowed naturally ventilated floor area based on ceiling height and opening configuration.

    Which units should be included in the calculations for this prerequisite?

    For CI projects, calculations must be done at the system level for any AHU1.Air-handling units (AHUs) are mechanical indirect heating, ventilating, or air-conditioning systems in which the air is treated or handled by equipment located outside the rooms served, usually at a central location, and conveyed to and from the rooms by a fan and a system of distributing ducts. (NEEB, 1997 edition) 2.A type of heating and/or cooling distribution equipment that channels warm or cool air to different parts of a building. This process of channeling the conditioned air often involves drawing air over heating or cooling coils and forcing it from a central location through ducts or air-handling units. Air-handling units are hidden in the walls or ceilings, where they use steam or hot water to heat, or chilled water to cool the air inside the ductwork. providing outside air to the tenant spaceTenant space is the area within the LEED project boundary. For more information on what can and must be in the LEED project boundary see the Minimum Program Requirements (MPRs) and LEED 2009 MPR Supplemental Guidance. Note: tenant space is the same as project space..

Legend

  • Best Practices
  • Gotcha
  • Action Steps
  • Cost Tip

Pre-Design

Expand All

  • Determine likely ventilation strategies during preliminary programming: natural, mechanical, or mixed-mode ventilation. This prerequisite is attainable with any of these strategies.


  • This prerequisite is paired with IEQc2: Increased Ventilation. If ventilation rates are targeted above the 30% ASHRAE requirement, projects can gain both the prerequisite and a point for EQc2. Projects pursuing IEQc2 may follow the compliance path for natural ventilation found in Chapter 2 of The CIBSE Applications Manual 10 (AM10) for both the prerequisite and for the credit.


  • Many of the strategies that contribute to meeting this prerequisite also support earning other indoor environmental quality credits and should be explored as integrated solutions. See LEEDuser's guidance on the rest of the IEQ section for ideas.


  • Natural ventilation strategies can reduce costs. Natural ventilation in particular can reduce the need for mechanical equipment as well as operational costs. Displacement ventilation, in which air is delivered at or near floor level at a low velocity, can also reduce ducting and improve equipment efficiency. In choosing a system, analyze life cycle cost tradeoffs.


  • Check local building codes to determine requirements. The project must either meet ASHRAE 62.1-2007, or local codes if they are more stringent. Since ASHRAE 62.1-2007 is often more stringent than local codes, be sure to review and be familiar with its requirements.


  • This prerequisite is not likely to require added costs.


  • Case 1: Mechanically Ventilated Spaces


  • Review the Ventilation Rate Procedure methodology in ASHRAE 62.1-2007 Section 6.2 and the associated Table 6-1.


  • ASHRAE 62.1 recognizes two procedures to prove IAQ compliance: the IAQ Procedure methodology and the Ventilation Rate Procedure. The Ventilation Rate Procedure is easier to apply and is the prescribed path for this LEED prerequisite. Documentation using the IAQ Procedure requires the quantification of contaminant source emissions rates and their reduction, and has historically not been accepted for this prerequisite because it is performance-based and difficult to compare across projects.


  • If you are pursuing IEQc5: Indoor Chemical and Pollutant Source Control, you must incorporate MERV 13 filters into your filtration system. These relatively tight filters may affect the fan power and fan sizes necessary to provide the required quantities of air. Involve the engineer early if pursuing IEQc5. 


  • Demand-controlled ventilation can greatly reduce energy use while providing large amounts of fresh air to occupants.


  • Case 2: Naturally Ventilated Spaces


  • Determine whether natural ventilation is feasible based on the project type, use, and climate.  Study the natural conditions of the site, such as prevailing wind direction, and orient the building to maximize airflow.


  • Review the prescriptive requirements for natural ventilation in ASHRAE 62.1-2007 Paragraph 5.1 (with errata but without addenda).


  • An integrated design meeting will help determine whether natural ventilation is a high priority and should be a primary driver of the design process.


  • Airflow modeling early in the design process can help teams by evaluating which space planning and envelope design strategies will create effective natural ventilation. An airflow modeling professional may add some upfront costs, while likely improving system efficiency.

 Airflow modeling can also help to determine compliance for an engineered natural ventilation system outside the prescriptive measures of ASHRAE 62.1-2007.


  • Consider the cost implications of natural ventilation. Passive strategies may reduce or eliminate the need for fans and HVAC equipment, but they may also require high quantities of operable windows and a floor plan that is conducive to passive ventilation.  Natural ventilation often requires the cooperation of occupants, to open and close windows when appropriate, for example, be sure that your project is likely to succeed in this respect.

Schematic Design

Expand All

  • Determine the required ventilation rates for indoor spaces based on occupancy and space types.  ASHRAE 62.1-2007 tables 6-1 and 6-4 list minimum requirements for particular spaces.


  • Separately evaluate each space to determine air requirements and what type of ventilation will be best.  Metabolic rate of the space activities and the occupant density are factors that determine the amount of fresh air needed in a space.  For example, exercise rooms and conference rooms require more fresh air than offices.


  • An integrated design approach among the mechanical engineer, architects, owners and occupants will facilitate design decisions that impact the HVAC design. For example, space planning decisions will impact the architectural programming of the space as well as access to natural ventilation.


  • Increasing a project’s ventilation rate brings long-term cost benefits. Good indoor air quality can lower operational costs by increasing occupants’ health and productivity as well as the value and marketability of the building.


  • For mixed-mode and naturally ventilated spaces, the mechanical engineer should calculate the outdoor airflow rate and communicate the area requirements for operable wall or roof openings to the architect.


  • The mechanical engineer begins preliminary ventilation rate calculations during project programming in order to set ventilation quality goals for particular spaces and occupancies. The area of a given multi‐zone system should be broken down by ventilation zones, and all zones within that system must meet the minimum breathing zone ventilation air requirements as per ASHRAE 62.1‐2004. For a typical office space, the mechanical design consists of multiple ventilation zones for which compliance would need to be shown on an individual basis.


  • Case 1 Mechanically Ventilated Spaces


  • For mixed-mode ventilation, zone the plan into areas—mechanically ventilated and naturally ventilated—and follow separate compliance calculations for each area.


  • Case 2 Naturally Ventilated Spaces


  • Determine the applicable floor area for operable wall or roof openings according to ASHRAE 62.1-2007 section 5.1.


  • Consider using Computational Fluid Dynamics (CFD) modeling to determine proper opening sizes and ensure proper airflow. Some energy modeling programs also have CFD analysis capabilities.


  • Expect upfront modeling fees for Computational Fluid Dynamics (CFD), but also consider the benefits of CFD modeling: a better-designed natural ventilation system that can bring short-term payback from reduced mechanical systems, and long-term operational savings.


  • At the first integrated design meeting during schematic design, develop a detailed natural ventilation strategy involving goals for windows, building orientation, space planning, use of atriums, and other access to natural ventilation. Natural ventilation systems may require a more robust and intense integrated design process, of several focused workshops analyzing several alternatives. Computer modeling may be necessary to test various design alternatives to determine which is most effective and efficient.


  • Hotel and multifamily projects may have difficulty achieving this prerequisite if they are naturally ventilated and have interior spaces that are further than 25 feet from an operable wall or roof opening. These projects might consider increased window areas, shallower floor plates, or using mixed-mode ventilation so that mechanically supplied outdoor air can support areas outside the 25-foot natural ventilation boundary.

Design Development

Expand All

  • The mechanical engineer continues to run ventilation rate calculations during the mechanical design process to inform design development and confirm compliance with this prerequisite. The ventilation rate procedure is explained in section 6 of ASHRAE 62.1-2007. See the attached 62MZ calculator.


  • Continuing to use an integrated design approach among the mechanical engineer, architects, owners and end users will facilitate design decisions that impact the mechanical design. For example, space planning decisions will impact the architectural programming of the space as well as access to natural ventilation.


  • Strategically locate air intakes for mechanical or natural ventilation systems to avoid taking in contaminants and odors like vehicle exhaust from parking lots or fumes from garbage storage areas.


  • Incorporating operable windows into the design for natural and mixed-mode ventilation can help with an additional LEED point for EAc6.1: Controllability of Systems—Thermal Comfort.


  • Case 1: Mechanically Ventilated Spaces


  • Continue running ventilation rate calculations during the mechanical design process to confirm compliance with this credit and to inform the design. The ventilation rate procedure is explained in section 6 of ASHRAE 62.1-2007. See the 62MZ calculator.


  • Implement energy recovery systems, economizers, low-pressure-drop design, and efficient fans as appropriate to support ventilation rates meeting or exceeding the referenced ASHRAE standard without compromising energy performance.


  • Avoid oversizing mechanical equipment. Oversized equipment will often increase operating costs and reduce operational efficiency. The correct equipment size will depend on a number of factors, including local climate, total building area, insulation levels, air filtration medium, number of windows and doors, and occupant comfort preferences.


  • Spaces served by the same VAV (variable air volume) controller can be grouped together in the 62MZ calculator, but grouped spaces should have similar exterior exposure. For example, you can group two perimeter spaces that share a VAV controller, but would want to separate a non-perimeter space even if it shares the same VAV controller.


  • Laboratory facilities generally require very high ventilation rates. Consider installing separate mechanical systems for lab spaces to maximize return-air mixing. Other strategies may include using a heat exchanger to capture energy from laboratory exhaust, using low-flow or variable-flow fume hoods, minimizing ventilation rates during unoccupied times, or using a dedicated outdoor air system.


  • Integrating building automation systems can control mechanical systems efficiently and maintain desired ventilation rates while minimizing unscheduled maintenance.


  • The Ventilation Rate Procedure calculation includes occupancy counts based on space types.


  • Case 2: Naturally Ventilated Spaces


  • Continue to run calculations and develop flow diagrams to inform the design process and confirm compliance. If you are using a natural ventilation modeler for the project, use the model as a tool to inform design development.


  • The calculation for operable openings will only apply to the floor area adjacent to the window—25 feet to either side and in front of the opening.


  • The surface area of window openings must, for compliance with ASHRAE 62.1, be equal to or greater than 4% of the occupied floor area that the design considers naturally ventilated. Multiple windows in aggregate can provide the operable area needed to meet the requirements.


  • In naturally ventilated multifamily buildings, air infiltration from a pressurized hallway or corridor can contribute to the Ventilation Rate Procedure calculation for areas that do not meet the requirements of ASHRAE 62.1, as long as the corridor is pressurized with outdoor air.

Construction Documents

Expand All

  • For mechanically ventilated spaces, run ventilation calculations to verify that the final design meets the minimum outside air rates equal to or exceeding the ASHRAE 62.1-2007 minimum.


  • For naturally ventilated spaces, confirm compliance with the requirements of ASHRAE 62.1-2007 section 5.1.


  • If natural ventilation strategies are integrated into the design, ensure that key elements of the natural ventilation system, such as operable windows, window actuators, controls, operable atrium elements, and solar chimneys, are not compromised during value engineering. Educate decision-makers about the natural ventilation design and the importance of maintaining all the key components. If these elements are altered in a way that compromises natural ventilation rates, the mechanical system may no longer be sized appropriately.


  • Fill out the LEED credit form and upload all supporting documents to LEED Online.


  • Use this checklist for naturally ventilated spaces prior to construction to review plans for prerequisite compliance:

    • Are all floor areas within 25 feet of an operable window?
    • Do all floor areas within 25 feet of an operable window appear have 4 ft2 of opening per 100 ft2 of floor area?
    • Is fresh outdoor air mechanically supplied and exhausted for all regularly occupied spaces beyond 25 feet of an operable window?
    • Do any corridors or entryways fall outside of these naturally or mechanically ventilated areas? If so, develop the design further to supply sufficient ventilation.

  • Use this checklist for mechanical systems prior to construction to check prerequisite compliance:

    • Using the mechanical equipment schedule, confirm that outside air is being supplied to mechanically ventilated spaces.
    • Do you have calculations showing the outside air required by ASHRAE 62.1-2007 for mechanically ventilated spaces separate from naturally ventilated spaces?
    • Do outside air rates meet or exceed the calculated ASHRAE minimums?
    • Are all regularly occupied spaces listed in the ASHRAE calculations?
    • What is the desired MERV filtration? If using a high level of ventilation to meet EQc5, has the mechanical system been sized accordingly?

Construction

Expand All

  • Coordinate the installation of ventilation systems with the project’s commissioning process.


  • Use commissioning to confirm that installed systems are providing the outside air rates specified in the design. 

Operations & Maintenance

Expand All

  • Monitor outdoor air delivery periodically to confirm that minimum ventilation rates are being maintained. Implement a maintenance program to ensure that mechanical system components are functioning properly.


  • Test all dedicated building exhaust systems including chemical areas, bathroom, shower, kitchen, and parking exhaust systems to confirm proper fan speed, voltage, control sequences, and set points as applicable. Provide operations and maintenance personnel with manuals and educate them about any atypical maintenance requirements.


  • Getting feedback on ventilation performance from occupants through surveys can help to identify potential problems that may become expensive if they go unnoticed.


  • A documented ventilation performance plan can help ensure that systems reach the expected ventilation thresholds.


  • In projects with operable windows, occupants may not know when conditions are best for opening the windows. Implement a system so that occupants are informed of when to open and close the windows to achieve designed performance and optimal comfort.


  • Maintain a building operating plan (BOP) that establishes operating schedules and set points and regularly review these parameters against actual building needs. When developing these parameters, consider both time-of-day and time-of-year variations in optimal temperature requirements and be careful to avoid over-conditioning the building spaces with more ventilation, heating or cooling than is necessary.


  • Adjust reset and setback temperature settings and calibrate controls and sensors. A Building Automation System (BAS) will allow building managers to adjust, monitor and control temperature set points and air volumes throughout the building from a central location. Direct digital controls (DDC) utilized by the BAS will function more efficiently than older pneumatic controls and help to avoid unnecessary use of HVAC equipment during non-business hours and holidays.


  • Develop and implement a comprehensive Indoor Air Quality Management Plan using the EPA’s “Indoor Air Quality Building Education and Assessment Model” (I-BEAM).

    • Assign an IAQ manager. This individual should be responsible for developing and managing the IAQ plan including managing contracts for IAQ related services and communication with building occupants about IAQ related issues.
    • Conduct an IAQ audit of the building and grounds to determine IAQ status. Use forms provided by I-BEAM to record the basic conditions of the building’s occupied spaces, mechanical systems, and building exterior.

  • Following the initial audit, the IAQ manager must make periodic inspections to uncover new IAQ issues and monitor the status of previous issues. The I-BEAM tool supplies inspection forms that can be tailored to the project building to facilitate this process.


  • Establish protocols to manage all significant pollutant sources referenced in I-BEAM that are applicable to the project building.


  • Ensure that procedures are in place for receiving and responding to IAQ complaints from building occupants. The I-BEAM tool provides sample forms and logs for fielding and recording occupant complaints as well as information about key principles for developing effective communication with building occupants regarding IAQ issues. Strategies for investigating and resolving the issues that trigger occupant complaints are covered by a variety of I-BEAM guidelines.

  • USGBC

    Excerpted from LEED 2009 for New Construction and Major Renovations

    IEQ Prerequisite 1: Minimum IAQ Performance

    Required

    Intent

    To establish minimum indoor air quality (IAQIndoor air quality: The quality and attributes of indoor air affecting the health and comfort building occupants. IAQ encompasses available fresh air, contaminant levels, acoustics and noise levels, lighting quality, and other factors.) performance to enhance indoor air quality in buildings, thus contributing to the comfort and well-being of the occupants.

    Requirements

    CASE 1. Mechanically Ventilated Spaces


    Mechanical ventilation systems must be designed using the ventilation rate procedure as defined by ASHRAE 62.1-2007, or the applicable local code, whichever is more stringent.

    OPTION 1. ASHRAE Standard 62.1-2007 or Non-U.S. Equivalent

    Meet the minimum requirements of Sections 4 through 7 of ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air Quality (with errata but without addenda). Projects outside the U.S. may use a local equivalent to Sections 4 through 7 of ASHRAE Standard 62.1-2007.

    OR

    OPTION 2. CEN Standards EN 15251: 2007 and EN 13779: 2007

    Projects outside the U.S. may earn this prerequisite by meeting the minimum requirements of Annex B of Comité Européen de Normalisation (CEN) Standard EN 15251: 2007, Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics; and the requirements of CEN Standard EN 13779: 2007, Ventilation for nonresidential buildings, Performance requirements for ventilation and room conditioning systems, excluding Section 7.3 – Thermal environment, 7.6 – Acoustic Environment, A.16, and A.17.


    CASE 2. Naturally Ventilated Spaces


    Naturally ventilated buildings must comply with ASHRAE Standard 62.1-2007, Paragraph 5.1 (with errata but without addenda). Project teams wishing to use ASHRAE approved addenda for the purposes of this prerequisite may do so at their discretion. Addenda must be applied consistently across all LEED credits.

    Potential Technologies & Strategies

    Design ventilation systems to meet or exceed the minimum outdoor air ventilation rates as described in the ASHRAE standard. Balance the impacts of ventilation rates on energy use and indoor air quality to optimize for energy efficiency and occupant comfort. Use the ASHRAE Standard 62.1-2007 Users Manual (with errata but without addenda1) for detailed guidance on meeting the referenced requirements.

    FOOTNOTES

    1 Project teams wishing to use ASHRAE approved addenda for the purposes of this prerequisite may do so at their discretion. Addenda must be applied consistently across all LEED credits.

Technical Guides

IEQ Space Matrix - 2nd Edition

This updated version of the spreadsheet categories dozens of specific space types according to how they should be applied under various IEQ credits. This document is essential if you have questions about how various unique space types should be treated. Up to date, 2nd Edition.


ASHRAE 62.1-2007: Outdoor Airflow Monitoring Devices.

ASHRAE 62.1-2007 should be referenced when designing outdoor airflow monitoring devices.


IEQ Space Matrix - 1st Ed.

This spreadsheet categories dozens of specific space types according to how they should be applied under various IEQ credits. This document is essential if you have questions about how various unique space types should be treated.  This is the 1st edition.

Publications

Greening the Building and the Bottom Line

This Rocky Mountain Institute publication is a case study of the connection between worker productivity and indoor air quality.


Procedural Standards for Testing, Adjusting and Balancing of Environmental Systems, 7th ed. (National Environmental Balancing Bureau, 2005)

This manual provides information on the technology and techniques for the design, operation, servicing, and balancing of environmental systems.

Organizations

American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE)

ASHRAE publishes widely used standards and publishes the ASHRAE Journal.


Labs for the 21st Century (Labs 21)

Labs21 is a voluntary partnership program dedicated to improving the environmental performance of U.S. laboratories.


Indoor Air Quality Association

IAQA is a nonprofit organization dedicated to promoting the exchange of indoor environmental information through education and research.


Mechanical Service Contractors of America

MSCA is a national trade association that provides educational resources and training programs on sustainable service and maintenance practices for HVACR contractors.


CIBSE Applications Manual 10-2005

Located in London, this organization publishes a series of guides on ventilation, including natural ventilation.

Web Tools

Energy Cost and IAQ Performance

This website contains reports from an extensive EPA modeling study that assessed the compatibilities and trade-offs between energy, indoor air quality, and thermal comfort objectives for HVAC systems and formulated strategies to achieve superior performance.

Software Tools

62MZ Calculator: Ventilation Rate Procedure

This is a Microsoft Excel calculator that accompanies the ASHRAE 62.1 reference standard. The calculator allows users to plug in variables for specific project types and run the Ventilation Rate Procedure.


CONTAM 3.0 Multizone Modeling Software

Public domain software from NIST (National Institute of Standards and Technology) that has natural ventilation sizing tools, and flow models to analytically predict room-by-room airflows.


Loop DA Multizone Modeling Software

Public domain software from NIST (National Institute of Standards and
Technology) that has natural ventilation sizing tools, and flow models
to analytically predict room-by-room airflows.


ASHRAE 62.1 iPhone App

ASHRAE released an app for iPhone, iPod touch, and iPad that allows you to perform comprehensive minimum ventilation calculations for a wide variety of commercial buildings based upon Standard 62.1, using either I-P or SI units. This app is based upon the 62MZCalc.xls. Now, you can make calculations at a meeting and know if your project meets IEQp1 or IEQc2.

Ventilation Rate Table

This example ventilation rate table from 23 High Line provides guidance when developing prerequisite compliance documents for your project.

Air Riser Diagram

This example air riser diagram from 23 High Line shows the mechanical ventilation supply for the building. It is the ducted diagram showing how air will be supplied to building occupants. Use this as an example for how to document ventilation effectiveness compliance.

Mechanical Systems Schedule

Use this example mechanical schedule created from 23 High Line for guidance when developing ventilation effectiveness compliance documents for your project.

LEED Online Forms: NC-2009 IEQ

Sample LEED Online forms for all rating systems and versions are available on the USGBC website.

Design Submittal

PencilDocumentation for this credit can be part of a Design Phase submittal.

1030 Comments

0
0
Heather Holdridge Sustainability Coordinator Lake/Flato Architects
Apr 28 2016
LEEDuser Member
1744 Thumbs Up

State of Illinois Smoking Law

There is a Smoke Free Illinois Act that bans smoking inside buildings or within 15' of a window, door, or ventilation system. We are working on a school project that falls under this law. Is there a way to avoid posting signage since we comply with the law? The owner would really like to eliminate signage if possible.

1
3
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Apr 28 2016 LEEDuser Expert 3629 Thumbs Up

I believe that you should be asking thie in IEQp2. The LEED requirement is 25', so I do not think that the state law would qualify for the prerequisite requirements.

2
3
0
David Hubka Director - Operations, Transwestern Sustainability Services Apr 28 2016 LEEDuser Expert 2412 Thumbs Up

I concur with Andrew, EQp2 question and 25ft is required. (See LI #1967)

As for the bare minimum for the signage, i have previously asked this question of the GBCIThe Green Building Certification Institute (GBCI) manages Leadership in Energy and Environmental Design (LEED) building certification and professional accreditation processes. It was established in 2008 with support from the U.S. Green Building Council (USGBC). and here is there response:

"There is no firm answer to this as it depends on the overall context of the exterior smoking policy communication method on the site, but the exact language on the signage, its size, and location(s) are up to the project team (with one caveat for signage locations for v4 projects - see the end of my message below). That being said, the signage throughout the site must somehow effectively communicate the exterior smoking policy to all building occupants and visitors and it must be reasonably visible. For example, a single sign with a crossed-out cigarette and no text at one entrance may not be sufficient and could be misinterpreted as the interior smoking policy, but if such a sign is installed at multiple locations around the building exterior to communicate the extent of the non-smoking area or if there is additional signage to indicate the location of the designated smoking area, this would better communicate the exterior smoking policy. Another example of effective signage language is "Smoking is allowed in designated smoking areas only." Also, reviewers will take into consideration other methods of communicating the exterior smoking policy in conjunction with the signage, such as policing of non-smoking areas by security staff or regular communications with occupants about the smoking policy. If the client wants to do the bare minimum, one approach could be to place a sign only at the designated smoking area saying something such as "Smoking permitted in this area only" and supplementing that with regular communications with the occupants about the site smoking policy.

Also, I just wanted to note that in LEED v4, the prerequisite requirements require signage within 10 feet of all entrances in case this happens to be a v4 project."

hope this helps!

3
3
0
Heather Holdridge Sustainability Coordinator, Lake/Flato Architects Apr 28 2016 LEEDuser Member 1744 Thumbs Up

Thank you both. My mistake -- I absolutely posted this in the wrong forum. Only problem is I can't figure out how to delete it now?

Post a Reply
0
0
Diego Pietzsch Mechanical Engineer
Apr 15 2016
Guest
65 Thumbs Up

Exhaust Rates for Enclosed Parking Garages

How project teams applying combined a ventilation strategy(Mechanical + Natural) should proceed in order to meet the minimum requirements established in ASHRAE 62.1-2007, Table 6-4, for parking garages. ASHRAE 62.1 eliminates exhaustion necessity in cases where at least two sides of the parking garage are at least 50% open to the outside. However, for cases where openings do not meet these requirements ( 30% openings for example), is it possible to reduce the required mechanical ventilation flow rate based on designed opening areas?

Post a Reply
0
0
Laura Charlier LEED Services Director Group14 Engineering
Apr 14 2016
LEEDuser Member
565 Thumbs Up

Exhaust-only ventilation?

Does anyone know if there is a LEED interpretationLEED Interpretations are official answers to technical inquiries about implementing LEED on a project. They help people understand how their projects can meet LEED requirements and provide clarity on existing options. LEED Interpretations are to be used by any project certifying under an applicable rating system. All project teams are required to adhere to all LEED Interpretations posted before their registration date. This also applies to other addenda. Adherence to rulings posted after a project registers is optional, but strongly encouraged. LEED Interpretations are published in a searchable database at usgbc.org. that allows exhaust-only ventilation in multifamily units under LEED-NC?
Thanks!

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Apr 14 2016 LEEDuser Expert 3629 Thumbs Up

You can use exhaust only as mechanical ventilation. Look at the ventilation effectiveness schedule in Table 6-2 to determine how to apply this to your project.

Post a Reply
0
0
Thu Nguyen LEED AP, Green Building Specialist GreenViet Consultancy Co., Ltd.
Mar 29 2016
Guest

Combine Natural ventilation & trickle ventilation for Apartment

Project Location: Vietnam

Dear all experts!
I have a high-rise residential building which aim to comply with IEQ pre.1 by combining 2 ways.
1. Living room and dinning room will comply with natural ventilation: 4% operable window and within 25 feet.
2. Bedroom is completely closed, and not connect with any operable window, therefore we try to comply with IEQ pre.1 by trickle ventilation. It means that, we have Toilet exhaust fan (continously operated) and we want to prove that the bedroom will provide with fresh air through this exhaust fan (of course, we will calculate with Vbz=0.8).
=> The question is: is that complied with IEQ pre. 1 for all living room, dining room, and bedroom by the above methods?
=> and the next question is: that bedroom near the corridor (which is permanent open and connect with outdoor), so is this ok for providing fresh air through trickle ventilation by exhaust fan at toilet (as above mention) and fresh air taking from corridor which permanent open like that?

Looking forward to receiving your feedback. Thanks so much.

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Mar 31 2016 LEEDuser Expert 3629 Thumbs Up

If the make-up air being drawn in by the exhaust fan is outside air, then you can use it as mechanical ventilation by exhaust fan. The effectiveness will be 0.5 or 0.8 based on where your exhaust fan is in relation to the ventilated space. See the table in chapter 6.

Post a Reply
0
0
Hongyun Zhou
Mar 29 2016
Guest
17 Thumbs Up

single zone or multi-zone calculation?

Project Location: China

I have a project, which have two types of system:
1. OA system offering the fresh air to each room, and each room has an individual fan coil unit .
2. OA system offering the fresh air through chilled beams to each room.
Should I verify the ventilation by 62MZ calculator or single zone as IEQp1-A2 table?
I appreciate any comments for this.

1
2
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Mar 31 2016 LEEDuser Expert 3629 Thumbs Up

If the OA system is variable volume, then you should you the MZcalc. If not, you can treat each one as a separate zone receiving a set amount of OA.

2
2
0
Hongyun Zhou Mar 31 2016 Guest 17 Thumbs Up

It is VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. for OA system. In MZcalc, should I include fan coil supply air (or chilled beam induced air) and outdoor air into the design supply air? It says primary plus local recirculated, just want to make sure. Thank you!

Post a Reply
0
0
Kristopher Lashley INVIRO Engineered Systems Ltd.
Mar 16 2016
Guest
88 Thumbs Up

ASHRAE 62.1

Project Location: Canada

We have an electrical room on site that is not attached to the main building and will hold the electrical equipment for a diesel fueling station. Someone will be in the room twice a day just to turn the system on and then turn it off (less than a minute each time) each day. Am i right in assuming that this room can be considered not regularly occupied and thus can be excluded from having to abide by ASHRAE 62.1?
Client does not want to put any mechanical cooling or heating equipment.

1
1
0
David Hubka Director - Operations, Transwestern Sustainability Services Mar 16 2016 LEEDuser Expert 2412 Thumbs Up

The space you describe seems to be intended primarily for purposes other than human functions AND it is only occupied for very short periods of time.

The overview of the EQ credit category within the v4 Reference Guide lists "electrical rooms" as being unoccupied.

I would define this room as "unoccupied" hence not requiring ventilation.

Be sure to include a narrative within EQp1 explaining the use of the room and why it is considered "unoccupied".

Post a Reply
0
0
SAMY Chamy Enginneer T&T Green
Mar 12 2016
Guest
206 Thumbs Up

Fresh air supply using Cooling pad in Production area

Project Location: Pakistan

Dear all

Our project is single storied sewing factory in production area we have large size Exhaust fans in one side and opposite side of exhaust fan have cooling pad

Now the issue is we can't provide any fresh air fans to production area but fresh air is mandatory for IEQp1 credit

But fresh air is continuously coming to room via cooling pads due to continuous exhaust in opposite side

as per rule the amount of exhaust we take from room is automatically comes due to pressure variance in space

so can we assume the exhaust air quantity is equal to fresh outdoor air quantity enter from other openings and cooling pads and count the same in VRP calculation for production area where no fresh air supplied mechanically but have the cooling pad with exhaust fan in opposite side

is it acceptable manner if it is not accepted means why?

kindly assist us to solve this issue (is these space need mechanical fans to supply fresh air )

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Mar 14 2016 LEEDuser Expert 3629 Thumbs Up

If you are drawing fresh air in from a known intake using exhaust fans, then you are mechanically ventilating the space. You need to decide which of the following you fall into:

Makeup supply drawn in near to the exhaust and/or return location. (Ez value of 0.5)

Makeup supply drawn in on the opposite side of the room from the exhaust and/or return. (Ez value of 0.8)

Also, I assume that when you say cooling pad, you are referring to evaporative cooling pads. If that is the case, keep the following requirement in mind:

5.9 Particulate Matter Removal. Particulate matter filters or air cleaners having a minimum efficiency reporting value (MERVMinimum Efficiency Reporting Value (MERV) rating is an American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) measurement scale which rates the effectiveness of air filters. ) of not less than 6 when rated in accordance with ANSI/ASHRAE Standard 52.2 shall be provided upstream of all cooling coils or other devices with wetted surfaces through which air is supplied to an occupiable space.

Post a Reply
0
0
Alejandro Macias
Feb 24 2016
LEEDuser Member
16 Thumbs Up

Naturally Ventilated

Project Location: Mexico

Hi! I'm working on a one-story dormitory project. The different spaces are naturally ventilated and are in compliance with ASHRAE 62.1 "All must be naturally ventilated spaces within 25 feet of ( and permanently open to) operable wall or roof openings to the outdoors ; Also the operable area must be at Least 4% of the space 's net floor area occupiable " .

How can I document the credit? On the credit format on LEED Online states: Provide documentation demonstrating the minimum outdoor air opening and space configurations meet or Exceed the the minimum values from the natural ventilation requirements outlined in ASHRAE 62.1-2007 , Section 5.1.1 .

If I only send a floor plan of the different spaces ,sections and dimensions of the operable windows, and also a narrative, would it be ok?

1
2
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Feb 24 2016 Guest 1196 Thumbs Up

You will also be required a spreadsheet showing: operable window area, space floor area and access within 25ft for each space.

2
2
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Feb 25 2016 LEEDuser Expert 3629 Thumbs Up

I have uploaded floor plans showing a scaled 25' line, with each operable opening tagged for area as well as a tag on each space showing floor area and required openings.

Post a Reply
0
0
James Lee
Feb 12 2016
Guest
5 Thumbs Up

Engineered Natural Ventilation with Ceiling Fan

Hi,
I have a lobby which has one side is open to outside. But the length of lobby is almost 40ft instead of 25ft. And their are 8 ceiling fans evenly. Could be this the case for engineered natural ventilation in IEQp1?

1
3
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Feb 16 2016 LEEDuser Expert 3629 Thumbs Up

If you can document that the air circulation induces OA all the way to the back, then you can submit it. Otherwise, install a small inline fan in the ceiling to meet the requirements of the remaining 15 feet and submit under mixed mode ventilation.

2
3
0
Harry Flamm Project Architect and Sustainability Coordinator, Elkus Manfredi Architects Apr 15 2016 LEEDuser Member 37 Thumbs Up

Andrew,
Regarding your point about installing an "inline fan" to mitigate the 25' distance requirement, is this technique something that LEED has previously accepted? I have an occupied space that is 28' away and see this as a simple solution -- both for my current project, and for future designs.

3
3
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Apr 15 2016 LEEDuser Expert 3629 Thumbs Up

I have not done this exactly, but I have used mixed mode ventilation successfully.

Post a Reply
0
0
Geraldo Pithon
Jan 19 2016
Guest
3 Thumbs Up

VRP Compliance Calculator or 62MZCalc for projects outside U.S.?

Project Location: Brazil

I am submitting for review a project outside the US, in Brazil.
The legislation of Brazil is very similar to that specified by ASHRAE 62.1. However, at the LEED Online I am instructed to prepare a new worksheet describing the service to credit according to local law, and may not use the VRP Compliance Calculator option or 62MZCalc spreadsheet. Would not it be more appropriate for the analysis team I ever use one of these presentation tools available? What is recommended in this case? Okay to me to continue the service through the VRP Compliance Calculator?

If I can use the VRP Compliance Calculator, should I mark "Is the project located outside of the U.S. and pursuing Option 2 or a local equivalent in Option 1?"

1
1
0
David Hubka Director - Operations, Transwestern Sustainability Services Feb 11 2016 LEEDuser Expert 2412 Thumbs Up

you are allowed to use the 62MZ calculator, i suggest you use this to document the minimum ventilation requirements are met.

Post a Reply
0
0
CATALINA CABALLERO SUSTAINABILITY COORDINATOR JALRW Eng. Group Inc.
Dec 29 2015
LEEDuser Member
4314 Thumbs Up

Existing building with new addition compliance

we have a new addition added to an existing facility. The consultant has decided to pursuit NC for this project, therefore the question comes if there is an existing area within the LEED boundary with existing AC units that wont be modified, do these units need to comply with the minimum OA required as well? Would a Test and Balance be necessary or only plans?

In the case that they take these existing areas out of the LEED boundary, only the new equipment will need to be Tested and Balanced, correct?

1
1
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Dec 29 2015 Guest 1196 Thumbs Up

i.First of all, there are two different concepts here: this prerequisite requires your project to have VENTILATION (natural, mechanical, engineered...) regardless of whether or not you have A/C.

ii.Every occupiable space within your LEED Project Boundary must be ventilated. I am pretty sure your reviewers will require you to demonstrate that.

iii.Regarding your cx1. Commissioning (Cx) is the process of verifying and documenting that a building and all of its systems and assemblies are planned, designed, installed, tested, operated, and maintained to meet the owner's project requirements. 2. The process of checking the performance of a building against the owner's goals during design, construction, and occupancy. At a minimum, mechanical and electrical equipment are tested, although much more extensive testing may also be included. question I would ask in the EAp1 forum.

Post a Reply
0
0
CATALINA CABALLERO SUSTAINABILITY COORDINATOR JALRW Eng. Group Inc.
Dec 29 2015
LEEDuser Member
4314 Thumbs Up

Existing building compliance

we have a new addition added to an existing facility. The consultant has decided to pursuit NC for this project, therefore the question comes if there is an existing area within the LEED boundary with existing AC units that wont be modified, do these units need to comply with the minimum OA required as well?

In the case that they take these existing areas out of the LEED boundary, only the new equipment will need to be Tested and Balanced, correct?

1
1
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Jan 18 2016 Guest 1196 Thumbs Up

Every interior space within your LEED Project Boundary must comply with the ventilation requirements.

Regarding the TaB question, I am not pretty sure but I would test the existing equipment to guarantee the outdoor air required by the VRP is provided by your system.

Post a Reply
0
0
Joe Sechler BNK
Dec 21 2015
LEEDuser Member
15 Thumbs Up

IEQP1 VRP Calculator saying I'm non-compliant

Project Location: United States

Figured out my question. Please delete

Post a Reply
0
0
Elodie DUMAS ALTO Ingénierie
Dec 21 2015
LEEDuser Member
816 Thumbs Up

Global Compliance Paths EN 15251

Project Location: France

Hi,
There's several quality level for interior air in EN 15251 : category I to III. The reference guide doesn't enjoin a specific category, as you can see in this extract :
"To determine the ventilation rate: Use Table B.1 in Annex B of CEN Standard EN 15251:2007 to find the appropriate percentage of dissatisfied building occupants and select Category I, II, or III based on the building design and applicable local codes."

We hesitate to select the lower category (III). Do you have any feedback about this ?
Thanks

1
1
0
Elodie DUMAS ALTO Ingénierie Jan 19 2016 LEEDuser Member 816 Thumbs Up

Any idea ?

Post a Reply
0
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor Revitaliza Consultores
Dec 16 2015
Guest
1196 Thumbs Up

VRP in the space matrix

Hallo,

What does VRP stand for in the column IEQp1 of the space matrix? I've looked it up in the notes and definitions tab but it does not appear.

I do not think it stands for Ventilation Rate Procedure because there are other methodologies appart from that one (CIBSE, natural ventilation...)

Thanks

1
1
0
Andrey Kuznetsov Green Building and Sustainability Consultant (LEED AP BD+C), Signy Group Feb 11 2016 Guest 157 Thumbs Up

Actually I supposed that it's per 62.1 - the ventilation rate procedure (VRP), the indoor air quality procedure (IAQP), and the natural ventilation procedure (NVP) - see ASHRAE Journal, June 2012, "Minimum Outdoor Airflow Using the IAQ Procedure".

Post a Reply
0
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor Revitaliza Consultores
Dec 04 2015
Guest
1196 Thumbs Up

Aeronautical Maintenance Workshop

Project Location: Colombia

This is a 70,000 sf Aeronautical Maintenance Workshop in Colombia with the following features:

-The space is 6 meters height.
-There are interior walls 5 meter height. Therefore, all the workshop is connected at the top of the space (1 meter)
-There are plenty of skylights that provide natural ventilation.
-Distances and size of openings meet sections 6.4.1 and 6.4.2 of the Standard ASHRAE 62.1 - 2010.

My question is: can I consider it correctly ventilated considering the openings are at the top of the space? We are going to use ASHRAE 62.1-2010 to demonstrate compliance for the whole workshop.

Thanks in advance.

1
1
0
Miriam Ramírez Baumgarten ARCH. LEED AP BD+C, ID+C, Revitaliza Consultores Dec 09 2015 Guest 43 Thumbs Up

Our question is if the interior 5m division walls would affect compliance with the prerequisite even though every "cubicle" or confined area is less than 25´(8m) away from the openings (vertically as well as horizontally) Any thoughts?

Thanks!

Miriam

Post a Reply
0
0
Ian McCall Environmental Engineer Le Sommer Environnement
Nov 17 2015
LEEDuser Member
1091 Thumbs Up

Global Compliance Paths ASHRAE 62.1 & EN 15251 and EN 13779

Project Location: France

Dear All,
The Global compliance Path guide book gives the option between ASHRAE 62.1-2007 or European standards EN 15251: 2007 and EN 13779: 2007.

Question :
Can we use the ventilation rates described in the ASHRAE 62.1 in regularly occupied spacesRegularly occupied spaces are areas where one or more individuals normally spend time (more than one hour per person per day on average) seated or standing as they work, study, or perform other focused activities inside a building. (Table 6.1, 6.2, 6.3) and the extraction rates (e.g. bathrooms) described in the CEN Standards EN 15251: 2007 and EN 13779: 2007 in in non-regularly occupied rooms (bathrooms) and achieve credit compliance?
If the French extraction rate is higher than the CEN / EN standard can it replace them?

Regards,
Ian

1
2
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Nov 17 2015 Guest 1196 Thumbs Up

Hallo Ian,
I do not think they will accept combining both methodologies unless you have a good reason for doing that, for instance, if you your project has a type of space that is not covered in one of the standards.
My advise is that you should use the ASHRAE calculator because the reviewers are usually not familiar with the CEN standard.

2
2
0
Devani PERERA Green Building Consultant, ELAN Nov 19 2015 Guest 394 Thumbs Up

Hello Ian,
I agree with Gustavo in that GBCIThe Green Building Certification Institute (GBCI) manages Leadership in Energy and Environmental Design (LEED) building certification and professional accreditation processes. It was established in 2008 with support from the U.S. Green Building Council (USGBC). would accept one path or the other and not a mix of it. I have submitted projects using the european standrads and it has been accepted without any problem.
The credi focus is the minimum rates so if your rates are higher on your design it isnt a problem.

Post a Reply
0
0
BAOQUY VU Principal R.W. Sullivan Engineering
Nov 06 2015
LEEDuser Member
39 Thumbs Up

Dorm Suite Ventilation

Project Location: United States

Our project is a large high rise dorm consisting of 4-person suites arranged typically as a 2BR and two 1BR's connected by a short inner hallway. The suite has a shared single bathroom accessible from the inner hallway. The inner hallway is very narrow and not occupiable for any duration. Our current scheme includes bathroom exhaust at 50-cfm continuous. Fresh air (neutral, i100% outside air) is delivered at 50-cfm to the hallway only (not each bedroom). The 50-cfm of OA meets the total suite ventilation requirement based on the 5-cfm/person + 0.06 cfm/sf requirement of ASHRAE 62.1-2007. The doors to each bedroom are undercut to allow the fresh air into the bedrooms.

Would the above scheme meet the requirements for mechanical ventilation per ASHRAE 62.1 for all spaces in the dorm suite?

1
2
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 06 2015 LEEDuser Expert 3629 Thumbs Up

No, that would not meet the requirements for mechanical ventilation. Mechanical ventilation should have some way of making the air come into the occupiable space.

2
2
0
Michelle Schwarting Robinson Re:Vision Architecture Nov 06 2015 LEEDuser Member 1237 Thumbs Up

Any chance the bedrooms have operable windows such that they meet the naturally ventilation requirements in terms of size, while the inner hallway is mechanically ventilated?

Post a Reply
0
0
ABDUL MUTHALIB MOHAMED INNOWELL ENGINEERING INTERNATIONAL PVT LTD
Nov 05 2015
LEEDuser Member
206 Thumbs Up

LEED Boundary

Project Location: India

I am working on LEED boundary for Factory building. The factory has two buildings with common car parking but we are applying LEED certification for only building - 1. Moreover, the car parking is near to building - 2 and a bit far away from building - 1. To achieve SSCR 7.2 Heat Island Reduction - Non roof, should i include parking area in LEED boundary?

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 06 2015 LEEDuser Expert 3629 Thumbs Up

You should ask this on the SSc7.2 forum. Tristan may be able to relocate it for you.

Post a Reply
0
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor Revitaliza Consultores
Nov 05 2015
Guest
1196 Thumbs Up

Hangar

Project Location: Colombia

My project is a 93,000 sf open-plan hangar. We are designing grills on walls that count for 4% of the floor area on 2 opposite facades to induce crossed-ventilation. Has anyone tried this strategy successfully in a project before?

My concern is that it is a big space and I am afraid the reviewer will ask for mechanical ventilation.

1
5
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 06 2015 LEEDuser Expert 3629 Thumbs Up

For natural ventilation, all occupiable space should be within 25' of an opening. If you do not meet this, then I would recommend adding exhaust fans to draw the ventilation air through the openings. You are allowed to control this based on CO2Carbon dioxide levels in the space.

2
5
0
Joseph Snider, AIA, LEED Fellow LEED Architect, SEQUIL Systems, Inc. Nov 06 2015 LEEDuser Member 376 Thumbs Up

As Andrew has noted, if any part of the space is further than 25' (8 m) away from those openings, the LEED reviewers will have a questions. We have used a similar strategy on large warehouse and manufacturing spaces in multiple LEED projects in Colombia and Venezula. In those cases though, there was a ridge vent in addition to the side wall louvered openings. This works as a stack event and air comes in the sides and is exhausted out the top. These can even be mechanical exhaust fans for not too much cost. When the fans were passive and not mechanical, we had to provide documentation of an engineered natural ventilation system showing how the air would move through the space and how that was more than enough air than required by ASRHAE.

3
5
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Nov 11 2015 Guest 1196 Thumbs Up

Thanks for your comments,

If I could use Section 6.4.1.2. of ASHRAE 62.-2010 I would be able to comply with natural ventilation. Can I use 2010 version instead of section 6.4 - ASHRAE 62.1-2007?

"6.4.1.2. Double side openings. For spaces with operable openings on two opposite sides of the space, the maximum distance from the operable openings is 5H, where H is the ceiling height"

4
5
0
Annalise Reichert Project Manager, stok Dec 15 2015 LEEDuser Member 296 Thumbs Up

I am working on a similar project, a 45,000 sf warehouse that is part of an Electrical Training Facility to train electrical contractors. The warehouse is primarily used for storage of educational materials, however a small section (about 2,000 sf) is used for an hour long training session 3 times per week. The facility manager considers this space unoccupied.

The warehouse perimeter wall has large roll-up doors that are manually opened in the morning, and manually closed at night. 3 large rooftop exhaust fans run continuously throughout the building's hours of operation.

To demonstrate that the unoccupied space meets ASHRAE 62.1 minimum ventilation rates, I am using the engineered natural ventilation approach to show the exhaust fans induce outside air from the doors throughout the warehouse space. My question is, do the roll-up doors need to have automatic controls, or is manually opening them acceptable? Additionally, do the rooftop exhaust fans need any sort of control or is it adequate that they turn on and off based on the facility operating schedule?

5
5
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Dec 21 2015 Guest 1196 Thumbs Up

1. According to LEED definition of regularly occupied space I think your warehouse cannot be considered as unoccupied.
2.In the VRP calculator you should use peak occupancy (but you should also consider the diversity factor)
3.Taking into account this is an engineered system, I think there is no specific requirement for the controllability of the roll-up doors. The outdoor air will enter the building through cracks and gaps in the envelope.
4.Based in my experience, I have never been asked to provide a minimum control or schedule, but it needs to be properly commissioned and meet the OPROwner's project requirements (OPR) is a written document that details the ideas, concepts, and criteria that are determined by the owner to be important to the success of the project..

Post a Reply
0
0
William Beechinor Engineer 1 AlfaTech
Nov 04 2015
Guest
13 Thumbs Up

Calculating Ds for LEED 62MZCalc

Project Location: United States

Hello,

I am currently trying to calculated Ds for the cooling condition for a project I an working on. Initially, I had the Ds value for each dual fan duct duct VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. unit set to 100%, but I was told by a colleague to change the value of Ds to be Ds = the minimum cooling flowrate of VAV/ the maximum cooling flowrate (Vdzd) of VAV.

For example a room in the building has a max supply cfm of 210 and a minimum supply cfm of 63. Should Ds then be: Ds=63/210 = 30%? Or should I leave Ds as 100%?

When I switched Ds from 100% to the equation I got the critical zone needs more ventialation error message.

1
1
0
Omar ElRawy Building Engineer, LEED AP BD+C, EA Building Consultants Nov 05 2015 Guest 1030 Thumbs Up

A direct answer to your question is: set Ds = minimum flow (30%).

I had a technical advice by the reviewer before to perform the calculations at the worst-case conditions, which was (in my case) to set most VAVs at Ds of 30%, and few VAVs that where designed with Ds of 40% (and I justified that by a narrative).
Also the worst-case case is generally during heating mode, for me, I like to check both; heating and cooling modes.

Post a Reply
0
0
William Beechinor Engineer 1 AlfaTech
Nov 03 2015
Guest
13 Thumbs Up

Calculating Ds for cooling condition

Project Location: United States

Hello,

I am trying to determine whether or not I am calculating Ds correctly. I previously had every zone set to 100% Ds, but I was told that Ds = the minimum supply air flowrate/maximum supply air flowrate. For example we are using dual fan dual duct VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. units and the maximum cooling cfm for a room is 210 cfm and the minimum is 63 cfm. Should Ds then be:
Ds = 63/210 = 30%? Or should I just have Ds set to 100%?

When I had all the values to Ds set to 100% the sheet worked, but when I changed it to the equation I got the error message Critical zone needs more ventilation. Any help would be greatly appreciated.

Thank you for your time,

William Beechinor

Post a Reply
0
0
Logan Dorrell Sr. Mechanical Engineer AECOM
Nov 03 2015
LEEDuser Member
41 Thumbs Up

How do we show for compliance for non-occupiable spaces?

Project Location: United States

I'm a little confused by what we are supposed to show to document compliance for non-occupiable spaces, like restrooms, that the space matrix call out as "N (VRP) / Y (other req's).

We have filled out the VRP calculator for all the spaces and have ventilation thru 100% DOAS serving all the spaces with radiant panels for heating. However, the LEED reviewer is questioning our square footage because the SF in the VRP Calculator is less than the total project square footage because the non-occupiable spaces are not included, since the space matrix said not to include them in the VRP Calcs.

We have enough exhaust in these spaces to comply with ASHRAE 62.1, but what does LEED want us to show for these spaces to prove compliance? Does checking the box that says, "The project meets Sections 4 through 7 of ASHRAE Standard 62.1-2007, Ventilation for Acceptable Indoor Air
Quality." qualify us as stating that we meet the ventilation rates for these spaces or do we need to prove it further to LEED?

Should we just submit a floor plan with the non-occupiable zones highlighted and with square footages shown or do we need to submit some kind of offline spreadsheet for these zones?

Thank you,

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 03 2015 LEEDuser Expert 3629 Thumbs Up

I always upload a sheet showing every space type that is not included in the VRP calc and the associated areas. Some are exhaust only, some are non-occupiable, and some are not applicable such as chase space and shafts. If you add it all up then you should be somewhere around 90% of the gross area from PIf3.

Post a Reply
0
0
SAMY Chamy Enginneer T&T Green
Nov 02 2015
Guest
206 Thumbs Up

Exhaust Requirement

Project Location: Afghanistan

I think this credit is for fresh air requirement.

Is there any requirement for Exhaust rates, are they need to documented for this credit

Our project have store rooms as per local Fire and safety compliance no electrical circuits and equipment's are allowed to this rooms

so can we exclude this kind of spaces from VRP calculation

VRP calculation is for Occupied area or all areas (Toilet, Storerooms)

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 02 2015 LEEDuser Expert 3629 Thumbs Up

The VRP calculation is for occupiable spaces. However, the credit applies to all requirements of ASHRAE 62.1 - 2007, including exhaust rates.

Post a Reply
0
0
kevin connolly
Oct 28 2015
Guest
6 Thumbs Up

Alternative Compliance in lieu of LEED Tables

Has anyone been successful using the alternative compliance path and submitting their own ASHRAE 62.1 calculation/spreadsheets in lieu of using the built in LEED or 62MZCalc form?

We would rather save time by not re-entering a ton of info and just provide a narrative and our calcs to prove we meet ASHRAE 62.1.

1
2
0
David Hubka Director - Operations, Transwestern Sustainability Services Oct 31 2015 LEEDuser Expert 2412 Thumbs Up

While we have not submitted our own EQp1 calculations in lieu of the 62MZ we have been told by GBCIThe Green Building Certification Institute (GBCI) manages Leadership in Energy and Environmental Design (LEED) building certification and professional accreditation processes. It was established in 2008 with support from the U.S. Green Building Council (USGBC). that non-62MZ calculations are acceptable.

As always, provide a detailed narrative explaining your methodology.

2
2
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Nov 02 2015 LEEDuser Expert 3629 Thumbs Up

I think that it is unlikely that the LEED reviewer will accept your own spreadsheet. They provide a spreadsheet for you to use. I think it would take longer for you to convince them that you calculated multiple zones with unused OA correctly than it would to just fill out their spreadsheet. I recommend using the provided 62MZcalc.

Post a Reply
0
0
SUMAC Inc. SUMAC
Oct 27 2015
Guest
196 Thumbs Up

source of air for mechanical Ventilation

Project Location: Peru

We have a project that is natural ventilated in perimeter spaces (circulations and cafe dining rooms), and It is mechanical ventilated in core spaces (meeting rooms and cafe dining room) that is pursuing LEED for NC 2009.
Our mechanical designer is wondering if the source of supply outdoor air can be an indoor natural ventilated space. What I mean is that we can locate the supply duct for the injector fan near to the operable window in the indoors?

Any help, please?

Thanks you!

Dante Garcia
LEED AP BD+C

1
1
0
Andrew Mitchell, P.E. Principal, Mitchell Gulledge Engineering, Inc. Oct 27 2015 LEEDuser Expert 3629 Thumbs Up

No, you cannot. The fresh air needs to come from outside.

Post a Reply
0
0
O Moltay
Oct 19 2015
LEEDuser Member
14 Thumbs Up

v2009v4_Minimum IAQ Performance Calculator_v02 - Any Experience?

Dear Members,

Do you any experience with the v2009v4_Minimum IAQIndoor air quality: The quality and attributes of indoor air affecting the health and comfort building occupants. IAQ encompasses available fresh air, contaminant levels, acoustics and noise levels, lighting quality, and other factors. Performance Calculator_v02 spreadsheet found under Credit Resources for IEQp1? Is this form suitable for showing compliance with Multiple Zone Systems in lieu of ASHRAE 62MZ calc spreadsheet?

Additionally, we are confused by some of the parameters when using the Appendix A method for VAVVariable Air Volume (VAV) is an HVAC conservation feature that supplies varying quantities of conditioned (heated or cooled) air to different parts of a building according to the heating and cooling needs of those specific areas. systems. When there is no secondary recirculation, shouldn't Er and Ep be "1"? However, the definition of Ep is given as Vpz / Vdz, in which case Vpz = Ds * Vdz for VAV systems representing minimum flow conditions. Therefore, shouldn't Ep be equivalent to Ds?

Thank you,

1
3
0
Joseph Snider, AIA, LEED Fellow LEED Architect, SEQUIL Systems, Inc. Oct 19 2015 LEEDuser Member 376 Thumbs Up

We recently had the opportunity to get some feedback from a USGBC reviewer on the new spreadsheet. Yes, this is the preferred calculator, instead of the older ASHRAE 62mz excel sheet and the template. This appears to be what they want to see going forward as it is better organized and the results tab makes it easier to review.

Note one item we found which is that on the SINGLE ZONE tab, the default occupancy isn't populating correctly. It pulls numbers from the wrong place. So you need to use manually entered occupancies. Apparently this is a known error and they are working on fixing it and re-releasing it.

I'll default to some of the more technical experts on the second part of your question.

2
3
0
O Moltay Oct 27 2015 LEEDuser Member 14 Thumbs Up

Yes, the single zone tab does not populate correctly. Additionally, the summary tab fails to display all input systems in our case. We contacted the GBCIThe Green Building Certification Institute (GBCI) manages Leadership in Energy and Environmental Design (LEED) building certification and professional accreditation processes. It was established in 2008 with support from the U.S. Green Building Council (USGBC). about this and they said that they did not know of this mistake before and that it is probably due to the fact we have gone back and forth in inputting multiple zone and %100 OA systems. So be careful when using this spreadsheet.

3
3
0
Jian Hui Liu Oct 28 2015 Guest 63 Thumbs Up

My project is outside of the US.Can't i use the spreadsheet?

Post a Reply
0
0
Jutta Berns-Mumbi principal ecocentric cc
Oct 09 2015
LEEDuser Member
1874 Thumbs Up

Engineered natural ventilation system

Project Location: South Africa

Hi all

We have three Warehouse's that use 'turbo ventilators' (wind driven extraction fans) and not a pure mechanical system. The warehouses also do not have enough enough openings to meet the natural ventilation requirements of 5.1 in ASHRAE 62.1.

To meet the requirements of IEQp1 I feel my only option is to motivate that the this is an 'Engineered natural ventilation system' as per the exception to 5.1 in ASHRAE 62.1. In the wording (and confirmed in CIRCredit Interpretation Ruling. Used by design team members experiencing difficulties in the application of a LEED prerequisite or credit to a project. Typically, difficulties arise when specific issues are not directly addressed by LEED information/guide ID#2539);

'An engineered natural ventilation system when approved by the authority having jurisdiction need not meet the requirements of Sections 5.1.1 and 5.1.2. '

South African building codes don't deal with turbo ventilators directly, and because warehouses do not have a minimum ventilation requirement here the designs/drawings were approved by the authority having jurisdiction (AHJ).

The issue is they would definitely be approved by AHJ because there is no minimum requirement.
But this is like simply using a less stringent code, which is not the intent.

How can I show compliance with IEQp1 for these areas?

1
3
0
Gustavo De las Heras Izquierdo Arch. Eng. LEED AP BD+C; O+M; CxA: Green Rater: EDGE Auditor, Revitaliza Consultores Oct 09 2015 Guest 1196 Thumbs Up

Does the cut-sheet show estimated cfm under normal conditions? Then, you might be able to complete the calculator and meet the minimum requirement.

2
3
0
Joseph Snider, AIA, LEED Fellow LEED Architect, SEQUIL Systems, Inc. Oct 19 2015 LEEDuser Member 376 Thumbs Up

We have used these types of systems in Colombia in similar warehouse applications. The walls also had louvers on them for intake. We provided basically an engineered natural ventilation analysis to show the projected air flow through the spaces, and compare it to the required amount by ASHRAE. Usually these systems, especially if there are openings on the side, bring in more than enough outdoor air.

3
3
0
Jutta Berns-Mumbi principal , ecocentric cc Oct 27 2015 LEEDuser Member 1874 Thumbs Up

Thanks for the responses. Sorry I took so long to reply.

Gustavo yes the cut-sheets show estimated cfm. But this is of course at an assumed wind speed over the roof.

Joseph was this approach accepted?

So in summary my approach would be to provide analysis that shows the ASHRAE 62.1 requirements are met rather than approved by AHJ because there is no requirement here.

Post a Reply

Start a new LEED comment thread

May 01 2016
Type the characters you see in this picture. (verify using audio)
Type the characters you see in the picture above; if you can't read them, submit the form and a new image will be generated. Not case sensitive.

Copyright 2016 – BuildingGreen, Inc.